The grey
side of the
ECL Card
Ex
tended ser
vic
e
The grey
side of the
ECL Card
Ex
tended ser
vic
e
32d
Service parameter(s) 21
Service parameter(s) 22-23
32e
21 Total stop
Circuit
Setting range
Factory setting
I / II
ON / OFF
OFF / OFF
Decide whether you want a total stop during the setback
temperature period.
ON:
The desired flow temperature is lowered
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
Desired flow
temp. (°C)
10 °C
Time
OFF:
No total stop
Desired flow
temp. (°C)
10 °C
Time
22 Pump exercise
Circuit
Setting range
Factory setting
I / II
ON / OFF
ON / ON
Exercises the pump to avoid blocking in periods without heat
demand.
ON:
The pump is switched ON for 1 minute every
third day around noon.
OFF:
The pump exercise is not active.
23 Valve exercise
Circuit
Setting range
Factory setting
I
ON / OFF
OFF
Exercises the valve to avoid blocking in periods without heat
demand.
ON:
The valve receives a signal to open and
close every third day around noon.
OFF:
The valve exercise is not active.