D
US
14 | AQ450438405295en-US0201
© Danfoss | Climate Solutions | 2023.06
4.9 Operating mode of the lockable service connections
After activating the spindle, generally fit the spindle protection cap again and tighten with 40 - 50 Nm.
This serves as a second sealing feature during operation.
Pipe connection
Pipe connection
Fig. 12
Opening the shut-off valve:
Spindle: turn to the left (counter-clockwise) as far as it will go.
—> Shut-off valve completely opened / service connection closed.
Fig. 13
Opening the service connection
Spindle: Turn
1
/
2
- 1 turn to the right clockwise.
—> Service connection opened / shut-off valve opened.
Connection
blocked
Spindle
Spindle
Connection
open
Compressor
Compressor
Service connec-
tion closed
Service connec-
tion opened
4
|
Compressor assembly
To ensure the oil return function will work reliably no matter what kind of system configuration you
are using, Bock recommends incorporating oil separators or oil level monitoring equipment. The "O"
connection is already available from the factory for the purpose of installing the additional oil level
monitoring component. Oil should be returned from the oil separator to the compressor via the "D1"
connection provided for this purpose on the compressor.
4.10 Oil return
For systems with long pipes and higher degree of contamination, a filter on the
suction-side is recommended. The filter has to be be renewed depending on the degree of contamina-
tion (reduced pressure loss).