Selection number
Selection name
Selection description
56
Heat Sink Cleaning Warning, High
Activated when the heat sink temperature is not lower than the
calculated value. The calculated Value is equal to the maximum
value of
P 2.1.9 Heat Sink Temperature
minus the current value of
P 2.1.9 Heat Sink Temperature
.
60
Comparator 0
Use result of comparator 0 in logic rule.
61
Comparator 1
Use result of comparator 1 in logic rule.
62
Comparator 2
Use result of comparator 2 in logic rule.
63
Comparator 3
Use result of comparator 3 in logic rule.
64
Comparator 4
Use result of comparator 4 in logic rule.
65
Comparator 5
Use result of comparator 5 in logic rule.
70
Logic rule 0
Use result of logic rule 0 in logic rule.
71
Logic rule 1
Use result of logic rule 1 in logic rule.
72
Logic rule 2
Use result of logic rule 2 in logic rule.
73
Logic rule 3
Use result of logic rule 3 in logic rule.
74
Logic rule 4
Use result of logic rule 4 in logic rule.
75
Logic rule 5
Use result of logic rule 5 in logic rule.
80
SL digital output A
See
P 8.4.6.2 Action
. The output goes high whenever the smart
logic action
[38] Set digital out A high
is executed. The output
goes low whenever the smart logic action
[32] Set digital out A
low
is executed.
81
SL digital output B
See
P 8.4.6.2 Action
. The output goes high whenever the smart
logic action
[39] Set digital out B high
is executed. The output
goes low whenever the smart logic action
[33] Set digital out B
low
is executed.
160
No Fault
The output is high when no alarm is present.
161
Running Reverse
The output is high when the frequency converter is running
counterclockwise (the logical product of the status bits Running
AND Reverse).
165
Local Ref. Active
The output is high when local reference is activated.
166
Remote Ref. Active
The output is high when remote reference is activated.
167
Start Command Active
The output is high when there is an active start command, and
no stop command is active.
168
Drive in Local Mode
The output is high when the frequency converter is in Local
mode.
169
Drive in Remote Mode
The output is high when the frequency converter is in Remote
mode.
193
Sleep Mode
The frequency converter/system has entered sleep mode.
194
Lost Load Function
A lost-load condition is detected.
242
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters