AKD 5000
Programming
■
Parameters — Technical functions and
Parameter no.
Description
Operating data
Display text
Unit
Range
600
Operating hours
(OPERATING
HOURS)
Hours
0 - 130,000.0
601
Hours run
(RUNNING HOURS)
Hours
0 - 130,000.0
602
kWh counter
(KWH COUNTER)
kWh
0 - 9999
603
No. of cut-ins
(POWER UP
’
s)
Nos.
0 - 9999
604
No. of overtemps
(OVER TEMP
’
s)
Nos.
0 - 9999
605
No. of overvoltages
(OVER VOLT
’
S)
Nos.
0 - 9999
Function:
These parameters can be read out via the
serial communication port and via the display
in the parameters.
Description of choice:
Operating hours, parameter 600:
Indicates the number of hours in which the frequency
converter has been in operation.
The value is updated in the frequency converter every
hour and saved when the unit is turned off.
Hours run, parameter 601:
Indicates the number of hours in which the
frequency converter has been in operation since
reset in parameter 619.
The value is updated in the frequency converter every
hour and saved when the unit is turned off.
kWh counter, parameter 602:
States the power consumption from mains in
kWh as a mean value over one hour. Reset
counter: Parameter 618.
No. of cut-ins, parameter 603:
States the number of power-ups of the supply
voltage to the frequency converter.
No. of overtemps, parameter 604:
States the number of temperature faults there has
been on the frequency converter.
No. of overvoltages, parameter 605:
States the number of overvoltages there has
been on the frequency converter.
Parameter no.
Description
Data log
Display text
Unit
Range
606
Digital inputs
(LOG: DIGITAL INP)
Decimal
0 - 255
607
Control word
(LOG: CONTROL
WORD
Decimal
0 - 65535
608
Status word
(LOG: BUS STAT WD)
Decimal
0 - 65535
609
Reference
(LOG: REFERENCE)
%
0 - 100
610
Feedback
(LOG: FEEDBACK)
Par. 416
999,999.99 -
999,999.99
611
Output frequency
(LOG: MOTOR
FREQ.)
Hz.
0.0 - 999.9
612
Output voltage
(LOG: MOTOR VOLT)
Volt
50 - 1000
613
Output current
(LOG: MOTOR
CURR.)
Amp
0.0 - 999.9
614
DC link voltage
(LOG: DC LINK VOLT)
Volt
0.0 - 999.9
Function:
Via this parameter it is possible to see up to 20
data-logs, where [0] is the latest log and [19] the
oldest. Each data-log is made every 160 ms as long
as a start signal has been given. If a stop signal is
given, the latest 20 data-logs will be saved and the
values will be available on the display. This is useful,
e.g. when carrying out service after a trip.
This parameter can be read out via the serial
communication port or via the display.
Description of choice:
The data-log number is stated in square brackets: [1].
Data-logs are frozen if there is a trip and released when
the frequency converter is subsequently reset.
Data-logging is active while the motor is running.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -