background image

EKC 361 

Manual  RS8AE802  ©  Danfoss  12-2009 

13

Method for fixing Kp, Tn and Td

Described below is a method (Ziegler-Nichols) for fixing Kp, Tn 

and Td.

1. The system is made to regulate the temperature at the required 

reference with a typical load. It is important that the valve regu

-

lates, and that it is not fully open.

2. Parameter u05 is read. The actuator’s min. and max. setting is 

adjusted, so that the average of the min. and max. values is 
equal to the read u05.

3. The controller is set, so that it will regulate as a P-controller. (Td is 

set to 0, Tn in pos. OFF (600), and Q-Ctrl.mode is set at 0).

4. The stability of the system is examined by stopping the system 

for, say, one minute (using the start/stop setting or the switch). 
Now check how the building-up of the temperature proceeds. 
If the building-up peters out, raise Kp a little and repeat the 
start/stop operation. Continue with this until you obtain a build

-

ing-up which does 

not

 peter out.

5. Kp is in this case the critical amplification (Kp

critical

) and the build-

ing-up time for the continued oscillation is the critical building-

up time (T

critical

).

6. Based on these values, the regulating parameters can now be 

calculated and subsequently set:
• If PID regulation is required:

Kp <  0.6x Kp

critical

   

 

Tn >  0.5x T

critical 

 

Td <  0.12x T

critical

• If PI regulation is required:

Kp <  0.45x Kp

critical

 

Tn >  0.85x T

critical

7. Reset the values for the controller’s min. and max. tem peratures 

and Q-Ctrl.mode.

Adjustment of the actuator’s min. and max. temperatures

At the first setting these values were set to 10 K outside of the 
expected temperature in order to eliminate the tolerances in the 
actuator. By adjusting the two values to the values where the 
valve is exactly in mesh, the valve will all the time remain active in 

its regulation.

If the actuator is replaced at a later date, this procedure must be 

repeated for the new actuator.

Min.

By adjusting the actuator’s min. temperature you obtain a limit 
for how low a pressure can occur in the evaporator (the point is 
where the valve starts a limitation of the refrigerant flow).
The system must be put in an operating situation where max. 
capacity is called for (large refrigeration need).
The min. temperature must now be changed upwards step by 
step, at the same time as the evaporating pressure is read on the 
system’s manometer.
When a change of the evaporating pressure is registered, this is 
the point where the valve is exactly in mesh. (If frost protec tion is 
required for the system, the value can be raised to the belonging 

value).

Max.
By adjusting the actuator’s max. temperatur you obtain a limit for 
how high a pressure can occur in the evaporator (the refrigerant 
flow is blocked completely).
The system is put in an operating situation where there is no call 
for refrigeration capacity (no refrigerant flow).
The max. temperature is now changed downwards step by step, at 
the same time as the evaporating pressure is read on the system’s 

manometer. 

When a change of the evaporating pressure is registered, this 

is the point where the valve opens. Adjust the setting a little 

upwards, so that the valve will again close completely for the 
refrigerant flow. (If the actual application has a requirement re

-

garding max. evaporating pressure, a lower setting may of course 
be selected, so that the pressure is limited).

Fine adjustments

When the system has been operating for a while, it may be 
required for some systems to optimise some of the adjustments. 
Below we have a look at settings having an influence on the speed 
and accuracy of the regulation.

Summary of Contents for EKC 361

Page 1: ...REFRIGERATION AND AIR CONDITIONING Controller for regulation of media temperature EKC 361 Manual...

Page 2: ...pt high and waste is limited A transient phenomenon can be controlled with the adaptive function Select either Fast build up where underswings are allowed Not quite so fast build up where underswings...

Page 3: ...r ICS PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line Digital output on terminal 9 and 10 It will follow the status of Digital Input however if a low temperature alarm is d...

Page 4: ...hecks the temperature pres sure in the actuator s pressure vessel In this way a very stable control system is obtained If there is a deviation between the required and the registered temperature the c...

Page 5: ...an also be accomplished with the external switch function See also appendix 1 r12 Main Switch Alarm The controller can give alarm in different situations When there is an alarm all the light emitting...

Page 6: ...nd to the setting in o27 Sair Saux max value 20 mA will correspond to the setting in o28 If ICM has been selected n03 6 OD u24 to control ICM is send out to the analog output o27 and o28 is not active...

Page 7: ...ssolution wil be better than 0 2 C o28 Temp at AO max Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor calibrated value u01 A...

Page 8: ...splay Shows the temperature at the selected sensor At ICM valve OD also can be selected C Reference Set the required room temperature 70 C 160 C 10 C Temperature unit r05 C F C Input signal s temperat...

Page 9: ...rtant that the installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically...

Page 10: ...ogramme will for exam ple upload all the collected tempera ture values once a day Measurements are shown at one side and settings at the other You will also be able to see the parameter names of the f...

Page 11: ...ion pressure will have a belonging to value which in turn indicates the value of the n02 setting Due to tolerances in the actuator the setting value must be 10 K lower than shown in the curve CVQ KVQ...

Page 12: ...V a c 10 15 under all working conditions If voltage drops under some working conditions the transformer is undersized Loss of charge in actuator Replace actuator Media temperature too high Actuator fe...

Page 13: ...alues where the valve is exactly in mesh the valve will all the time remain active in its regulation If the actuator is replaced at a later date this procedure must be repeated for the new actuator Mi...

Page 14: ...14 Manual RS8AE802 Danfoss 12 2009 EKC 361...

Page 15: ...EKC 361 Manual RS8AE802 Danfoss 12 2009 15...

Page 16: ...right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications a...

Reviews: