PC, Modem or server con-
nection
(Only handshake signals DTR and CTS can be used)
The PC can stop the communication from AKA 245.
AKA 245 cannot stop communica tion from the PC.
The connection is made with a screened cable, wire diameter = 0.25 mm.
The screen is only connected to the plug at one end.
The length of the cable must not exceed 15 m.
A PC, a modem or a TCP/IP server can be connected to the RS232 plug. A setting in the gateway deter-
mines the application.
Warning!
In order not to destroy the output on the PC, the modem or the server the following precautions must be
taken:
- Establish the correct earth connection on AKA 245
- Interrupt the supply voltage to the gateway and to the PC / the Modem / the server, when the cable is
mounted and dismounted.
PC to gateway
Check whether the PC has a 9-pole or a 25-pole plug for this connection. A 3 m cable with plugs fi tted
can be supplied. See Ordering. If the cable has to be longer than 3 m, mount it based on the following
instructions:
10
Manual RS8DT102 © Danfoss 09/2004
AKA
245