Selection number
Selection name
Selection description
28
Catch Up
Increase reference value by percentage (relative) set in
P 5.5.3.13
Freeze Up/Down Step Delta
. See
.
29
Slow Down
Reduce reference value by percentage (relative) set in
P 5.5.3.13
Freeze Up/Down Step Delta
. See
.
34
Ramp Bit 0
Enable a selection from the 2 ramps available.
45
Latched Start Reverse
The motor starts to run reverse when a pulse is applied for
minimum 4 ms. The motor stops when stop commands are
given.
51
External Interlock
This function makes it possible to give an external fault to
the frequency converter. This fault is treated as an internally
generated alarm.
60
Counter A (up)
Input for increment counting in the SLC counter A.
61
Counter A (down)
Input for decrement counting in the SLC counter A.
62
Reset Counter A
Input for reset of counter A.
63
Counter B (up)
Input for increment counting in the SLC counter B.
64
Counter B (down)
Input for decrement counting in the SLC counter B.
65
Reset Counter B
Input for reset of counter B.
101
Sleep
A signal applied puts the frequency converter into sleep mode.
P 9.4.1.4 T15 Digital Input
Select the function from the available digital input range.
Default value:
1 [Reset]
Parameter type:
Selection
Parameter
number:
512
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
No Operation
No reaction to signals transmitted to the terminal.
1
Reset
Resets the frequency converter after a trip/alarm. Not all alarms
can be reset.
2
Coast Inverse
Coasting stop, inverted input (NC). The frequency converter
leaves the motor in free mode. Logic 0
⇒
coasting stop.
3
Coast and Reset Inverse
Reset and coasting stop inverted input (NC). Leaves motor in free
mode and resets frequency converter. Logic 0
⇒
coasting stop.
Logic 1 to Logic 0
⇒
reset.
226
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters
Summary of Contents for iC2