3.4 Removing the stator
WARNING
The heavy weight of the stator can potentially be dangerous; risk of falling, danger of crushing.
X
Use a suitable hoist for the removal.
X
Take the measures required to safely remove the stator by placing a square of the correct height at the
open end of the motor housing. Prevent inadvertent rolling of the removed stator.
¾
Carefully pull the stator out of the compressor housing and pay attention to the cable!
¾
Remove the feather key from the compressor housing.
¾
Remove both stator screws (M8x20).
¾
Remove both stator screws (M8x10, M8x20).
HG7/HGZ7
HG8/HG88e
max.
75kg
Disassembly