24
VI.KT.F2.02
© Danfoss 06/2008
DH-SMT/DK
DH-SMT/DK
VI.KT.F2.02
© Danfoss 06/2008
25
For easy access, you should mount the ECL Comfort controller near the system. Select
one of the three following methods:
• Mounting on a wall
• Mounting on a DIN rail
• Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting on a wall
Mount the controller on a wall with a smooth surface and establish the electrical
connections.
Danfoss 87B787.10
Mounting on a DIN rail
Mount the controller on the DIN rail and establish the electrical connections.
Danfoss 87B788.10
Mounting in a panel
Mounting kit: Order code no. 087B1249.
The panel plate thickness must not exceed 5 mm. Prepare a cut-out with the dimensions
93 x 139 mm. Insert the controller into the panel cut-out and fix it with the clamp which
is placed horisontally on the controller. Establish the electrical connections.
Danfoss 87B789.10
For further details on mounting, see the mounting guide.
Mounting the ECL Comfort controller
Installation
* Optional connections for safety thermostat
Terminal
Description
Max. load
20
Supply voltage 230 V a.c. - neutral (N)
21
Supply voltage 230 V a.c. - live (L)
22
Optional connections for safety thermostat
23
Optional connections for safety thermostat
24
M1 Actuator - open
15 VA
25
M1 Actuator - close
15 VA
26
M1 Actuator - neutral
27
P1
Circulation pump - neutral
28
P1
Circulation pump - live (relay R1)
4 (2) A
29
Not to be used
30
Not to be used
Wire cross section: 0.5 - 1.5 mm
2
Incorrect connection can damage the TRIAC outputs.
Electrical connections - 230 V a.c. - in general