© Danfoss | 2016.09
VD.CV.A2.02 | 1
Actuator for modulating control
AME 55QM
Data sheet
Actuator is used with pressure independent
balancing and control large valve type AB-QM
DN 125 and DN 150.
Features:
• “Self stroking” function
• Load related “Switch off“ function that
prevents overloading
• Diagnostic LED
Main data:
• Nominal voltage: 24 VAC, 50 Hz/60 Hz
• Control input signal:
- 0(4)-20 mA
- 0(2)-10 V
• Force: 2000 N
• Stroke: 40 mm
• Speed: 8 s/mm
• Max. medium temperature: 200 °C
• Manual operation
Description
Ordering
Type
Supply voltage
Code No.
AME 55 QM
24 V~
082H3078
Technical data
Power supply
V
24~; +10 to – 15%
Power consumption
VA
9
Frequency
Hz
50 / 60
Control input Y
V
0 – 10 (2 – 10) Ri = 24 kΩ
mA
0 – 20 (4 – 20) Ri = 500 Ω
Output signal X
V
0 – 10 (2 – 10)
Close of force
N
2000
Max. stroke
mm
40
Speed
s/mm
8
Max. medium temperature
°C
200
Ambient temperature
0 – 55
Storage and transport temp.
–40 to +70
Ambient humidity
95% r.h., non-condensing
Protection class
III safety extra-low voltage
Degree of protection
IP 54
Weight
kg
3.8
- marking in accordance with standards
Low Voltage Directive 73/23/EEC
EMC-Directive 2006/95/EEC, EN 60730-1, EN 60730-2-14