AME 10, AME 11

ENGLISH

Safety Notes

To avoid injury of persons and 
damages to the device, it is absolutely 
necessary to read and observe these 

instructions carefully.

Necessary assembly, start-up, and maintenance 
work must be performed by qualified and 
authorized personnel only.

Please comply with the instructions of the 
system manufacturer or system operator.

Disposal instruction

This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal.

Always follow the local disposal regulations.

Mounting 

Fix the actuator on the valve.
Wiring 

Control signal

Control signal from the controller must be 
connected to terminals Y (input signal) and SN 
(common) on the AME printed board.

Output signal

Output signal from the terminal X can be used 
for indication of the current position. Range 
depends on the DIP switch settings.

Supply voltage

Supply voltage (24 V~ −15 to +10 %, 50/60 Hz) 
must be connected to the terminals SN and SP.

DIP switch settings 

U

I

2 V_--- V

0 V_--- V

Direct

Inverse

---

Sequential

0(2)_5(6) V

5(6)_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % k

VS

RED. k

VS

Reset

Reset

  Factory settings: 

ALL switches are on OFF position! 

 

Note:

 All combinations of DIP switches are 

allowed. All functions that are selected are 
added consecutively. There is only one logic 
override of functionalities i.e. the switch No.6 
Proportional / 3 point, which sets actuator to 
ignore control signal and works as a “simple” 
3-point actuator.

SW1:   U/I 

Actuator can responde to a voltage or current 
control signal. With switch No.1: U/I actuator can 
be set either to operate with a voltage control 
signal (actuator responds to signal between 
0-10 V), or current control signal (actuator 
responds to signal between 0-20 mA).

 

Factory setting: 
voltage control signal (0-10 V).

SW2:  2 V-10 / 0 V-10 

Actuator can be set to response on a control 
signal from 2 V, or 0 V. If the actuator is set to 
current signal then it responds to control signal 
from 4 mA or 0 mA.

  Factory setting is: 

2-10 V.

SW3:   Direct/Inverse 

Actuator can be set for spindle to travel 
downwards on rising control signal (DIRECT), OR 
for spindle to travel upwards on rising control 
signal (INVERSE).

  Factory setting is: 

DIRECT

SW4:   ---/Sequential 

Two actuators can be set to work parallel with 
one control signal. If the SEQUENTIAL is set then 
an actuator responds to split control signal (see 
0(2)-5(6) V/ 6(6)-10 V).

 

Note: 

This combination works in combination 

with switch No.5: 0(2)-5(6) V/ 6(6)-10 V

SW5:  0(2)-5(6) V/6(6)-10 V 

 

Note:

 

This function is available if 

switch No.4:  
--- / Sequential is set.

SW6:  Proportional/3 point 

Actuator needs to perform Self 
stroking prior changing DIP 6 to ON.
Output signal depends on DIP 2, 3&5 
setting.

Actuator can operate in modulating (DIP 6 to 
OFF) or in “simple” 3-point mode, if the 3-point 
function is selected (DIP 6 to ON).
Connect power supply on terminals SN and SP 
terminals.

Factory set DIP 6 to OFF for operating actuator 
in Modulating mode.

Actuator’s stem will run to its totally extended 
or retracted position by bridging SN signal to 

terminals 1 or 3 and will remain in this positron 
as long as potential is present.

Set DIP 6 to ON for operating actuator in 3-point 
mode.

Look carefully wiring diagram as wiring is 
different for controllers with triac output (ECL) 
in comparison to controllers with relay output.

Return signal X indicates the correct position.

 

Note:

 If 

3-point

 function is selected actuator 

does not respond to any control signal on 
port Y. It only rises and lowers spindle if power 
is supplied on port 1 or 3.

SW7:  

LOG/LIN - Not in use.

SW8:

  100 % k

VS

/Reduced k

VS

 - Not in use.

SW9:   Reset 

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and will 
normally last a few minutes. The stroke length 
of the valve is stored in the memory after self 
adjustment has been completed. To restart 
self adjustment, change the position of RESET 
switch (switch No. 9). If the supply voltage is 
switched off or falls below 80 % in more then 
0.1 s, the current valve position will be stored 
in the memory and all data remain saved in the 
memory also after a power supply cut-out.

Function test

The indicator light shows whether the 
positioner is in operation or not. Moreover, the 
indicator shows the control status and faults.
Constant light

-  normal operation

No light

-  no operation or no power supply

Intermittent light (1 Hz) 
-  

self adjusting-mode

Intermittent light (3 Hz):
-  

power supply too low

-  insufficient valve stroke (<20 s)
-  end-position cannot be reached.

Dimensions

 ❹

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Plug

X

O

O

O

O

O

Bush

X

O

O

O

O

O

O:  Indicates that this hazardous substance contained in all of the homogeneous material for this part is below the limit requirement in GB/T 26572;
X:  Indicates that this hazardous substance contained in at least one of the homogeneous material for this part is above the limit requirement in GB/T 26572;

Summary of Contents for AME 10

Page 1: ...ss es Page 10 SVENSKA AME 10 AME 11 varme danfoss se Sida 11 NEDERLANDS AME 10 AME 11 www danfoss nl Blz 12 SUOMI AME 10 AME 11 www danfoss fi Sivu 13 POLSKI AME 10 AME 11 www danfoss pl Strona 14 AME...

Page 2: ...2 Danfoss 2019 07 EI 96 L5 1F AME 10 AME 11 4 6mm 1mm 32 mm 5 95 RH no condensing MAINTENANCE FREE O 18 T ambient 0 55 C T s T media 0 130 C T s 0 130 C Max 25 Nm 1 32 mm M16 1 5 IP 54...

Page 3: ...Danfoss 2019 07 3 EI 96 L5 1F AME 10 AME 11 Wiring O min 5 max 10 mm IP 54 min 4 Nm max 5 Nm A B A CLOSE OPEN B OPEN CLOSE A B min 4 Nm max 5 Nm IP 54...

Page 4: ...l SP 24 Vac Power supply Y 0 2 10 Vdc Input 0 4 20 mA 1 0 Vac Input 3 X 0 2 10 Vdc Output Proportional 3 point RL Wiring for modulating mode DIP 6 OFF DIP 6 ON Wiring for 3 point floating mode Control...

Page 5: ...AME 10 AME 11 VB 2 DN 15 25 H 4 H 1 AME 10 AME 11 VM 2 DN 15 32 AME 10 AME 11 VS 2 DN 20 25 H 2 AME 10 AME 11 VMV DN 15 40 H 3 AME 10 AME 11 AVQM PN 16 see AVQM data sheet AME 10 AME 11 AVQM PN 25 see...

Page 6: ...0 2 5 6 V 6 6 10 V SW5 0 2 5 6 V 6 6 10 V Note This function is available if switch No 4 Sequential is set SW6 Proportional 3 point ActuatorneedstoperformSelf strokingpriorchangingDIP6toON Outputsigna...

Page 7: ...ndirekte Aktuatoren kan indstilles til nedadg ende spindel ved stigende kontrolsignal DIREKTE Eller opadg ende spindel ved stigende kontrolsignal INDIREKTE Fabriksindstilling DIREKTE SW4 Sekvens To ak...

Page 8: ...gendem Steuersignal DIRECT ODER dass die Motorenspindel nach oben bewegt bei steigendem Steuersignal INVERSE Werkseinstellung DIRECT SW4 Sequentiell Zwei Antriebe k nnen parallel mit einem Steuersigna...

Page 9: ...place vers le bas quand le signal de commande augmente DIRECT ou qu elle se d place vers le haut quand le signal de commande augmente INVERSE R glage de l usine DIRECT SW4 S quentiel Deux moteurs peu...

Page 10: ...ue la se al de control aumenta DIRECTO o que el v stago se mueva hacia arriba a medida que la se al de control aumenta INVERSO Ajuste de f brica DIRECTO SW4 Secuencial Se pueden ajustar dos acuadores...

Page 11: ...V 10 Motorn kan st llas in till att reagera p signaler fr n 2 V eller 0 V r motorn inst lld p str msignal reagerar den p signaler fr n 4 mA eller 0 mA Fabriksinst llning 2 10 V SW3 Direkt Indirekt Mo...

Page 12: ...l SW2 2 V 0 V Instelling voor stuursignaal vanaf 2 V of vanaf 0 V Als de servomotor is ingesteld voor stroom sturing dan komt dit overeen met 4 mA of 0 mA Fabrieksinstelling 2 V 4 mA SW3 Direct Invers...

Page 13: ...naaliin se reagoi ohjaussignaaleihin 4 mA tai 0 mA Tehdasasetus 2 10 V SW3 Suora tai k nteinen K ytt laite voidaan m ritt siirt m n karaa alasp in nousevasta ohjaussignaalista SUORA TAI karaa yl sp in...

Page 14: ...nie fabryczne 2 V 10 V SW3 Direct Inverse Wrzeciono si ownika mo e porusza si w d przy narastaj cym sygnale steruj cym DIRECT lub porusza si w g r przy narastaj cym sygnale steruj cym INVERSE Ustawien...

Page 15: ...V 3 RL 100 Kvs Red Kvs OFF DIP 6 SW1 U I 1 U I 0 10 20 0 10 B SW2 2 10 B 0 10 B 2 0 B 4 0 2 10 B SW3 SW4 0 2 5 6 6 6 10 5 0 2 5 6 6 6 10 SW5 0 2 5 6 6 6 10 4 SW6 DIP 6 DIP 2 35 DIP6 Outputsignaldepend...

Page 16: ...S All rights reserved AME 10 AME 11 AME 10 11 Wiring for modulating mode Wiring for 3 point floating mode Controller with relay output Wiring for 3 point floatig mode Controller with triacs output AM...

Reviews: