5.3.2. Class ID 0x01
Attrib-
ute
Access
Name
Data
type
Min/
Max
Units
Default Description
1
Get
Vendor
USINT
97
Danfoss Drives
Vendor Code
2
Get
Device
Type
UNIT
2
AD/DC Motor
3
Get
Product
Code
UNIT
100
See EDS File Sec-
tion
4
Get
Revision
UNIT
Software version
on FC 100, 200
or 300
5
Get
Status
UNIT
6
Get
Serial
Number
UDINT
From frequency
converter
7
Get
Product
Name
String
FC 100, 200 or
300
10
Get/Set
Heartbeat
Interval
USINT
0-255
sec
0
Off
5.3.3. Class ID 03h DeviceNet Object
This is a standard DeviceNet Object for configuration and status of the DeviceNet connection.
The attributes supported for this class are listed below.
5.3.4. Class ID 0x03
Attrib-
ute
Access
Name
Data
type
Min/
Max
Units
Default Description
1
Get/Set
MAC ID
USINT
0-63
63
Node address
2
Get/Set
Baud Rate USINT
0-2
0
0=125
1=250
2=500
4
Get
BOC
Bus-Off Counter
5
Get
Allocate
informa-
tion
Only required if
predefined Mas-
ter/Slave is im-
plemented
6
Get
MAC ID
Switch
changed
BOOL
0-1
0
The node ad-
dress switch has
changed since
the last power-
up/reset
7
Get
Baud rate
switched
from last
power up
BOOL
0-1
0
The baud rate
switch has
changed since
the last power-
up
5. How to Access the Parameters
FC 100/ 200/ 300 DeviceNet
40
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
5