FCM 300 Series
MG.03.B6.02 - VLT is a registered Danfoss trademark
38
001 Language
(LANGUAGE)
Settings:
✭
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPAÑOL)
[4]
Italian (ITALIANO)
[5]
State when delivered may vary from factory setting.
Function:
The choice in this parameter defines the language to
be used on the display.
Description of choice:
There is a choice of
English
[0],
German
[1],
French
[2],
Danish
[3],
Spanish
[4] and
Italian
[5].
002 Local/remote control
(OPERATION SITE)
Settings:
✭
Remote control (REMOTE)
[0]
Local control (LOCAL)
[1]
Function:
There is a choice of two methods of controlling the
FC motor:
Remote control
[0] and
Local control
[1].
Description of choice:
If
Remote control
[0] is selected, the FC motor can be
controlled via:
1. The control terminals or the serial communication
port .
2. The [START] key. However, this cannot overrule
Stop commands (also start-disable) entered via
the digital inputs or the serial communication port.
3. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameters 014, 015 and 017).
If
Local control
[1] is selected, the FC motor can be
controlled via:
1. The [START] key. However, this cannot override
Stop commands on the digital terminals (if [2] or
[4] has been selected in parameter 013).
2. The [STOP], [JOG] and [RESET] keys, provided
that these are active (see parameters 014, 015
and 017).
3. The [FWD/REV] key, provided that this has been
activated in parameter 016 and that in parameter
Operation & Display
013 a choice of [1] or [3] has been made.
4. Via parameter 003 the local reference can be
controlled by means of the "Arrow up" and "Arrow
down" keys.
003 Local reference
(LOCAL REFERENCE)
Settings:
Par 013 set for [1] or [2]:
0 - f
MAX
✭
000.000
Par 013 set for [3] or [4] and par. 203 = [0] set for
:
Ref
MIN
- Ref
MAX
✭
000.000
Par 013 set for [3] or [4] and par. 203 = [1] set for:
-Ref
MAX
- + Ref
MAX
✭
000.000
Function:
This parameter allows manual setting of the desired
reference value (speed or reference for the selected
configuration, depending on the choice made in
parameter 013).
The unit follows the configuration selected in
parameter 100, provided that
Process regulation,
closed loop
[3] has been selected.
Description of choice:
Local
[1] must be selected in parameter 002 for this
parameter to be used.
The set value is saved in the case of a voltage drop-
out, see parameter 019.
In this parameter Data Change Mode is not exited
automatically (after time out).
Local reference cannot be set via the serial
communication port.
Warning: Since the value set is remembered
after the power has been cut, the motor
may start without warning when the power is rein-
stated; if parameter 019 is changed to
Auto restart
,
use
saved ref.
[0].
✭
=
factory setting. ( ) = display text [ ] = value for use in communication via serial communication port