Reglermanual - VMGFF102

4.9.8 - RUNTIME menu

NAME

FORMAT

UNIT

DESCRIPTION

HR_MACH

nnnnn

hours

Unit operating hours

st_mach

nnnnn

-

Number of start-ups, unit

HR_CP_A1

nnnnn

hours

Operating hours compressor A1

st_cp_a1

nnnnn

-

Number of start-ups compressor A1

HR_CP_A2

nnnnn

hours

Operating hours compressor A2

st_cp_a2

nnnnn

-

Number of start-ups compressor A2

HR_CP_A3

nnnnn

hours

Operating hours compressor A3

st_cp_a3

nnnnn

-

Number of start-ups compressor A3

HR_CP_B1

nnnnn

hours

Operating hours compressor B1

st_cp_b1

nnnnn

-

Number of start-ups compressor B1

HR_CP_B2

nnnnn

hours

Operating hours compressor B2

st_cp_b2

nnnnn

-

Number of start-ups compressor B2

hr_fana1

nnnnn

hours

Operating hours fan A1

hr_fana2

nnnnn

hours

Operating hours fan A2

hr_fanb1

nnnnn

hours

Operating hours fan B1

st_fa_a1

nnnnn

-

Number of start-ups fan A1

st_fa_a2

nnnnn

-

Number of start-ups fan A2

st_fa_b1

nnnnn

-

Number of start-ups fan B1

hr_cpum1

nnnnn

hours

Operating hours pump 1

hr_cpum2

nnnnn

hours

Operating hours pump 2

nb_def_a

nnnnn

  -

Number of defrost cycles circuit B

nb_def_b

nnnnn

  -

Number of defrost cycles circuit A

4.9.9 - MODES menu

NAME

FORMAT

UNIT

DESCRIPTION

m_limit

Yes/No

-

Demand limit active

m_ramp

Yes/No

-

Ramp loading active

m_cooler

Yes/No

-

Heat exchanger heater active

m_night

Yes/No

-

Low-noise level night mode

m_SM

Yes/No

-

Aquasmart active

m_leadla

Yes/No

-

Master/slave active

m_auto

Yes/No

-

Change-over active

m_heater

Yes/No

-

Electric heater stages active

m_lo_ewt

Yes/No

-

Lock heating mode and entering water too cold

m_boiler

Yes/No

-

Boiler active

m_defr_a

Yes/No

-

Defrost circuit A active

m_defr_b

Yes/No

-

Defrost circuit B active

m_sst_a

Yes/No

-

Low suction temperature circuit A

m_sst_b

Yes/No

-

Low suction temperature circuit B

m_dgt_a

Yes/No

-

High discharge gas temperature circuit A

m_dgt_b

Yes/No

-

High discharge gas temperature circuit B

m_hp_a

Yes/No

-

High pressure circuit A

m_hp_b

Yes/No

-

High pressure circuit B

m_sh_a

Yes/No

-

Low superheat circuit A

m_sh_b

Yes/No

-

Low superheat circuit B

Summary of Contents for AR05

Page 1: ...AR05 Control Operation instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP...

Page 2: ...ics 6 4 3 Password screens 6 4 4 Menu screen characteristics 7 4 5 Data screen or con gurable parameter characteristics 7 4 6 Parameter modi cation 7 4 7 Operating mode screen 8 4 8 Menu tree structur...

Page 3: ...egulate the AR05 units These units have one or two refrigerant circuits Controls compressor start up to control the water loop the fans to optimise operation of each refrigerant circuit the defrost cy...

Page 4: ...sure the suction and discharge pressure in each circuit Thermistors The heat exchanger water sensors are installed in the enter ing and leaving side The outdoor temperature sensor is mounted under a m...

Page 5: ...pump 1 J2B CH 22 NRCP2 BASE Command water pump 2 J2B CH 23 NRCP2 BASE The change over between the two pumps is con gurable Alarm relay output J3 CH 24 30A 31A NRCP2 BASE Unit operation relay output J3...

Page 6: ...ction screen Password entry screen Parameter modi cation screen NOTE If the interface is not used for a long period it will go black The control is always active the operating mode remains unchanged T...

Page 7: ...arameters such as the water temperature setpoints MAINMENU TEMP Current path in the menu structure EWT 12 0 C List of items LWT 7 0 C Cursor position OAT 35 0 C CHWSTEMP 17 8 C SCT_A 57 0 C Leaving Wa...

Page 8: ...Select Machine Mode Description of the screen Local On List of the machine operating modes Local Schedule Cursor CCN Remote The Up and Down keys position the cursor on the selected operating mode Fou...

Page 9: ...DAY BRODCAST DATETIME CTRL_ID HOLIDY01S HOLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs O...

Page 10: ...LWT nnn n C Heat exchanger leaving water temperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n...

Page 11: ...tput B1 exv_a 0 100 EXV position circuit B HD_POS_B 0 100 Position variable fan speed controller B RV_B On O Four way refrigerant valve C_HEATER On O Heat exchanger and lower coil heater BOILER On O B...

Page 12: ...of start ups fan B1 hr_cpum1 nnnnn hours Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles c...

Page 13: ...rent alarm 1 alarm_2c nnnnn Current alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus a...

Page 14: ...me Summer time startmon 1 to 12 3 Month startdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday s...

Page 15: ...0 to 13 9 0 C Delta T for maximum reset cr_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature...

Page 16: ...Monday P2 period 2 7h00 18h00 Monday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not us...

Page 17: ...l be in occupied or unoccupied mode depending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTEN...

Page 18: ...ange over to heating mode Heating cooling control can be automatic or manual In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold valu...

Page 19: ...customer safety loop see chapter 3 6 It prevents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 He...

Page 20: ...Heating sp 1 open Heating setpoint 1 Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modi ed so that less machine capacity is required in cooling mode the se...

Page 21: ...rotection and in all cases cannot satisfy the heating load The outdoor temperature is below a con gured threshold see HCCONFIG con guration The unit demand limit is not active The user may con gure th...

Page 22: ...eturn to an autonomous operating mode until the fault is cleared If the master unit is halted due to an alarm the slave unit is authorised to start without prior conditions ATTENTION For heat pumps op...

Page 23: ...hen communication is re established Installation bus fault or defective slave board Depending on the con guration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with...

Page 24: ...ve 45 P 43 Heat exchanger temperature too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor p...