Compressor operation is possible within the operating limits.
These can be found in Bock compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
- Permissible ambient temperature -4°F ... 140°F (-20 °C) - (+60 °C).
- Max. permissible discharge end temperature 320°F (160 °C).
- Min. discharge end temperature
≥
122°F (50 °C).
- Min. oil temperature
≥
86°F (30 °C).
- Max. permissible switching frequency 12x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
Avoid continuous operation in limit range.
3.3 Limits of application
3
|
Areas of application
1)
LP = Low pressure
HP = High pressure
Max. permissible operating pressure (LP/HP)
1)
:
100/150 bar (1450/2176 psig)