Determine the connection points
All connections must be programmed with module and point, so
in principle it does not matter where the connections are made, as
long as it takes place on a correct type of input or output.
• The controller is the first module, the next one is 2, etc.
• A point is the two or three terminals belonging to an input or
output (e.g. two terminals for a sensor and three terminals for a
relay).
The preparation of the connection diagram and the subsequent
programming (configuration) should take place at the present
time. It is most easily accomplished by filling in the connection
survey for the relevant modules.
Principle:
Name
On module
On Point
Function
fx Compressor 1
x
x
ON
fx Compressor 2
x
x
ON
fx Alarm relay
x
x
OFF
fx Main switch
x
x
Close
fx P0
x
x
AKS 32R 1-6 bar
The connection survey from the controller and any extension
modules are uploaded from the paragraph "Module survey. E.g.
controller module:
10
Signal
Module
Point
Terminal
Signal type /
Active at
1 (AI 1)
1 - 2
2 (AI 2)
3 - 4
3 (AI 3)
5 - 6
4 (AI 4)
7 - 8
Module Point
Mind the numbering.
The right-hand part of the
controller module may look like
a separate module. But it isn’t.
- Columns 1, 2, 3 and 5 are used for the programming.
- Columns 2 and 4 are used for the connection diagram.
Signal
Module
Point
Terminal
Signal
type /
Active at
Air temperature - Saux1
1
1 (AI 1)
1 - 2
Pt 1000
Air temperature - Saux2
2 (AI 2)
3 - 4
Pt 1000
3 (AI 3)
5 - 6
Air temperature - Saux3
4 (AI 4)
7 - 8
Pt 1000
5 (AI 5)
9 - 10
Voltage signal - U1
6 (AI 6)
11 - 12
0-10 V
Voltage signal - U2
7 (AI 7)
13 - 14
0-10 V
8 (AI 8)
19 - 20
9 (AI 9)
21 - 22
Pressure measurement -
Paux1, to 12 bar
10 (AI 10)
23 - 24
AKS 32R-12
Pressure measurement -
Paux2, to 34 bar
11 (AI 11)
25 - 26
AKS 32R-34
12 (DO 1)
31 - 32
13 (DO 2)
33 - 34
14 (DO 3)
35 - 36
15 (DO 4)
37 - 38
Relay for thermostat Saux3
16 (DO 5) 39 - 40 - 41
ON
Relay for voltage for signal U2
17 (DO6) 42 - 43 - 44
ON
Relay for pressostat Paux2
18 (DO7) 45 - 46 - 47
ON
Alarm relay
19 (DO8) 48 - 49 - 50
OFF
24
-
25
-
Tip
The Appendix shows 16 general installation types.
If your plant closely resembles one of those shown, you
can use the connection points indicated for it.
Signal
Module
Point
Terminal
Signal type /
Active at
Defrost DI1 for Saux2
2
1 (DI 1)
1 - 2
Closed
Appliance stopped DI2 for
Saux2
2 (DI 2)
3 - 4
Closed
Alarm signal DI3
3 (DI 3)
5 - 6
Closed
Alarm signal DI4
4 (DI 4)
7 - 8
Closed
5 (DI 5)
9 - 10
6 (DI 6)
11 - 12
7 (DI 7)
13 - 14
8 (DI 8)
15 - 16
Pulse signal - E
3
1 (CI 1)
1 - 2
- - -
2 (CI 2)
3 - 4
3 (CI 3)
5 - 6
4 (CI 4)
7 - 8
5 (CI 5)
9 - 10
6 (CI 6)
11 - 12
7 (cI 7)
13 - 14
8 (cI 8)
15 - 16