60
RS8FR302 © Danfoss 2015-08
AK-LM
330
Check configuration
1. Go to Configuration menu
2. Select I/O configuration
3. Check configuration of Digital Outputs
Press the +-button to go on to the next page
4. Check configuration of Digital Inputs
Press the +-button to go on to the next page
5. Check configuration of Analog inputs
Configuration - continued
This control requires that the setup is locked
(Only when the setup is locked are all settings for in- and out-
puts activated.)
An error has occurred, if you see the fol-
lowing:
A 0 – 0 next to a defined function.
If a setting has reverted to 0-0, you must control
the setup again.
This may be due to the following:
• A selection has been made of a combination of
module number and point number that does
not exist.
• The selected point number on the selected mod-
ule had been set up for something different.
The error is corrected by setting up the output
correctly.
Remember that the setup must be unlocked be-
fore you can change module and point numbers..
The settings are shown on a RED background.
If a setting has turned red, you must control the
setup again.
This may be due to the following:
• The input or the output has been set up; but the
setup has later been changed so that it should
no longer be applied.
The problem is corrected by setting module
number to 0 and point number to 0.
Remember that the setup must be unlocked be-
fore you can change module and point numbers.
The setup of the digital
inputs appears as it is sup-
posed to according to the
wiring made.
The setup of the digital
outputs appears as it is sup-
posed to according to the
wiring made.
The setup of the analog
inputs appears as it is sup-
posed to according to the
wiring made.