background image

Instructions  RI8RE3ML   ©  Danfoss  10/2016 

   AK-CC 210A

1 2

3 4 

o61 — Electrical connections - Conexão elétrica

*) DI1, DI2:  

AU: Guld, Gold, Or, Oro  

l

 = max. 15 m

*)

*)

*)

*)

*)

*)

Summary of Contents for AK-CC 210A

Page 1: ... 6 A 10 A Resistive 5FLA 30LRA DO2 Defrost 8 6 A 10 A Resistive 5FLA 30LRA DO3 Refrigeration 2 6 3 A 6 A Resistive 3FLA 18LRA 131 VA Pilot duty DO4 Alarm light rail heat fan or comp fan 4 1 A Min 100 mA 4 A Resistive 131 VA Pilot duty DO1 and DO2 are 16 A relays DO3 and DO4 are 8 A relays Max load must be kept Gold plating ensures make function with small contact loads UL approval based on 30000 c...

Page 2: ...2 Instructions RI8RE3ML Danfoss 10 2016 AK CC 210A 1 2 3 4 5 o61 Electrical connections Conexão elétrica DI1 DI2 AU Guld Gold Or Oro l max 15 m ...

Page 3: ...ermostatfølere S4 100 S4 0 S3 r15 0 100 100 Aktivering af referenceforskydning r40 r39 OFF ON OFF Værdi for referenceforskydning aktiveres via r39 eller DI r40 50 0 K 50 0 K 0 0 K Alarm Forsinkelse på temperaturalarm A03 0 min 240 min 30 min Forsinkelse på døralarm A04 0 min 240 min 60 min Forsinkelse på temperaturalarm efter afrimning A12 0 min 240 min 90 min Høj alarmgrænse A13 50 0 C 50 0 C 8 0...

Page 4: ...ngen S4 100 S4 0 S3 o17 0 100 100 Indgangssignal på DI2 Funktion 0 ikke anvendt 1 status på DI2 2 dørfunktion med alarm ved åben 3 døralarm ved åben 4 afrimningsstart pulssignal 5 ekstern hovedafbryder 6 natdrift 7 skift reference r40 aktiveres 8 alarmfunktion ved sluttet 9 alarmfunktion ved åben 10 møbelrengøring pulssignal o37 0 10 0 Konfiguration af lysfunktionen relæ 4 1 ON under dagdrift 2 ON...

Page 5: ...eter 2 Tryk på øverste eller nederste knap og find hen til den parameter du vil indstille 3 Tryk på den midterste knap indtil vær dien for parameteren vises 4 Tryk på øverste eller nederste knap og find den nye værdi 5 Tryk igen på den midterste knap for at fastlåse værdien Udkoble alarmrelæ se alarmkode Kort tryk på den øverste knap Indstille temperaturen 1 Tryk på den midterste knap til tempera ...

Page 6: ...efrost A12 0 min 240 min 90 min High alarm limit A13 50 0 C 50 0 C 8 0 C Low alarm limit A14 50 0 C 50 0 C 30 0 C Alarm delay DI1 A27 0 min 240 min 30 min Alarm delay DI2 A28 0 min 240 min 30 min Signal for alarm thermostat S4 100 S4 0 S3 A36 0 100 100 Compressor Min ON time c01 0 min 30 min 0 min Min OFF time c02 0 min 30 min 0 min Time delay for cutin of comp 2 c05 0 sec 900 sec 5 sec Compressor...

Page 7: ... 100 Input signal on DI2 Function 0 not used 1 status on DI2 2 door function with alarm when open 3 door alarm when open 4 defrost start pulse signal 5 ext main switch 6 night operation 7 change reference activate r40 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal o37 0 10 0 Configuration of light function relay 4 1 ON during day operation 2 ON OFF via data c...

Page 8: ...arameter r01 is shown 2 Push the upper or the lower button and find that parameter you want to change 3 Push the middle button until the parameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to enter the value Cutout alarm relay receipt alarm see alarm code Push short the upper button Set temperature 1 Push the middle button until the...

Page 9: ...e alarme DI1 A27 0 min 240 min 30 min Atraso de alarme DI2 A28 0 min 240 min 30 min Sinal do termostato do alarme S4 100 S4 0 S3 A36 0 100 100 Compressor Tempo mínimo LIGADO c01 0 min 30 min 0 min Tempo mínimo DESLIGADO c02 0 min 30 min 0 min Tempo de atraso de ativação do comp 2 c05 0 sec 900 sec 5 sec O relé do compressor 1 deve ativar e desativar inversamente função NC c30 0 OFF 1 ON 0 OFF Temp...

Page 10: ...ando fe chado 9 função de alarme quando aberto 10 limpeza do expositor pressão de pulso o37 0 10 0 Configuração da função de luz relé 4 1 LIGADO durante a operação diurna 2 LIGADO DESLIGADO via comunicação de dados 3 segue a função de DI quando DI estiver selecionado para função de porta ou alarme da porta o38 1 3 1 Ativação do relé de luz somente se o38 2 o39 OFF ON OFF Tempo de aquecimento do tr...

Page 11: ... Há parada baseada no tempo d Degelo em andamento Primeiro resfria mento após degelo PS Senha requerida Configurar senha Os botões Programar menu 1 Pressione o botão superior até ser mos trado um parâmetro r01 2 Pressione o botão superior ou inferior e localize o parâmetro que deseja alterar 3 Pressione o botão intermediário até o valor de parâmetro ser mostrado 4 Pressione o botão superior ou inf...

Page 12: ...12 Instructions RI8RE3ML Danfoss 10 2016 AK CC 210A ...