To run AMA
1.
Press [Main Menu] to access parameters.
2.
Scroll to parameter group
1-** Load and Motor
.
3.
Press [OK].
4.
Scroll to parameter group
1-2* Motor Data
.
5.
Press [OK].
6.
Scroll to
1-29 Automatic Motor Adaptation (AMA)
.
7.
Press [OK].
8.
Select
Enable complete AMA
.
9.
Press [OK].
10.
Follow on-screen instructions.
11.
The test will run automatically and indicate when
it is complete.
3.7 Check Motor Rotation
Before running the frequency converter, check the motor
rotation.
1. Press [Hand On].
2. Press [
►
] for positive speed reference.
3. Check that the speed displayed is positive.
When
1-06 Clockwise Direction
is set to
[0] Normal
(default
clockwise):
4a. Verify that the motor turns clockwise.
5a. Verify that the LCP direction arrow is
clockwise.
When
1-06 Clockwise Direction
is set to
[1] Inverse
(counter-
clockwise):
4b. Verify that the motor turns counter-clockwise.
5b. Verify that the LCP direction arrow is counter-
clockwise.
3.8 Check Encoder Rotation
Check encoder rotation only if encoder feedback is used.
Check encoder rotation in default open loop control.
1.
Verify that the encoder connection is according
to
:
130BA090.11
+24V DC
A
B
GND
13
12
18
37
32
27
19
29
33
20
24V or 10-30V encoder
Illustration 3.7 Wiring Diagram
NOTE
When using an encoder option, refer to the option manual
2.
Enter the Speed PID feed-back source in
7-00 Speed PID Feedback Source
.
3.
Press [Hand On]
4.
Press [
►
] for positive speed reference
(
1-06 Clockwise Direction
at
[0] Normal
).
5.
Check in
16-57 Feedback [RPM]
that the feed-back
is positive
NOTE
If the feedback is negative, the encoder connection is
wrong!
Start Up and Functional Tes...