© Danfoss | Climate Solutions | 2023.07
AX450533577373en-000201 | 5
Disassembly
3.2 Disconnecting the electrical connections
X
Do not damage any cables and components.
Damaged parts must be repaired or replaced immediately.
HG7/HGZ7
¾
Remove the terminal box (4 hexagon head screws M6,
AF10).
¾
Remove the terminal board (10 hexagon head screws
M10x35, AF17).
¾
Remove the electrical lines from the underside of the
terminal board.
¾
Remove the terminal box (4 hexagon head screws M8,
AF13).
¾
Remove the socket head screws (10x M10x20, AF8) from
the terminal board.
¾
The terminal board must be pushed off the compressor
housing.
To do so, completely remove the nuts (M6, AF10 and M8,
AF13) from the threaded pins of the earthing connector.
Now rotate the threaded pins (socket head AF3 and AF4)
further in order to push the terminal board out of the
compressor housing. The silicon bonded joint is dest-
royed in the process!
¾
Remove the electrical lines from the underside of the
terminal board.
HG8/HG88e