Installation Guide
Ready-made self-limiting cable DEVIpipeheat™ 10 V3
Product specification
Type
Value
Nominal voltage
230 V~
Nominal output (tolerance)
10 W/m @ 10 °C (7,5-13,5 W/m @ 10 °C )
Max permissible use temperature, powered
65 °C
Max permissible use temperature, unpowered
65 °C
Minimum installation temperature
- 5 °C
Max water temperature (inside water pipe installation)
23 °C
Max water pressure (inside water pipe installation)
10 bar
Heating cable dimensions
8,75 × 5,15 mm
Outer sheath
HDPE + blue PVDF
Minimum Screen Coverage
100% aluminium foil
Maximum resistance of protective aluminum foil and drain wire
36 Ω/Km
Bending Ø, min
50 mm (to the inside of the cable)
Cold lead with plug
2 m, 3 х 0,75 mm²
IP Class for ready made unit
IP Class for heating part and end termination
IP67
IP68
Specific heating cable length can be chosen from product range and used for different suitable projects For more details contact
your local DEVI sales company
Note:
In case of cold lead extension it is the full responsibility of the installer/designer to use proper cold lead dimensioned
for the purpose and assembly sets that establish sufficient mechanical strength, flammability resistance and water proofing
- and to design the heating unit with correct output for the specific application to avoid overheating of the cable or
building materials
Regarding other types of applications please contact your local DEVI sales company.
More information about applications (maximum linear output, specific output, heating circuit length, voltage etc) can be found
at
www.devi.com
DEVI
6