FCM 300 Series
MG.03.B6.02 - VLT is a registered Danfoss trademark
14
T
echnical data
Mains supply, TT, TN and IT* (L1, L2, L3):
- Supply voltage 380-480 V units ........................................................... 3 x 380/400/415/440/460/480 V ±10%
- Supply frequency ................................................................................................................................ 50/60 Hz
- Max. imbalance of supply voltage ......................................................................... ±2% of rated supply voltage
- Power factor / cos
ϕ .......................................................................................................
max. 0.9/1.0 at rated load
- No. of switching operations on supply input L1, L2, L3 ................................................. approx. 1 time/2 min
See chapter 10, "Special conditions".
*) Not valid for RFI class 1B units
Torque characteristics:
- Starting torque/overload torque .............................................................................................. 160 % for 1 min
- Continuous torque ........................................................................................................................ see page 84
■
FCM 305-375 for 3 phases, 380-480 V
■
General technical data
FCM
FCM
FCM
FCM
FCM
3 0 5
3 0 5
3 0 5
3 0 5
3 0 5
3 0 7
3 0 7
3 0 7
3 0 7
3 0 7
3 1 1
3 1 1
3 1 1
3 1 1
3 1 1
315
315
315
315
315
3 2 2
3 2 2
3 2 2
3 2 2
3 2 2
3 3 0
3 3 0
3 3 0
3 3 0
3 3 0
3 4 0
3 4 0
3 4 0
3 4 0
3 4 0
3 5 5
3 5 5
3 5 5
3 5 5
3 5 5
3 7 5
3 7 5
3 7 5
3 7 5
3 7 5
Motor output
[HP]
0.75
1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
[kW]
0.55
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
Motor torque
2 pole [Nm]
1.8
2.4
3.5
4.8
7.0
9.5
12.6
17.5
24.0
4 pole [Nm]
3.5
4.8
7.0
9.6
14.0
19.1
25.4
35.0
48.0
Frame
size [mm]
80
80
90
90
100
100
112
132
132
Weight [kg]
11
13
17
20
26
28
37
56
61
Input current [A]
380 V
2 p
1.4
1.6
2.2
2.8
4.1
5.3
7.0
9.3
13.0
4 p
1.4
1.7
2.5
3.3
4.7
6.4
7.9
11.1
15.3
480 V
2 p
1.2
1.3
1.8
2.3
3.3
4.2
5.6
7.4
10.2
4 p
1.1
1.4
2.0
2.6
3.7
5.1
6.4
8.8
11.9
Power
terminals
[AWG]
10
10
10
10
10
10
10
6
6
[mm
2
]
4
4
4
4
4
4
4
10
10
Gland sizes 3XPG16 3XPG16 3XPG16 3XPG16 3XPG16 3XPG16 3XPG16 1XPG21/ 1XPG21/
3XPG16 3XPG16
Max. prefuse
UL
1)
[A]
10
10
10
10
10
15
15
25
25
IEC
1)
[A]
25
25
25
25
25
25
25
25
25
1)
Type gG prefuses must be used. If you want to maintain UL/cUL you must use prefuses of the type
Bussmann KTS-R 500 V or Ferraz Shawmut, type ATMR (max. 30A). The fuses must be placed for protection
in a circuit that is capable of supplying a maximum of 100,000 amps RMS (symmetrical), 500 V maximum.