Danfoss District Energy 

VI.GP.V2.02 

DKDHR

Instructions 

 

 

Akva Lux II VX3 

12.3  Akva Lux II VX3 (ECL210/A260)

Substation for indirect heating for single-family, semi-detatched 

and terraced houses as well as flats. With two heating circuits and 

instantaneous domestic water heater. Designed for wall-mounting 

with connections in top and bottom of substation.

The temperature for the heating circuits is controlled by a Danfoss ECL 

310 controller in combination with electronic actuators. The supply 

temperature is calculated by the controller on basis of the outdoor 

temperature.

Please note: 

Your substation may look different than the substation shown, as vari-

ants with other components may be supplied. 

Instructions for the fitted components will always be supplied to-

gether with the substation.

Heating circuit

The temperature for the heating circuit is controlled electronically by 

the Danfoss ECL controller. The supply temperature ist calculated by 

the controller on basis of the outdoor temperature.

The ECL Comfort 310 controller is loaded with a selected application 

by means of an ECL Application Key (Plug-&-Play). The Application 

Key contains information about application, languages and factory 

settings. 

The controller is factory preset to turn off the heating automatically 

in the summer period.

The controller settings can be changed in accordance with the en-

closed producer instructions for the mounted controller.

See ECL Application Key Box with ECL Comfort 210/310 user guide 

and mounting guide, for further information.

 

Control of heating circuit 1

For control of heating circuit 1 the Akva Lux II VX3 (ECL 310) is supplied 

with a 2-way valve VS 2 and an electrical actuator AMV 150, which 

in combination with the ECL controller controls the heating circuit. 

The electrical actuator has undergone a functional test from factory. 

In case of operating disturbances the actuator can be closed manu-

ally  turning the manual override knob on top of actuator counter-

clockwise.

Please see enclosed instructions,

Electrical actuator AMV 150

2-way valve VS 2

Manual override (AMV 150)

7369267-9  SIBC R&D

EI.97.Q2.00 © Danfoss 12/01

1

INSTRUCTIONS

VS2    2-way

065R9075

065R9075

DN

L (mm)

15

65

20

70

25

75

DN

L

1

(mm)

15

131

20

142

25

159

DN

L

2

(mm)

15

139

20

154

25

159

DN

L

3

(mm)

15

69

20

74

25

79

Instructions

AMV 150

73691180 DH-SMT/SI

 

VI.KU.N2.1J © Danfoss 01/2008 

1

ENglIsh

 Actuators for three point control AMV 150

www.danfoss.com

Page 2

DANsK

 Motorer til 3-punkts styring AMV 150

www.danfoss.dk

Side 3

DEUTsCh

 Stellantriebe für 3-Pkt.- Eingangssignal AMV 150

www.danfoss.de

Seite 3

sVENsKA

 Motor för 3-punktsreglering AMV 150

varme.danfoss.se

Sida 4

NEDERlANDs

 Servomotor met 3-puntssturing AMV 150

www.danfoss.nl

Pagina 4

lIETUVIŲ K.

 Pavaros trijų padėčių valdymui AMV 150

www.danfoss.lt

5 puslapis

lATVIsKI

Motori trīs punktu kontrolei AMV 150

www.danfoss.com

Lpp. 5

MAgYAR

Szelepmozgatók hárompontos szabályozáshoz AMV 150

www.danfoss.com

6. oldal 

ČEsKY

 Servopohony s tříbodovým regulačním signálem AMV 150

www.danfoss.cz

Strana 6

POlsKI

 Siłowniki sterowane sygnałem 3-punktowym AMV 150

www.danfoss.pl

Strona 7

РУССКИЙ

 Электроприводы для трехпозиционного регулирования AMV 150

www.danfoss.ru

Страница 7

 

AMV 150 + 

AMV 150 + 

AMV 150 + 

 

VS2 (DN 15) 

VMV 

AVQM (DN 15)

VS 2

Press and hold the button (on 

the bottom side of the actuator) 

during manual override.

Summary of Contents for Akva Lux II VX Series

Page 1: ...Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Lux II VX2 VX2 E VX3 VX3 E Instructions for installation and use...

Page 2: ...Safety thermostat 15 8 4 Expansion vessel 16 8 5 Heat meter Fitting piece 17 8 6 Test and connections 17 8 7 Mounting of outdoor temperature sensor 17 8 8 Safety valves 17 9 0 Filling Start up 18 10 0...

Page 3: ...re The maximum supply temperature in the district heating network can be up to 110 C and the operating pressure can be up to 16 bar This may result in a risk of scalding from touching the substation a...

Page 4: ...sions with cover H780 x W550 x D380 mm Connections Order 1 District heating DH supply 2 District heating DH return 4 Heating HE return 5 Heating HE supply 6 Domestic hot water DHW 7 Domestic cold wate...

Page 5: ...Order 1 District heating DH supply 2 District heating DH return 4 Heating HE return 5 Heating HE supply 6 Domestic hot water DHW 7 Domestic cold water DCW top view wall Connection sizes DH G ET HE G E...

Page 6: ...nections Order 1 District heating DH supply 2 District heating DH return 3 Heating HE return 4 Heating HE supply 5 Heating HE return 6 Heating HE supply 7 Domestic hot water DHW 8 Domestic cold water...

Page 7: ...tions Order 1 District heating DH supply 2 District heating DH return 3 Heating HE return 4 Heating HE supply 5 Heating HE return 6 Heating HE supply 7 Domestic hot water DHW 8 Domestic cold water DCW...

Page 8: ...bilities as con nection of pipes can be established both in the top or in the bottom of the substation Please note Your substation may look different than the substation shown as vari ants with other...

Page 9: ...tom of the substation Please note Your substation may look different than the substation shown as vari ants with other components may be supplied The control function however is basically as stated in...

Page 10: ...meter 25 Electronic controller ECL 310 260 29 Actuator AMV 150 30 2 way valve VS2 38 PTC2 P controller 40 Danfoss thermostat for bypass circulation The substations offer variable connection possibili...

Page 11: ...ure controller 20 Switch box for pumps 22 Safety thermostat 21 Flowswitch 24 Fitting piece for heat meter 25 Electronic controller ECL 310 A376 29 Actuator AMV 150 30 2 way valve VS2 31 Actuator AMV 3...

Page 12: ...m overstrain of union nuts 8 On systems that feature a safety valve establish a drain con nection in compliance with the applicable legislation 9 SettemperatureforATsafetythermostatforfloororradiatorh...

Page 13: ...substation is prepared for mounting of the ball valves for DH supply and return as well as the ball valves for HE supply and return in top of the substation and for mounting of the ball valves for DH...

Page 14: ...Assemble the circulation set as illustrated in fig 2b and re member to use packing yarn when packing the hexagon nipple non return valve in the 5 4 pump union piece and make sure that the arrow on th...

Page 15: ...ostat is used to regulate the medium temperature in the pipe on which the thermostat is mounted AT senses the tempera ture in the pipe through its contact surface and is therefore suitable to control...

Page 16: ...substation either in the top or in the bottom of the substation oppositely to the pipes connection which can be established both in the top or in the bottom of the substation Mount the expansion vess...

Page 17: ...necessary Please note that the connections may feature EPDM rubber gaskets Therefore it is important that you DO NOT OVERTIGHTEN the union nuts Over tightening may result in leaks Leaks caused by over...

Page 18: ...the system with water and at the same time vent the system Fill heat exchanger the system with water until the mano meter shows a working pressure which corresponds to the system height 5 m approx 1 2...

Page 19: ...r supply connection must be carried out in accordance with the applicable regulations and instructions The station must be wired and connected to an external main switch so that it can be turned off d...

Page 20: ...which in combination with the ECL controller controls the heating circuit The electrical actuator has undergone a functional test from factory In case of operating disturbances the actuator can be clo...

Page 21: ...or Akva Lux II VX2 switching to recirculation is possible from a constructional point of view requiring only an additional circula tion set The circulation set is not included in the delivery and must...

Page 22: ...ormation Control of heating circuit For control of heating circuit 1 the Akva Lux II VX2 E ECL 310 is supplied with a 2 way valveVS 2 and an electrical actuator AMV 150 which in combination with the E...

Page 23: ...iler or flow tem perature in central heating systems The AT pipe thermostat comprises a bimetallaic sensor a contact system and a setting knob On connection to terminals CO and NC the ther mostat brea...

Page 24: ...ectrical actuator AMV 30 2 way valve VM2 DHW recirculation Substations with electronic control of the domestic hot water circuit are prefabricated for DHW recirculation The circulation set is supplied...

Page 25: ...Control of heating circuit 1 For control of heating circuit 1 the Akva Lux IIVX3 ECL 310 is supplied with a 2 way valve VS 2 and an electrical actuator AMV 150 which in combination with the ECL contr...

Page 26: ...w danfoss lt 5 puslapis lATVIsKI Motori tr s punktu kontrolei AMV 150 www danfoss com Lpp 5 MAgYAR Szelepmozgat k h rompontos szab lyoz shoz AMV 150 www danfoss com 6 oldal EsKY Servopohony s t bodov...

Page 27: ...ould never exceed 55 C to avoid lime scale precipitation Bypass or circulation thermostat Bypass thermostat default AsastandardtheAkvaLuxIIVX3isequippedwithabypassthermostat Danfoss FJVR 2 which ensur...

Page 28: ...substation Heating circuit The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller The supply temperature ist calculated by the controller on basis of the o...

Page 29: ...sreglering AMV 150 varme danfoss se Sida 4 NEDERlANDs Servomotor met 3 puntssturing AMV 150 www danfoss nl Pagina 4 lIETUVI K Pavaros trij pad i valdymui AMV 150 www danfoss lt 5 puslapis lATVIsKI Mot...

Page 30: ...nsor a contact system and a setting knob On connection to terminals CO and NC the ther mostat breaks on a rise in temperature On connection to terminals CO and NO the ther mostat close on a rise in te...

Page 31: ...nation with the ECL controller controls the domes tic hot water circuit The controller closes when set max flow is exceeded The electrical actuator has undergone a functional test from fac tory Please...

Page 32: ...aspassedthepumpsmustbesetaccordingtotheaboveinstructions For more information please refer to enclosed installation and ope rating instructions WiloYonosPara Installationandoperatinginstructions Insta...

Page 33: ...Wilo Star Z NOVA circulation pump Substation start up setting of pump The pump is electrically connected to the ECL controller from factory and needs no start up adjustment For information about venti...

Page 34: ...acid Measures after maintenance work After maintenance work and before commissioning Check that all screwed connections are tight Check that all safety features covers that were removed have been rep...

Page 35: ...replace gaskets and tighten connections Check the functions of the safety valve on the DCW inlet pipe Check the functions of the safety valves by turning the valve head of the safety valve General vi...

Page 36: ...required Defective sensor Replace sensor Defektive actuator Check the functioning of the actuator Defective motor valve or possibly dirt in the valve housing Check the functions of the motor valve cl...

Page 37: ...r cooling Strainer clogged Clean strainer Too small heating surface too small radiators compared to the total heating requirement of the building Increase total heating surface Poor utilization of exi...

Page 38: ...heat exchanger with acid solution or replace plate heat exchanger Not enough pressure on the hot water Strainer in cold water meter clogged Clean strainer possibly in consultation with the water supp...

Page 39: ...t and capillary tubes if required air and rinse capillary tubes Automatic controls wrongly set Check that the controller has been cor rectly set see separate instructions Calified plate heat exchanger...

Page 40: ...7 Electromagnetic compatibility Generic standard Immunity for residential commercial and light industry EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3...

Page 41: ...41 41 Danfoss District Energy VI GP V2 02 DKDHR Instructions Akva Lux II VX...

Page 42: ...42 DKDHR VI GP V2 02 Danfoss District Energy Instructions Akva Lux II VX...

Page 43: ...43 43 Danfoss District Energy VI GP V2 02 DKDHR Instructions Akva Lux II VX...

Page 44: ...Produced by Danfoss Redan A S 05 2013 VI GP V2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: