Reglermanual - VMGFF102

4.9.20 - HCCONFIG menu

NOM

FORMAT

DEFAULT

UNIT

DESCRIPTION

auto_sel

No/Yes

No

-

Automatic change-over selection

cr_sel

0 to 2

0

-

Cooling reset selection

hr_sel

0 to 2

0

-

Heating reset selection
1 = outside temp., 0 = none, 2 = delta T

heat_th

-20 to 0

-15

°C

Outside temperature threshold cooling mode

boil_th

-15 to 15

-10

°C

Outside temperature threshold for the boiler

ehs_th

-5 to 21.2

5

°C

Outside temperature threshold for electric heater stages

both_sel

No/Yes

No

-

Heating or cooling command selection for HSM

ehs_back

No/Yes

No

-

1 backup electric heater stage

ehs_pull

0 to 60

0

minutes

Delay before start-up of the fi rst electric heater stage

ehs_defr

No/Yes

No

-

Quick electric heat stages for defrost

4.9.21 - RESETCFG menu

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

COOLING RESET

oatcr_no

-10 to 51.7

-10

°C

Outside temperature for no reset

oatcr_fu

-10 to 51.7

-10

°C

Outside temperature for maximum reset

dt_cr_no

0 to 13.9

0

^C

Delta T for no reset

dt_cr_fu

0 to 13.9

0

^C

Delta T for maximum reset

cr_deg

-16.7 to 16.7

0

^C

Cooling reset value

HEATING RESET

oathr_no

-10 to 51.7

-10

°C

Outside temperature for no reset

oathr_fu

-10 to 51.7

-10

°C

Outside temperature for maximum reset

dt_hr_no

0 to 13.9

0

^C

Delta T for no reset

dt_hr_fu

0 to 13.9

0

^C

Delta T for maximum reset

hr_deg

-16.7 to 16.7

0

^C

Heating reset value

4.9.22 - USERCONF menu

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

language

 0 to 4

0

-

Language selection 
English = 0, Spanish = 1, French =  2, Portuguese = 3, Italian = 4, 
Translation = 5

use_pass

1 to 9999

11

-

User password

4.9.23 - DATETIME menu

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

hour

0 to 24

hours

Hour

minutes

0 to 59

minutes

Minutes

dow

1 to 7

Day of the week

tom_hol

No/Yes

No

- Holiday 

tomorrow?

tod_hol

No/Yes

No

-

Holiday today

dlig_off 

No/Yes

-

Winter time change-over active?

dlig_on

No/Yes

-

Summer time change-over active?

d_of_m

1 to 31

Day of the month

month

1 to 12

Month

year

0 to 99

Year

4.9.24 - Menu CTRL_ID

NAME

FORMAT

DEFAULT

UNIT

DESCRIPTION

elemt_nb

1 to 239

1

-

Element number

bus_nb

0 to 239

0

-

Bus number

baudrate

9600 to 38400

9600

-

Communication speed

AR05

Description

CSA-SR-20H430NN
-

Software version
Serial number

Summary of Contents for AR05

Page 1: ...AR05 Control Operation instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP...

Page 2: ...ics 6 4 3 Password screens 6 4 4 Menu screen characteristics 7 4 5 Data screen or con gurable parameter characteristics 7 4 6 Parameter modi cation 7 4 7 Operating mode screen 8 4 8 Menu tree structur...

Page 3: ...egulate the AR05 units These units have one or two refrigerant circuits Controls compressor start up to control the water loop the fans to optimise operation of each refrigerant circuit the defrost cy...

Page 4: ...sure the suction and discharge pressure in each circuit Thermistors The heat exchanger water sensors are installed in the enter ing and leaving side The outdoor temperature sensor is mounted under a m...

Page 5: ...pump 1 J2B CH 22 NRCP2 BASE Command water pump 2 J2B CH 23 NRCP2 BASE The change over between the two pumps is con gurable Alarm relay output J3 CH 24 30A 31A NRCP2 BASE Unit operation relay output J3...

Page 6: ...ction screen Password entry screen Parameter modi cation screen NOTE If the interface is not used for a long period it will go black The control is always active the operating mode remains unchanged T...

Page 7: ...arameters such as the water temperature setpoints MAINMENU TEMP Current path in the menu structure EWT 12 0 C List of items LWT 7 0 C Cursor position OAT 35 0 C CHWSTEMP 17 8 C SCT_A 57 0 C Leaving Wa...

Page 8: ...Select Machine Mode Description of the screen Local On List of the machine operating modes Local Schedule Cursor CCN Remote The Up and Down keys position the cursor on the selected operating mode Fou...

Page 9: ...DAY BRODCAST DATETIME CTRL_ID HOLIDY01S HOLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs O...

Page 10: ...LWT nnn n C Heat exchanger leaving water temperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n...

Page 11: ...tput B1 exv_a 0 100 EXV position circuit B HD_POS_B 0 100 Position variable fan speed controller B RV_B On O Four way refrigerant valve C_HEATER On O Heat exchanger and lower coil heater BOILER On O B...

Page 12: ...of start ups fan B1 hr_cpum1 nnnnn hours Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles c...

Page 13: ...rent alarm 1 alarm_2c nnnnn Current alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus a...

Page 14: ...me Summer time startmon 1 to 12 3 Month startdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday s...

Page 15: ...0 to 13 9 0 C Delta T for maximum reset cr_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature...

Page 16: ...Monday P2 period 2 7h00 18h00 Monday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not us...

Page 17: ...l be in occupied or unoccupied mode depending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTEN...

Page 18: ...ange over to heating mode Heating cooling control can be automatic or manual In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold valu...

Page 19: ...customer safety loop see chapter 3 6 It prevents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 He...

Page 20: ...Heating sp 1 open Heating setpoint 1 Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modi ed so that less machine capacity is required in cooling mode the se...

Page 21: ...rotection and in all cases cannot satisfy the heating load The outdoor temperature is below a con gured threshold see HCCONFIG con guration The unit demand limit is not active The user may con gure th...

Page 22: ...eturn to an autonomous operating mode until the fault is cleared If the master unit is halted due to an alarm the slave unit is authorised to start without prior conditions ATTENTION For heat pumps op...

Page 23: ...hen communication is re established Installation bus fault or defective slave board Depending on the con guration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with...

Page 24: ...ve 45 P 43 Heat exchanger temperature too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor p...