ECL Card settings
(circuit I)
30a
A
Time and date
Section 17
B
System information
Sections 18 & 19
C
Heat curve
Section 20
Setting ranges
Factory settings
Your settings
Slope
0.2 ... 3.4
1.0
See section 20
Parallel displacement
-9 ... 9
0 K
See section 20
1
Limit for heating cut-out
10 ... 30 °C
18 °C
See section 21
2
Flow temperature , min. / max. limits
10 ... 110 °C
min. 20, max. 90 °C
See section 22
3
Room temperature influence
0 ... 99 / -99 ... 0
min. 0, max. -40
See section 23
4
Proportional band, Xp
1 ... 250 K
200 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec.
55 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec.
56 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K
3 K
See section 26
ECL Card settings
(circuits II / III)
30b
A
Time and date
Section 17
B
System information
Sections 18 & 19
C
Heat curve
Section 20
Setting ranges
Factory settings
Your settings
Slope II
0.2 ... 3.4
0.4
See section 20
Parallel displacement II
-9 ... 9
0 K
See section 20
1
II
Limit for heating cut-out
10 ... 30 °C
18 °C
See section 21
2
II
Flow temperature , min. / max. limits
10 ... 110 °C
min. 20, max. 50 °C
See section 22
3
II
Room temperature influence
0 ... 99 / -99 ... 0
min. 0, max. -40
See section 23
4
III
Proportional band, Xp
1 ... 250 K
88 / 102 K
See section 27
5
III
Integration time constant, Tn
5 ... 999 sec.
16 sec.
See section 27
6
III
Running time of the motorized control
valve
5 ... 250 sec.
15 sec.
See section 27
7
III
Neutral zone, Nz
0 ... 9 K
3 K
See section 27