Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
AKD
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
5001
KTN-R10
5017906-010
KLN-R10
ATM-R10 or A2K-10R
5002
KTN-R10
5017906-010
KLN-R10
ATM-R10 or A2K-10R
5003
KTN-R25
5017906-016
KLN-R15
ATM-R15 or A2K-15R
5004
KTN-R20
5017906-020
KLN-R20
ATM-R20 or A2K-20R
5005
KTN-R25
5017906-025
KLN-R25
ATM-R25 or A2K-25R
5006
KTN-R30
5012406-032
KLN-R30
ATM-R30 or A2K-30R
5008
KTN-R50
5014006-050
KLN-R50
A2K-50R
5011
KTN-R60
5014006-063
KLN-R60
A2K-60R
5016
KTN-R85
5014006-080
KLN-R80
A2K-80R
5022
KTN-R125
2028220-125
KLN-R125
A2K-125R
5027
KTN-R125
2028220-125
KLN-R125
A2K-125R
380-500 V
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
5001
KTS-R6
5017906-006
KLS-R6
ATM-R6 or A6K-6R
5002
KTS-R6
5017906-006
KLS-R6
ATM-R6 or A6K-6R
5003
KTS-R10
5017906-010
KLS-R10
ATM-R10 or A6K-10R
5004
KTS-R10
5017906-010
KLS-R10
ATM-R10 or A6K-10R
5005
KTS-R15
5017906-016
KLS-R16
ATM-R16 or A6K-16R
5006
KTS-R20
5017906-020
KLS-R20
ATM-R20 or A6K-20R
5008
KTS-R25
5017906-025
KLS-R25
ATM-R25 or A6K-25R
5011
KTS-R30
5012406-032
KLS-R30
A6K-30R
5016
KTS-R40
5012406-040
KLS-R40
A6K-40R
5022
KTS-R50
5014006-050
KLS-R50
A6K-50R
5027
KTS-R60
5014006-063
KLS-R60
A6K-60R
5032
KTS-R80
2028220-100
KLS-R80
A6K-180R
5042
KTS-R100
2028220-125
KLS-R100
A6K-100R
5052
KTS-R125
2028220-125
KLS-R125
A6K-125R
5062
KTS-R150
2028220-160
KLS-R150
A6K-150R
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
AKD 5001-5027
200-240 V
type gG
AKD 5001-5062
380-500 V
type gG
AKD 5032-5052
200-240 V
type gR
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
rms