background image

© Danfoss | 2016.09

VD.CV.A2.02 | 1 

Actuator for modulating control

AME 55QM

Data sheet

Actuator is used with pressure independent 

balancing and control large valve type AB-QM 

DN 125 and DN 150. 

Features:

•  “Self stroking” function

•  Load related “Switch off“ function that 

prevents overloading

•  Diagnostic LED

Main data:

•  Nominal voltage: 24 VAC, 50 Hz/60 Hz 

•  Control input signal: 

- 0(4)-20 mA 

- 0(2)-10 V 

•  Force: 2000 N

•  Stroke: 40 mm

•  Speed: 8 s/mm 

•  Max. medium temperature: 200 °C

•  Manual operation

Description

Ordering

Type

Supply voltage

Code No.

AME 55 QM

24 V~

082H3078

Technical data

Power supply

V

24~; +10 to – 15%

Power consumption

VA

9

Frequency

Hz

50 / 60

Control input Y

V

0 – 10 (2 – 10) Ri = 24 kΩ

mA

0 – 20 (4 – 20) Ri = 500 Ω

Output signal X

V

0 – 10 (2 – 10)

Close of force

N

2000

Max. stroke

mm

40

Speed

s/mm

8

Max. medium temperature

°C

200

Ambient temperature

0 – 55

Storage and transport temp. 

–40 to +70

Ambient humidity

95% r.h., non-condensing

Protection class

III safety extra-low voltage

Degree of protection

IP 54

Weight

kg

3.8

 

 - marking in accordance with standards

Low Voltage Directive 73/23/EEC
EMC-Directive 2006/95/EEC, EN 60730-1, EN 60730-2-14