73692310 DH-SMT/SI

 

EI.98.B3.8C 

© Danfoss 12/2008

 

4

DEUTsCh

EnglIsh

safety note

 

To avoid injury of persons and damages to 
the device, it is absolutely necessary to read 
and observe these instructions carefully.

Necessary assembly, start-up, and 
maintenance work must be performed by 
qualified and authorized personnel only.

Prior to assembly and depressurizing the 
system.

Please comply with the instructions of the 
system manufacturer or system operator.

Mounting 

Fix the actuator AME 55, AME 56 on the 
valve

 

Wiring 

Control signal

Control signal from the controller must be 

connected to terminals Y (input signal) and 

SN (common) on the AME printed board.

Output signal

Output signal from the terminal X can be 

used for indication of the current position. 

Range depends on the DIP switch settings.

supply voltage

Supply voltage (24 V~ -15 to +10%, 50 Hz) 

must be connected to the terminals SN and 

SP.

DIP switch settings 

 

Factory settings

 

:

ALL switches are on OFF position!

Note:

 

All combinations of DIP switches are 

allowed. All functions that are selected are 

added consecutively. There is only one logic 

override of functionalities i.e. the switch No.6 

Proportional / 3 point, which sets actuator to 

ignore control signal and works as a “simple” 

3-point actuator.

sW 1: 

U/I 

 

 

Actuator can responde to a voltage or 

current control signal. With switch No.1: U/I 

actuator can be set either to operate with 

a voltage control signal (actuator responds 

to signal between 0 … 10 V), or current 

control signal (actuator responds to signal 

between 0 … 20 mA).

Factory setting

:  

voltage control signal (0 … 10 V).

sW 2: 

2V … 10 / 0V … 10 

 

Actuator can be set to response on a 

control signal from 2 V, or 0 V. If the 

actuator is set to current signal than it 

responds to control signal from 4 mA or 

0 mA.

Factory setting is: 

2 … 10V.

sW 3: 

Direct/Inverse 

Actuator can be set for spindle to travel 

downwards on rising control signal 

(DIRECT), OR for spindle to travel upwards 

on rising control signal (INVERSE).

Factory setting is: 

DIRECT

sW 4: 

---/Sequential 

Two actuators can be set to work parallel 

with one control signal. If the SEQUENTIAL 

is set than an actuator responds to split 

control signal (see 0(2) V … 5(6 V) / 

6(6) V … 10 V).

Note: 

This combination works in combination with 

switch No.5: 0(2) V … 5(6 V) / 6(6) V … 10 V

sW 5: 

0(2) V … 5(6 V)/6(6) V … 10 V 

 

Note:

 

This function is available if switch No.4:  

--- / Sequential is set.  

Actuator can be set to match the range of the 

control signal:

2 … 6 V 

(switch No.2: 2 V … 10) 

0 … 5 V  

(switch No.2: 0 V … 10) 

4 … 12 mA  

(switch No.2: 2 V … 10)  

0 … 10 mA  

(switch No.2: 0 … 10)

OR

6 … 10 V  

(switch No.2: 2 V … 10) 

5 … 10 V  

(switch No.2: 0 V … 10) 

12 … 20 mA  

(switch No.2: 2 V … 10)  

10 … 20 mA  

(switch No.2: 0 … 10)

sW 6: 

Proportional/3 point 

Actuator can operate as “simple” 3-point 

actuator, if the 3-point function is selected. 

Power supply should be connected on 

SN and SP ports. On port 1 or 3 24 VAC 

signal is connected for rising or lowering 

of actuator. Return signal X indicates the 

correct position.

Note:

if 

3 point

 function is selected actuator does 

not respond to any control signal on port Y. 

It only rises and lowers spindle if power is 

supplied on port 1 or 3.

sW 7: 

LOG. flow/LIN. flow 

Almost all Danfoss valves that fit the 
actuator have logarithmic (equal 
percentage) flow

/position characteristic. 

With setting switch to LIN. flow the 
characteristic of motorised valve can be 
affected. Combination of actuator and valve 
can work together as valve with LINEAR 
characteristic.

Factory setting:

LOG. Flow (characteristic of valve is 
unchanged)

nOTE

If this function is used in combination with  
non-logarithmic valves the characteristic 
of motorised valve will be anti-logarithm of 
valve’s characteristic (e.g. valve with linear 
characteristic will be transformed to quick 
open characteristic). 

sW 8: 

100% K

VS

/RED. K

VS 

To be set on OFF position.

sW 9: 

Reset 

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and 
will normally last a few minutes. The stroke 
length of the valve is stored in the memory 
after self adjustment has been completed. To 
restart self adjustment, change the position 
of RESET switch  (switch No.9). If the supply 
voltage is switched off or falls below 80% in 
more than 0.1s, the current valve position will 
be stored in the memory and all data remain 
saved in the memory also after a power 
supply cut-out.

Function test

The indicator light shows whether the 

positioner is in operation or not. Moreover, 

the indicator shows the control status and 

faults.
•  Constant light

-   normal operation

•  No light 

-   no operation or no power supply

•  Intermittent light (1 Hz)  

-   self adjusting-mode

•  Intermittent light (3 Hz): 

-   power supply too low
-  insufficient valve stroke (<20 s)
-   end-position cannot be reached.

Summary of Contents for AME 56

Page 1: ...www danfoss fr Page 7 ESPA OL AME 55 AME 56 www danfoss es Page 8 NEDERLANDS AME 55 AME 56 www danfoss nl Page 9 SUOMI AME 55 AME 56 www danfoss fi Sivu 10 ESKY AME 55 AME 56 www danfoss cz Strana 11...

Page 2: ...73692310 DH SMT SI EI 98 B3 8C Danfoss 12 2008 2...

Page 3: ...73692310 DH SMT SI EI 98 B3 8C Danfoss 12 2008 3...

Page 4: ...This function is available if switch No 4 Sequential is set Actuator can be set to match the range of the control signal 2 6 V switch No 2 2 V 10 0 5 V switch No 2 0 V 10 4 12 mA switch No 2 2 V 10 0...

Page 5: ...10V Bem rk Denne funktion er tilg ngelig hvis kontakt Nr 4 Sekvens er indstillet Aktuatoren kan afpasses til styresignalet 2 6 V kontakt Nr 2 2 V 10 0 5 V kontakt Nr 2 0 V 10 4 12 mA kontakt Nr 2 2 V...

Page 6: ...Sequentiell eingestellt ist Antrieb kann auf den Steuersignalbereich angepasst werden 2 6 V Schalter No 2 2 V 10 0 5 V Schalter No 2 0 V 10 4 12 mA Schalter No 2 2 V 10 0 10 mA Schalter No 2 0 10 ODER...

Page 7: ...fonction est disponible si la commande 4 S quentiel est r gl e Le moteur peut tre r gl jusqu la zone laquelle le signal de commande r pond la zone 2 6V commande 2 2V 10 0 5V commande 2 0V 10 4 12mA c...

Page 8: ...r la area en la que la se al de control del actuador responder entre 2 y 6 V interruptor No 2 2 V 10 entre 0 y 5 V interruptor No 2 0 V 10 entre 4 y 12 mA interruptor No 2 2 V 10 entre 0 y 10 mA inter...

Page 9: ...schakelaar 4 op Sequential staat De motor kan worden ingesteld voor de volgende stuursignalen 2 6 V schakelaar 2 op 2 V 0 5 V schakelaar 2 op 0 V 4 12 mA schak 2 op 2 V 0 10 mA schak 2 op 0 V OF 6 10...

Page 10: ...5 6V 6 6 10V HUOMAUTUS T m toiminto on k ytett viss jos kytkin 4 vaiheittainen on m ritetty K ytt laite voidaan mukauttaa ohjaussignaaliin 2 6 V kytkin 2 2 10 V 0 5 V kytkin 2 0 10 V 4 12 mA kytkin 2...

Page 11: ...5 10 V p ep na 2 0 V 10 12 20 mA p ep na 2 2 V 10 10 20 mA p ep na 2 0 10 P ep na 6 Proporcion ln 3 bodov Jestli e je nastaven 3 bodov regulace tak regul tor bude pracovat jako jednoduch pohon s 3 bod...

Page 12: ...5 0 2 V 5 6 V 6 6 V 10 V UWAGA Ta funkcja jest dost pna gdy ustawiony jest prze cznik nr 4 Sequential Mo na ustawi zakres sygna u steruj cego na kt ry b dzie reagowa si ownik w zakresie 2 6 V prze cz...

Page 13: ...I 1 U I 0 10 20 0 10 B SW 2 2 10 B 0 10 B 2 0 B 4 0 2 10 B SW 3 SW 4 0 2 5 6 6 6 10 5 0 2 5 6 6 6 10 SW 5 0 2 5 6 6 6 10 4 2 6 2 10 0 5 2 0 10 4 12 2 2 10 0 10 2 0 10 6 10 2 2 10 5 10 2 0 10 12 20 2 2...

Page 14: ...0V 10 2V 4mA 0V 0mA 2 10V SW 3 SW 4 0 2 V 5 6V 5 6 V 10V 5 0 2 V 5 6V 5 6 V 10V SW 5 0 2 V 5 6 V 10 V 4 2 6V 2 2V 10 0 5V 2 0V 10 4 12mA 2 2V 10 0 10mA 2 0V 10 6 10V 2 2V 10 5 10V 2 0V 10 12 20mA 2 2...

Page 15: ...73692310 DH SMT SI EI 98 B3 8C Danfoss 12 2008 15...

Page 16: ...73692310 DH SMT SI EI 98 B3 8C Danfoss 12 2008 16...

Reviews: