6
Instructions RI8RE3ML © Danfoss 10/2016
AK-CC 210A
Setting:
1 Open parameter r12 and stop the regulation
2 Select electric connection based on the drawings on page 2
3 Open parameter o61 and set the electric connection number in it
4 Now select one of the preset settings from the table on the right-
hand side
5 Open parameter o62 and set the number for the array of preset-
tings
6 Open parameter r12 and start the regulation
7 Go through the survey of factory settings. Make any necessary
changes in the respective parameters.
8 For network. Set the address in o03 and then transmit it to the
gateway/system unit with setting o04.
Array 1-3: The settings in the grey fields will be changed
English
Parameters
Variant of AK-CC
Min.-
value
Max.-
value
Factory
setting
Actual
setting
Function
Codes
1
2
3
4
5
Normal operation
Temperature (set point)
---
-50.0°C
50.0°C
2.0°C
Thermostat
Differential
***
r01
0.0 K
20.0K
2.0 K
Max. limitation of setpoint setting
***
r02
-49.0°C
50°C
50.0°C
Min. limitation of setpoint setting
***
r03
-50.0°C
49.0°C
-50.0°C
Adjustment of temperature indication
r04
-20.0 K
20.0 K
0.0 K
Temperature unit (°C/°F)
r05
°C
°F
°C
Correction of the signal from S4
r09
-10.0 K
+10.0 K
0.0 K
Correction of the signal from S3
r10
-10.0 K
+10.0 K
0.0 K
Manual service, stop regulation, start regulation (-1, 0, 1)
r12
-1
1
0
Displacement of reference during night operation
r13
-20.0 K
20.0 K
0.0 K
Definition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3)
r15
0%
100%
100%
Activation of reference displacement r40
r39
OFF
ON
OFF
Value of reference displacement (activate via r39 or DI)
r40
-50.0 K
50.0 K
0.0 K
Alarm
Delay for temperature alarm
A03
0 min
240 min
30 min
Delay for door alarm
***
A04
0 min
240 min
60 min
Delay for temperature alarm after defrost
A12
0 min
240 min
90 min
High alarm limit
***
A13
-50.0°C
50.0°C
8.0°C
Low alarm limit
***
A14
-50.0°C
50.0°C
-30.0°C
Alarm delay DI1
A27
0 min
240 min
30 min
Alarm delay DI2
A28
0 min
240 min
30 min
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36
0%
100%
100%
Compressor
Min. ON-time
c01
0 min
30 min
0 min
Min. OFF-time
c02
0 min
30 min
0 min
Time delay for cutin of comp.2
c05
0 sec
900 sec
5 sec
Compressor relay 1 must cutin and out inversely
(NC-function)
c30
0
OFF
1
ON
0
OFF
Time delay for cutin of compressor 2 during defrost
c92
0 s
30 s
5 s
Defrost
Defrost method (none/EL/GAS)
d01
no
GAS
GAS
Defrost stop temperature
d02
0.0°C
25.0°C
6.0°C
Interval between defrost starts
d03
0 hours 240 hours 8 hours
Max. defrost duration
d04
0 min
360 min
45 min
Displacement of time on cutin of defrost at start-up
d05
0 min
240 min
0 min
Drip off time
d06
0 min
60 min
0 min
Delay for fan start after defrost
d07
0 min
60 min
0 min
Fan start temperature
d08
-50.0°C
0.0°C
-5.0°C
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
d09
0
2
1
Defrost sensor (0=time, 1=S5, 2=S4)
d10
0
2
0
Pump down delay
d16
0 min
60 min
0 min
Max. aggregate refrigeration time between two defrosts
d18
0 hours 48 hours 0 hours
Defrost on demand - S5 temperature’s permitted variation during frost build-up. On
central plant choose 20 K (=off)
d19
0.0 K
20.0 k
20.0 K
Max. duration of -d- in display
d40
5 min
240 min
30 min
Fan
Fan stop at cutout compressor
F01
no
yes
no
Delay of fan stop
F02
0 min
30 min
0 min
Fan stop temperature (S5)
F04
-50.0°C
50.0°C
50.0°C
Auxiliary table for settings
(quick-setup)
Defrost
stop on
time
Defrost stop
on S5
Preset settings
(o62)
1
2
3
Temperature (SP)
4°C
2°C
-24°C
Max. temp. setting (r02)
6°C
4°C
-22°C
Min. temp. setting (r03)
2°C
0°C
-26°C
Alarm limit high (A13)
10°C
8°C
-15°C
Alarm limit low (A14)
-5°C
-5°C
-30°C
Interval between defrost (d03)
6 h
6h
12h
Defrost sensor: 0=time,1=S5, 2=S4 (d10)
0
1
1
DI1 configuration (o02)
10
10
10