background image

21

Reglermanual - VMGFF102

5.9 - Capacity control

This function adjusts the number of active compressors to 
keep the heat exchanger water temperature at its setpoint. 
The precision with which this is achieved depends on the 
capacity of the water loop, the fl ow rate, the load, and the 
number of stages available on the unit. The control system 
continuously takes account of the temperature error with 
respect to the setpoint, as well as the rate of change in this 
error and the diff erence between entering and leaving water 
temperatures, in order to determine the optimum moment at 
which to add or withdraw a capacity stage.

If the same compressor undergoes too many starts (per hour) 
or runs below one minute each time it is started this 
automatically brings about reduction of compressor starts, 
which makes leaving water temperature control less precise.

The high pressure, low pressure or defrost unloading functions 
can also aff ect temperature control accuracy. Compres-sors are 
started and stopped in a sequence designed to equalise the 
number of start-ups (value weighted by their operating time).

5.10 - Head pressure control

The head pressure is independently controlled for each 
circuit, based on the saturated condensing temperature value.

5.11 - Defrost function

This function only applies to heat pumps. Defrost is activated, 
when the unit is in heating mode to reduce frost build-up on 
the air heat exchanger. The defrost cycle can only be applied to 
one circuit at a time. During the defrost cycle the fans of that 
circuit are stopped, and the four-way refrigerant valve is 
reversed, forcing the circuit to cooling mode. The fan can 
temporarily be restarted during the defrost cycle. The defrost 
cycle is fully automatic and does not require any setting.

5.12 - Desuperheater option

In units with desuperheater it is possible to reclaim the hot 
water. To optimise this option, the condensing setpoint 
should be increased (chapter 4.9.4 setpoint menu, sct_min) 
while the desuperheater heat exchanger is used. Optimis-
ing desuperheater condensation is activated via dry contact 
DSHTR_SW (see chapter 3.6.1).

5.13 - Additional electric heater stage control

The heat pump units can control up to four additional 
electric heating stages (accessory).

The electric heating stages are activated to complement the 
heating capacity when the following conditions are satisfi ed:
• 

The unit uses 100% of the available heating capacity, or 
the unit is limited in its operation by a protection mode 
(low suction temperature, hot gas or defrost sequence in 
progress protection), and in all cases cannot satisfy the 
heating load.

• 

The outdoor temperature is below a confi gured 
threshold (see HCCONFIG confi guration).

• 

The unit demand limit is not active.

The user may confi gure the last available electric heating 
stages as a safety stage. In this case, the safety stage is only 
activated in addition to the other stages if there is a machine 
fault, preventing the use of the heating capacity. The other 
electric heating stages will continue to operate as described 
above.

5.14 - Control of a boiler

NOTE: The control of the electric heating stages or of a 
boiler is not authorised for slave units.

The unit can control the start-up of a boiler, if it is in heating 
mode. When the boiler is operating, the unit water pump is 
stopped.

A heat pump unit and a boiler cannot operate together. In 
this case the boiler output is activated in the following 
conditions:
• 

The unit is in heating mode, but a fault prevents the use 
of the heat pump capacity.

• 

The unit is in heating mode, but works at a very low 
outdoor temperature, making the heat pump capacity 
insuffi

  cient. The outdoor air temperature threshold for 

use of the boiler is fi xed at -10°C, but this value can be 
adjusted in the HCCONFIG menu.

5.15 - Master/slave assembly

Two control units can be linked to produce a master/slave 
assembly. The two machines are interconnected over the CCN 
bus. All parameters required for the master/slave function 
must be confi gured through the Service confi gura-tion 
menu.

Master/slave operation requires the connection of a tempe-
rature probe at the common manifold on each machine, if the 
heat exchanger leaving water temperature is controlled. It is 
not required, if the entering water temperature is controlled.

The master/slave assembly can operate with constant or 
variable fl ow. In the case of variable fl ow each machine must 
control its own water pump and automatically shut down the 
pump, if the cooling capacity is zero.

For constant fl ow operation the pumps for each unit are 
continuously operating, if the system is operating. The master 
unit can control a common pump that will be activated, 
when the system is started. In this case the slave unit pump is 
not used.

All control commands to the master/slave assembly (start/
stop, setpoint, heating/cooling operation, load shedding, etc.) 
are handled by the unit which is confi gured as the master, 
and must therefore only be applied to the master unit. They 
will be transmitted automatically to the slave unit.

The master unit can be controlled locally, remotely or by CCN 
commands. Therefore to start up the assembly, simply 
validate the Master operating type (Master) on the master 
unit. If the Master has been confi gured for remote control 
then use the remote volt-free contacts for unit start/stop.

Summary of Contents for AR05

Page 1: ...AR05 Control Operation instructions MAINMENU STATUS Circuit B Total Capacity CAPB_T 0 DEM_LIM 100 SP 4 2 C CTRL_PNT 28 9 C EMSTOP dsable ENTER START STOP...

Page 2: ...ics 6 4 3 Password screens 6 4 4 Menu screen characteristics 7 4 5 Data screen or con gurable parameter characteristics 7 4 6 Parameter modi cation 7 4 7 Operating mode screen 8 4 8 Menu tree structur...

Page 3: ...egulate the AR05 units These units have one or two refrigerant circuits Controls compressor start up to control the water loop the fans to optimise operation of each refrigerant circuit the defrost cy...

Page 4: ...sure the suction and discharge pressure in each circuit Thermistors The heat exchanger water sensors are installed in the enter ing and leaving side The outdoor temperature sensor is mounted under a m...

Page 5: ...pump 1 J2B CH 22 NRCP2 BASE Command water pump 2 J2B CH 23 NRCP2 BASE The change over between the two pumps is con gurable Alarm relay output J3 CH 24 30A 31A NRCP2 BASE Unit operation relay output J3...

Page 6: ...ction screen Password entry screen Parameter modi cation screen NOTE If the interface is not used for a long period it will go black The control is always active the operating mode remains unchanged T...

Page 7: ...arameters such as the water temperature setpoints MAINMENU TEMP Current path in the menu structure EWT 12 0 C List of items LWT 7 0 C Cursor position OAT 35 0 C CHWSTEMP 17 8 C SCT_A 57 0 C Leaving Wa...

Page 8: ...Select Machine Mode Description of the screen Local On List of the machine operating modes Local Schedule Cursor CCN Remote The Up and Down keys position the cursor on the selected operating mode Fou...

Page 9: ...DAY BRODCAST DATETIME CTRL_ID HOLIDY01S HOLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs O...

Page 10: ...LWT nnn n C Heat exchanger leaving water temperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n...

Page 11: ...tput B1 exv_a 0 100 EXV position circuit B HD_POS_B 0 100 Position variable fan speed controller B RV_B On O Four way refrigerant valve C_HEATER On O Heat exchanger and lower coil heater BOILER On O B...

Page 12: ...of start ups fan B1 hr_cpum1 nnnnn hours Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles c...

Page 13: ...rent alarm 1 alarm_2c nnnnn Current alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus a...

Page 14: ...me Summer time startmon 1 to 12 3 Month startdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday s...

Page 15: ...0 to 13 9 0 C Delta T for maximum reset cr_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature...

Page 16: ...Monday P2 period 2 7h00 18h00 Monday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not us...

Page 17: ...l be in occupied or unoccupied mode depending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTEN...

Page 18: ...ange over to heating mode Heating cooling control can be automatic or manual In automatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold valu...

Page 19: ...customer safety loop see chapter 3 6 It prevents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 He...

Page 20: ...Heating sp 1 open Heating setpoint 1 Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modi ed so that less machine capacity is required in cooling mode the se...

Page 21: ...rotection and in all cases cannot satisfy the heating load The outdoor temperature is below a con gured threshold see HCCONFIG con guration The unit demand limit is not active The user may con gure th...

Page 22: ...eturn to an autonomous operating mode until the fault is cleared If the master unit is halted due to an alarm the slave unit is authorised to start without prior conditions ATTENTION For heat pumps op...

Page 23: ...hen communication is re established Installation bus fault or defective slave board Depending on the con guration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with...

Page 24: ...ve 45 P 43 Heat exchanger temperature too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor p...

Page 25: ...VMGFF102...

Reviews: