background image

www.DEVI.com

Installation Guide

DEVIreg™ 330 (+60 °С to +160 °C)

Electronic Thermostat

EN

Summary of Contents for DEVI 140F1073

Page 1: ...www DEVI com Installation Guide DEVIreg 330 60 to 160 C Electronic Thermostat EN...

Page 2: ......

Page 3: ...l air sensor must be used to measure and control the desired temperature The thermostat has a button to adjust the temperature set ting with a scale from 60 C to 160 C An LED indicator shows standby p...

Page 4: ...16 A 3680 W 230 V cos 0 3 max1A Sensing units NTC 16 7 kOhm at 100 C Sensing values 25 C 50 C 100 C 120 C 170 C 300 kOhm 99 4 kOhm 16 7 kOhm 8 8 kOhm 2 35 kOhm Hysteresis 0 4 C Ambient temperature 10...

Page 5: ...s supply to the thermostat is turned off before installation Please also note the following The installation of the thermostat must be done by an authorized and qualified installer according to local...

Page 6: ...ution Temperature sensor with silicon cable should not be installed in concrete aggressive and corrosive environment etc 2 Mounting Instructions Please observe the following placement guidelines Insta...

Page 7: ...40V 250V 16 1 A Sensor Load max 16 A heating Max 10 A cooling The screen of the heating cable must be connected to the earth conductor of the power supply cable by using a separate connector Note When...

Page 8: ...DEVIreg 330 60 C to 160 C Installation Guide 8 3 Warranty 4 Disposal Instruction...

Page 9: ...DEVIreg 330 60 C to 160 C 9 Installation Guide...

Page 10: ...DEVIreg 330 60 C to 160 C Installation Guide 10...

Page 11: ...DEVIreg 330 60 to 160 C Produced by Danfoss 06 2020 08091318 AQ087886468701en 000302 Danfoss A S Nordborgvej 81 6430 Nordborg Syddanmark Denmark...

Page 12: ...20 240V 50 60Hz 60 to 160 C 16A 3680W 230V Product Documentation DK EL 7224215328 SE EL 8581188 NO EL 5402664 FI SSTL 3531034 Designed in Denmark for Danfoss A S 5 7 0 3 4 6 6 2 0 9 2 3 3 5 6 7 8 DEVI...

Reviews: