Frame
IP20
IP21
IP55
IP66
A3/A4/A5
-
-
2
2
B1/B2
-
*
2.2
2.2
C1/C2/C3/C4
-
*
2.2
2.2
* No screws to tighten
- Does not exist
Table 2.3 Tightening Torques for Covers (Nm)
2.4.5.2 Control Terminal Types
and shows the removable frequency
converter connectors. Terminal functions and default
settings are summarized in
2
3
4
1
130BB921.11
Illustration 2.11 Control Terminal Locations
12 13 18 19 27 29 32 33 20 37
39 42 50 53 54 55
61 68 69
130BB931.10
1
2
3
Illustration 2.12 Terminal Numbers
•
Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. FC
302 and FC 301 (optional in A1 enclosure) also
provide a digital input for STO (Safe Torque Off)
function.
•
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
•
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
•
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
•
Also provided are two Form C relay outputs that
are in various locations depending upon the
frequency converter configuration and size
•
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See
for terminal ratings details.
Terminal description
Terminal Parameter
Default
setting
Description
Digital inputs/outputs
12, 13
-
+24 V DC
24 V DC supply
voltage. Maximum
output current is 200
mA total (130 mA for
FC 301) for all 24 V
loads. Useable for
digital inputs and
external transducers.
18
5-10
[8] Start
Digital inputs.
19
5-11
[10] Reversing
32
5-14
[0] No
operation
33
5-15
[0] No
operation
27
5-12
[2] Coast
inverse
Selectable for either
digital input or
output. Default setting
is input.
29
5-13
[14] JOG
20
-
Common for digital
inputs and 0 V
potential for 24 V
supply.
37
-
Safe Torque
Off (STO)
Safe input. Used for
STO.
Analog inputs/outputs
39
-
Common for analog
output
42
6-50
[0] No
operation
Programmable analog
output. The analog
signal is 0-20 mA or
4-20 mA at a
maximum of 500
Ω
50
-
+10 V DC
10 V DC analog
supply voltage. 15 mA
maximum commonly
used for potenti-
ometer or thermistor.
53
6-1*
Reference
Analog input.
Selectable for voltage
or current. Switches
A53 and A54 select
mA or V.
54
6-2*
Feedback
Installation
VLT
®
AutomationDrive Operating
Instructions
16
MG33AM02 - VLT
®
is a registered Danfoss trademark
2
2