background image

33

Danfoss District Energy 

VI.GP.V2.02 

DKDHR

Instructions 

 

 

Akva Lux II VX

2.0  Safety notes

Instructions

This operating manual should be read carefully before installation and 

start-up of the substation. The manufacturer accepts no liability for 

damage or faults that result from non-compliance with the operating 

manual.

Please read and follow all the instructions carefully to prevent acci-

dents, injury and damage to property. The risk of persons being injured 

and equipment damaged increases considerably if the recommended 

permissible operating parameters are exceeded. 

Installation, assembly work, first start-up and maintenance work may 

be carried out only by qualified and authorized personnel in compli-

ance with the safety regulations (both heating and electrical work).

Energy source

The substation is designed for district heating as the primary source 

of energy. However, also other energy sources can be used where the 

operating conditions allow it and always are comparable to district 

heating.

Application

The substation is designed only to operate with water or a water-glycol 

mixture (up to 40%), and other heating media may not be used.   

Connect the substation to the house installation in a frost-free room,  

where the temperature does not exceed 50 °C and the humidity does 

not exceed 80%. Do not cover or wall up the substation or in any other 

way block the entrance to the station.

Choice of material

Choice of materials always in compliance with local legislation.

Corrosion protection

The maximum chloride compounds of the flow medium should not 

be higher than 300 mg/l. The risk of equipment corrosion increases 

considerably if the recommended permissible chloride compounds 

are exceeded.

Safety valve(s)

We recommend mounting of safety valve(s), however, always in com-

pliance with local regulations.

Sound level.

 ≤ 55 dB.

Connection

The substation must be equipped with features that ensure that the 

substation can be separated from all energy sources (also power 

supply).

Warning! Hot surfaces

Parts of the substation may be very hot and can cause burn inju-

ries. Be very careful when you are in the immediate vicinity of the 

substation.

Warning of high pressure and high temperature

The maximum supply temperature in the district heating network 

can be up to 110°C and the operating pressure can be up to 16 bar. 

This may result in a risk of scalding from touching the substation 

and from outflow of the medium (water/steam). Exceeding the 

substation design data and operating parameters for pressure and 

temperature carries an appreciable risk of personal injury and/or 

damage to property.

Emergencies 

In the event of fire, leaks or other hazards, immediately shut off all 

sources of energy to the substation, if possible and call for appropri-

ate assistance. If the domestic hot water is discoloured or malodo-

rous, shut off all ball valves on the substation, notify all users and call 

for professional assistance immediately.

Warning of damage during transport 

On reception of the substation, and before installing it, check for 

any evidence of damage during transport.

The substation must be handled and moved with the greatest care 

and attention.

IMPORTANT - Tightening of connections 

Before adding water to the system, ALL pipe connections MUST be 

retightened, as vibrations during transport may have caused leaks. 

Once the substation has been filled and the system has been put 

into operation, ALL connections must be tightened once more. 

(Do not overstrain! - See item 8.6, page 17)

3.0   Storage and Handling

Before installation, the units must be stored in a dry, heated (i.e. frost-

free) room.

(Relative humidity max. 80% and storage temperature 5-70 °C).

The units must not be stacked higher than the limit at the factory . Units 

supplied in cardboard packaging must be lifted using the handles incor-

porated in the packaging. Units must be placed on pallets for transport/

moving across large distances.

As far as possible, do not lift the substation by the pipes. Lifting by the 

pipes may cause leaks. REMEMBER to retighten.

Handling

We recommend minimum two people to lift the substation.

We recommend that you wear suitable safety footwear while 

handling and installing the substation.

4.0   Disposal

Dispose of the packaging in accordance with the local regulations for 

disposal of used packaging materials.
The substation is made of materials that cannot be disposed of together 

with household waste.  

Close all energy sources and disconnect all connection pipes. Disconnect 

and dismantle the product for disposal in accordance with the applicable 

local regulations for the disposal of the individual components.

Summary of Contents for Akva Lux II VX Series

Page 1: ...Danfoss District Energy MAKING MODERN LIVING POSSIBLE Akva Lux II VX2 VX2 E VX3 VX3 E Instructions for installation and use...

Page 2: ...Safety thermostat 15 8 4 Expansion vessel 16 8 5 Heat meter Fitting piece 17 8 6 Test and connections 17 8 7 Mounting of outdoor temperature sensor 17 8 8 Safety valves 17 9 0 Filling Start up 18 10 0...

Page 3: ...re The maximum supply temperature in the district heating network can be up to 110 C and the operating pressure can be up to 16 bar This may result in a risk of scalding from touching the substation a...

Page 4: ...sions with cover H780 x W550 x D380 mm Connections Order 1 District heating DH supply 2 District heating DH return 4 Heating HE return 5 Heating HE supply 6 Domestic hot water DHW 7 Domestic cold wate...

Page 5: ...Order 1 District heating DH supply 2 District heating DH return 4 Heating HE return 5 Heating HE supply 6 Domestic hot water DHW 7 Domestic cold water DCW top view wall Connection sizes DH G ET HE G E...

Page 6: ...nections Order 1 District heating DH supply 2 District heating DH return 3 Heating HE return 4 Heating HE supply 5 Heating HE return 6 Heating HE supply 7 Domestic hot water DHW 8 Domestic cold water...

Page 7: ...tions Order 1 District heating DH supply 2 District heating DH return 3 Heating HE return 4 Heating HE supply 5 Heating HE return 6 Heating HE supply 7 Domestic hot water DHW 8 Domestic cold water DCW...

Page 8: ...bilities as con nection of pipes can be established both in the top or in the bottom of the substation Please note Your substation may look different than the substation shown as vari ants with other...

Page 9: ...tom of the substation Please note Your substation may look different than the substation shown as vari ants with other components may be supplied The control function however is basically as stated in...

Page 10: ...meter 25 Electronic controller ECL 310 260 29 Actuator AMV 150 30 2 way valve VS2 38 PTC2 P controller 40 Danfoss thermostat for bypass circulation The substations offer variable connection possibili...

Page 11: ...ure controller 20 Switch box for pumps 22 Safety thermostat 21 Flowswitch 24 Fitting piece for heat meter 25 Electronic controller ECL 310 A376 29 Actuator AMV 150 30 2 way valve VS2 31 Actuator AMV 3...

Page 12: ...m overstrain of union nuts 8 On systems that feature a safety valve establish a drain con nection in compliance with the applicable legislation 9 SettemperatureforATsafetythermostatforfloororradiatorh...

Page 13: ...substation is prepared for mounting of the ball valves for DH supply and return as well as the ball valves for HE supply and return in top of the substation and for mounting of the ball valves for DH...

Page 14: ...Assemble the circulation set as illustrated in fig 2b and re member to use packing yarn when packing the hexagon nipple non return valve in the 5 4 pump union piece and make sure that the arrow on th...

Page 15: ...ostat is used to regulate the medium temperature in the pipe on which the thermostat is mounted AT senses the tempera ture in the pipe through its contact surface and is therefore suitable to control...

Page 16: ...substation either in the top or in the bottom of the substation oppositely to the pipes connection which can be established both in the top or in the bottom of the substation Mount the expansion vess...

Page 17: ...necessary Please note that the connections may feature EPDM rubber gaskets Therefore it is important that you DO NOT OVERTIGHTEN the union nuts Over tightening may result in leaks Leaks caused by over...

Page 18: ...the system with water and at the same time vent the system Fill heat exchanger the system with water until the mano meter shows a working pressure which corresponds to the system height 5 m approx 1 2...

Page 19: ...r supply connection must be carried out in accordance with the applicable regulations and instructions The station must be wired and connected to an external main switch so that it can be turned off d...

Page 20: ...which in combination with the ECL controller controls the heating circuit The electrical actuator has undergone a functional test from factory In case of operating disturbances the actuator can be clo...

Page 21: ...or Akva Lux II VX2 switching to recirculation is possible from a constructional point of view requiring only an additional circula tion set The circulation set is not included in the delivery and must...

Page 22: ...ormation Control of heating circuit For control of heating circuit 1 the Akva Lux II VX2 E ECL 310 is supplied with a 2 way valveVS 2 and an electrical actuator AMV 150 which in combination with the E...

Page 23: ...iler or flow tem perature in central heating systems The AT pipe thermostat comprises a bimetallaic sensor a contact system and a setting knob On connection to terminals CO and NC the ther mostat brea...

Page 24: ...ectrical actuator AMV 30 2 way valve VM2 DHW recirculation Substations with electronic control of the domestic hot water circuit are prefabricated for DHW recirculation The circulation set is supplied...

Page 25: ...Control of heating circuit 1 For control of heating circuit 1 the Akva Lux IIVX3 ECL 310 is supplied with a 2 way valve VS 2 and an electrical actuator AMV 150 which in combination with the ECL contr...

Page 26: ...w danfoss lt 5 puslapis lATVIsKI Motori tr s punktu kontrolei AMV 150 www danfoss com Lpp 5 MAgYAR Szelepmozgat k h rompontos szab lyoz shoz AMV 150 www danfoss com 6 oldal EsKY Servopohony s t bodov...

Page 27: ...ould never exceed 55 C to avoid lime scale precipitation Bypass or circulation thermostat Bypass thermostat default AsastandardtheAkvaLuxIIVX3isequippedwithabypassthermostat Danfoss FJVR 2 which ensur...

Page 28: ...substation Heating circuit The temperature for the heating circuit is controlled electronically by the Danfoss ECL controller The supply temperature ist calculated by the controller on basis of the o...

Page 29: ...sreglering AMV 150 varme danfoss se Sida 4 NEDERlANDs Servomotor met 3 puntssturing AMV 150 www danfoss nl Pagina 4 lIETUVI K Pavaros trij pad i valdymui AMV 150 www danfoss lt 5 puslapis lATVIsKI Mot...

Page 30: ...nsor a contact system and a setting knob On connection to terminals CO and NC the ther mostat breaks on a rise in temperature On connection to terminals CO and NO the ther mostat close on a rise in te...

Page 31: ...nation with the ECL controller controls the domes tic hot water circuit The controller closes when set max flow is exceeded The electrical actuator has undergone a functional test from fac tory Please...

Page 32: ...aspassedthepumpsmustbesetaccordingtotheaboveinstructions For more information please refer to enclosed installation and ope rating instructions WiloYonosPara Installationandoperatinginstructions Insta...

Page 33: ...Wilo Star Z NOVA circulation pump Substation start up setting of pump The pump is electrically connected to the ECL controller from factory and needs no start up adjustment For information about venti...

Page 34: ...acid Measures after maintenance work After maintenance work and before commissioning Check that all screwed connections are tight Check that all safety features covers that were removed have been rep...

Page 35: ...replace gaskets and tighten connections Check the functions of the safety valve on the DCW inlet pipe Check the functions of the safety valves by turning the valve head of the safety valve General vi...

Page 36: ...required Defective sensor Replace sensor Defektive actuator Check the functioning of the actuator Defective motor valve or possibly dirt in the valve housing Check the functions of the motor valve cl...

Page 37: ...r cooling Strainer clogged Clean strainer Too small heating surface too small radiators compared to the total heating requirement of the building Increase total heating surface Poor utilization of exi...

Page 38: ...heat exchanger with acid solution or replace plate heat exchanger Not enough pressure on the hot water Strainer in cold water meter clogged Clean strainer possibly in consultation with the water supp...

Page 39: ...t and capillary tubes if required air and rinse capillary tubes Automatic controls wrongly set Check that the controller has been cor rectly set see separate instructions Calified plate heat exchanger...

Page 40: ...7 Electromagnetic compatibility Generic standard Immunity for residential commercial and light industry EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3...

Page 41: ...41 41 Danfoss District Energy VI GP V2 02 DKDHR Instructions Akva Lux II VX...

Page 42: ...42 DKDHR VI GP V2 02 Danfoss District Energy Instructions Akva Lux II VX...

Page 43: ...43 43 Danfoss District Energy VI GP V2 02 DKDHR Instructions Akva Lux II VX...

Page 44: ...Produced by Danfoss Redan A S 05 2013 VI GP V2 02 Danfoss Redan A S District Energy Omega 7 S ften DK 8382 Hinnerup Tel 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Reviews: