D
US
8 | AQ450437934291en-US0301
© Danfoss | Climate Solutions | 2023.09
Property damage possible.
The oil level must be in the
visible part of the sight glass;
damage to the compressor
is possible if overfilled or
underfilled!
Fig. 4
max.
min.
0,6 Ltr. /
21 fl.oz
Oil level
~
~
3
|
Areas of application
3.1 Refrigerants
•
R744: CO
2
(Recommendation CO
2
quality 4.5 (< 5 ppm H
2
O))
The compressors are filled at the factory with the following oil type:
Compressor version
ML(P)
and
S(P):
BOCK
lub E85
Compressor version
SH(P):
BOCK C170E
Only these oils may be used!
3.2 Oil charge
/
HG
2 4
110
CO
2
X
2.4 Type key
compressors with
LSPM Motor
(example)
¹
)
HG - Hermetic Gas-Cooled (suction gas-cooled)
²
)
X - Ester oil charge
³
)
MLP - Normal cooling and deep freezing at low and medium evaporation temperatures
SP - For frequency regulation and extended limits of application
SHP - For high evaporating temperatures eg. heat pumps, different oil charge
15
T
S P
2
|
Product description
UL -
Transcritical
CO
2
version
HP code for motor size
LSPM Motor
Compressor version
³
)
Swept volume
Number of cylinders
Size
Oil charge ²
)
Series ¹
)
Identification
UL compressor