EKC 361
Manual RS8AE802 © Danfoss 12-2009
7
Selection of running display value
If S
air
(017=Air) will be shown as running display value. If lower button is activated S
aux
will
be displayed for 5 sec, and then return to S
air
S
air
will send out to the analog output. See also (o09),(o27),(o28)
If (017=Au) S
aux
will be shown as running display value. If lower button is activated S
air
will
be displayed for 5 sec, and then return to S
aux
S
aux
will send out to the analog output. See also (o09),(o27),(o28)
If ICM has been selected (n03=6)
If (017=Air) S
air
(017=Air) will be shown as running display value. If lower button is activated
OD (u24) will be displayed for 5 sec, and then return to S
air
If (017=Au) OD (u24) will be shown as running display value. If lower button is activated
S
air
will be displayed for 5 sec, and then return to OD (u24)
o17
Display Aux/Air
Aux =0
Air = 1
(Setting for the function o09)
Set the temperature value where the output signal must be minimum
(0 or 4 mA)
o27
Temp. at AO min.
(Setting for the function o09)
Set the temperature value where the output signal must be maximum (20 mA). (With a tem
-
perature range of 50°C (differential between the settings in o27 and o28) the dissolution will be
better than 0.1 °C. With 100°C the dissolution wil be better than 0.2°C.)
o28
Temp. at AO max.
Service
A number of controller values can be printed for use in a service situation
Read the temperature at the S
air
sensor (calibrated value)
u01
Air temp.
Read the control reference
(Se any contribution from external signal)
u02
Air reference
Read temperature at the S
aux
sensor (calibrated value)
(This showing can also be uploaded from the normal display, if you push the lowermost button
for almost a second)
u03
Aux. temp.
Read valve’s actuator temperature
u04
Actuator temp.
Read reference for valve’s actuator temperature
u05
Actuator Ref.
Read value of external current signal
u06
AI mA
Read value of transmitted current signal
u08
AO mA
Read status of input DI (start/stop input)
u10
DI
ICM opening degree.
Only active if (n03)=6
u24
OD%
--
DO1 Alarm
Read status of alarm relay
--
DO2 Cooling
Read status of relay for solenoid valve
--
DO3 Fan
Read status of relay for fan
Operating status
Operating status of the controller can be called forth in the display. Push briefly (1s) the upper
button. If there is a status code, it will be shown on the display. (Status codes have lower priority
than alarm codes. In other words, you cannot see a status code, if there is an active alarm).
The individual status codes have the following meanings:
EKC State
(0 = regulation)
S10: Refrigeration stopped by the internal or external start/ stop
10
S12: Refrigeration stopped due to low S
air
12