FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
106 Rated motor speed
(MOTOR NOM. SPEED)
Value:
XX rpm - depends on the FCM 300
[XX]
Function:
Read only parameter.
126 DC braking time (DC BRAKING TIME)
Settings:
0.0 - 60.0 sec.
[0-600]
✭
10.0 sec.
[100]
Function:
This parameter is for setting the DC braking time for
which the DC braking voltage (parameter 132) is to
be active.
0.0 sec. = OFF
Description of choice:
Set the desired time.
127 DC brake cut-in frequency
(DC BRAKE CUT-IN)
Settings:
0.0 - f
MAX
(parameter 202)
[0 - ]
✭
0.0 Hz = OFF
[0]
Function:
This parameter is for setting the DC brake cut-in
frequency at which the DC braking voltage
(parameter 132) is to be active, in connection with a
Stop command.
132 DC braking voltage
(DC BRAKE VOLTAGE)
Settings:
0 - 100 %
[0-100]
✭
0 %
[0]
Function:
If the stator in an asynchronous motor is supplied
with DC voltage, a braking torque will accur. The
braking torque depends on the selected DC braking
voltage. The DC braking voltage is stated as a
percentage of maximum braking voltage.
Description of choice:
Set the desired voltage as a specified percentage of
maximum braking voltage.
NOTE!
The DC braking voltage cannot be used as a
holding brake.
✭
=
General factory setting - also applying to spare part unit, H
H
H
H
H = HVAC setting, IIIII = Industrial setting, ( ) = parameter
window text. [ ] = value for use in communication via serial communication port
Description of choice:
Set the desired frequency.
128 Motor thermal protection
(MOTOR THERM. PRO
TEC.)
Settings:
✭
Disable (DISABLE)
[0]
Enable (ENABLE)
[1]
Function:
The motor temperature is measured with a
thermistor (optional).
Description of choice:
If
Disable
[0] is selected no tripping is required when
the motor is overloaded.
Parameter Group 1: Load and Motor
9-3
Function:
Read only parameter.
105 Motor current (MOTOR CURRENT)
Value:
XX.X X A- depends on the FCM 300
[XXXX]
Function:
Read only parameter.