Troubleshooting

Error indication

Possible Causes

Impossible to add device,  ECL,  to the Danfoss Link™ CC system

- The distance between the Danfoss Link™ CC and the DLG has  

exceeded 1,5m.

- Check if the MODBUS address of the ECL controller is set to 5. 

- Check your software version (house control/settings/about) of the Danfoss 

Link™ CC and update if older than MkIII 3.2;  

http://link.danfoss.com

For further information, see separate instructions for Danfoss Link™ CC and 

Danfoss ECL Comfort 110 controller.

The connection to the ECL is lost

- The wireless signal is weak

- Defective device

For further information, see separate instruction  

for the Danfoss Link™ CC.

Danfoss Link™ indicates communication error on the ECL and the DLG for 

ECL has green light

- The cable connection between the ECL and the DLG is unstable / discon-

nected.

- Check if the cable connection between the ECL and the DLG has defects. 

Fasten the screw terminals and if the error persists the cable has to be 

changed.

Flashing LED on DLG

- The CC is disconnected

- The wireless signal is weak

Low room temperature (below comfort settings)

- Check if the ECL controller  is left in setback due to lost connection.

- If connection is ok check the heat curve slope setting of the ECL controller 

and increase if necessary.

Fejlfinding

Fejlmelding

Mulig årsag

Ikke muligt at tilføje enhed, ECL, til Danfoss Link™ CC systemet 

- Afstanden mellem Danfoss Link™ CC og DLG overstiger 1,5 meter.

- Kontroller, om MODBUS adressen i ECL regulatoren er indstillet til 5.

- Kontroller, om din softwareversion (huskontrol/indstillinger/om) i 

Danfoss Link™ CC og opdater, hvis den er ældre end MkIII 3.2;  

http://link.danfoss.com

For yderligere oplysninger, se separate vejledninger til Danfoss Link™ CC 

eller Danfoss ECL Comfort 110 regulator.

Forbindelsen til ECL er mistet 

- Det trådløse signal er svagt

- Defekt enhed

For yderligere oplysninger, se separat vejledning

til Danfoss Link™ CC.

Danfoss Link™ melder kommunikationsfejl på ECL og DLG for ECL lyser 

grønt

- Kabelforbindelsen imellem ECL og DLG er ustabil / afbrudt.

- Kontroller kabelforbindelsen imellem ECL og DLG for defekter. Efter-

spænd skrueterminaler, og vedbliver problemet, skift da kablet.

Blinkende udgangs-/alarmlysdioder på DLG

- CC er afbrudt

- Det trådløse signal er svagt

Lav rumtemperatur (under komfortindstillinger)

- Kontroller, om ECL regulatoren er efterladt i reduceret drift pga. tabt 

forbindelse.

- Hvis forbindelsen er ok, kontroller  den valgte varmekurve i ECL regula-

toren og hæv den hvis nødvendigt.

EC - Declaration of conformity

Hereby Danfoss A/S declares that this equipment is in compliance with the essential requirements and other relevant provisions of  

the Radio Equipment Directive.

Installation Guide, 

DLG / ECL 110 / Danfoss Link™

© Danfoss | 2017.03 | 7

VI.JM.C3.6K

Summary of Contents for ECL Comfort 110

Page 1: ...87H1435 10 ECL 110 http heating danfoss com Danfoss Link Gateway http heating danfoss com Danfoss Link CC http heating danfoss com Danfoss Living Connect http homeowners danfoss com products smartheat...

Page 2: ...s Link CC Danfoss 87H1438 11 Mk III v 3 2 0 Danfoss 87H1444 10 ECL 110 http heating danfoss com Documentation VIKTG Danfoss Link CC http heating danfoss com Documentation VISGL Danfoss Living Connect...

Page 3: ...110 Gnd D D Danfoss 87H1439 10 http heating danfoss com Documentation VIKTG DLG Data Daten DLG 8 24 V d c 220 240 V a c 50 Hz 0 9 W 0 45 C 868 42 MHz 0 30 m Max 1 mW IP class 20 Dim 80 x 80 x 30 mm D...

Page 4: ...0 hinzuf gen 1 2 3 4 5 6 7 230 V A C Danfoss 87H1441 10 Danfoss 87H1445 10 MANUAL Disconnecting DLG from CC Afbryde DLG fra CC Koppla DLG fr n CC DLG von CC abschalten Danfoss 87H1446 10 1 2a 2b 2c 10...

Page 5: ...Adding DLG ECL 110 Danfoss 87H1447 10 Tilmelding af DLG ECL 110 Danfoss 87H1447 10 Installation Guide DLG ECL 110 Danfoss Link Danfoss 2017 03 5 VI JM C3 6K...

Page 6: ...L gga till DLG ECL 110 Danfoss 87H1447 10 DLG ECL 110 hinzuf gen Danfoss 87H1447 10 Installation Guide DLG ECL 110 Danfoss Link 6 Danfoss 2017 03 VI JM C3 6K...

Page 7: ...nding Fejlmelding Mulig rsag Ikke muligt at tilf je enhed ECL til Danfoss Link CC systemet Afstanden mellem Danfoss Link CC og DLG overstiger 1 5 meter Kontroller om MODBUS adressen i ECL regulatoren...

Page 8: ...ECL en heten och h j om det r n dv ndigt Fehlersuche Fehleranzeige M gliche Ursachen Hinzuf gen vom Ger t ECL zum Danfoss Link CC System ist nicht m glich Der Abstand von 1 5 m zwischen Danfoss Link...

Reviews: