RECIPROCATING COMPRESSORS

15

SYSTEM DESIGN RECOMMENDATIONS

Motor protection

Internal motor protection

Maneurop®  NTZ  compressors  have  a 
built-in  motor  protection  which  pro-
tects  the  motor  against  overheating, 
current overload and locked rotor con-
ditions.  Additional  external  overload 
protection is not compulsory but may 
still  be  advisable  for  alarm  function 
and to avoid the compressor tripping 
on its internal protection.
Further an external safety cut-out can 
also  de-energise  the  liquid  line  sole-
noid  valve  preventing  liquid  transfer 
from the condenser to the evaporator. 
Such function can not be handled by 
the built-in motor protector.
For the selection of an external motor 
protector the RLA (Rated Load Amps) 
values from page 9 can be used. 

Discharge temperature 

protection

Even  when  the  motor  windings  are 
protected against overheating by the 
internal  motor  protection,  the  com-
pressor  discharge  gas  temperature 
could  exceed  the  maximum  allowed 
value  of  135°C  when  the  compressor 

is  operated  outside  its  application 
envelope.  The  most  effective  protec-
tion  against  too  high  discharge  gas 
temperature  is  to  mount  a  discharge 
gas  thermostat.  An  accessory  kit  is 
available  from  Danfoss  which  inclu-

Voltage unbalance

Operating  voltage  limits  are  shown 
in  the  table  on  page  9.  The  voltage 
applied  to  motor  terminals  must  lie  
within these limits during both start-up 
and normal operation. The maximum 
allowable  voltage  unbalance  is  2%. 

A  thermal  overload  relay  shall  be  se-
lected to trip at not more than 140% of 
the RLA value. A circuit breaker shall be 
selected to trip at not more than 125% 
of the RLA value. Further requirements 
for the external protector are:

 Over-current protection; the protec-

tor must trip within 2 minutes at 110% 
of  the  Maximum  Continuous  Current 
(MCC). The  MCC  value  is  listed  in  the 
table on page 9 and stamped as A-max 
on the compressor nameplate.

 Locked rotor protection; the protec-

tor  must  trip  within  10  seconds  on  a 
start at locked rotor current (LRA)

  Single  phasing  protection;  the  pro-

tector must trip when one of the three 
phases fails.

Voltage unbalance causes high ampe-
rage on one or more phases, which in 
turn leads to overheating and possible 
motor damage.
The voltage unbalance is given by the 
following formula:

Cycle rate limit

No  more  than  12  starts  per  hour  (6 
when  a  soft  start  accessory  is  used) 
are  allowed.  A  higher  number  would 
reduce  the  service  life  of  the  motor-
compressor  unit.  If  necessary,  use  an 
anti-short-cycle timer within the con-
trol circuit. 
The system must be designed in a way 
that guarantees minimum compressor 
running time so as to provide sufficient 
motor cooling after start-up as well as 

proper  oil  return  from  the  system  to 
the compressor.
A  5-minute  delay  between  two  suc-
cessive compressor starts is being pro-
posed herein, with a 2-minute runtime 
after  each  start  and  a  3-minute  idle 
time between each stop and start.
Only  during  the  pump-down  cycle 
may  the  compressor  run  for  much 
shorter intervals.

|V

avg

 - V

1-2

 |+|V

avg

 - V

1-3

 |+|V

avg 

- V

2-3

 |

2 xV

avg

Vavg = Mean voltage of phases 1, 2 and 3

V1-2 = Voltage between phases 1 and 2

V1-3 = Voltage between phases 1 and 3

V2-3 = Voltage between phases 2 and 3.

% voltage unbalance:

 x 100

Summary of Contents for Maneurop NTZ048

Page 1: ...RECIPROCATING COMPRESSORS Selection Application Guidelines Reciprocating Compressors NTZ R404A R507A Low temperature refrigeration ...

Page 2: ...ase motor protection and suggested wiring diagram 10 Single phase electrical characteristics 10 Single phase motor protection and suggested wiring diagram 10 REFRIGERANTS AND LUBRICANTS 11 SYSTEM DESIGN RECOMMENDATIONS 12 Piping design 12 Operating limits 14 Motor protection 15 Discharge temperature protection 15 Liquid refrigerant control and charge limits 16 SOUND AND VIBRATION MANAGEMENT 18 Sou...

Page 3: ... existing LTZ range The NTZ series is engineered as a true low temperature compressor opti mised at 35 C with an extended evaporating temperature range from 45 C up to 10 C The compressors can be operated at a return gas tem perature suction gas temperature of 20 C even at low evaporating temperatures A liquid injection system is not re quired All components are of high quality and precision to as...

Page 4: ...60 460 3 60 400 3 50 230 1 50 230 3 50 575 3 60 500 3 50 380 3 60 NTZ048 120F0001 NTZ068 120F0002 NTZ096 120F0003 NTZ108 120F0004 NTZ136 120F0005 NTZ215 120F0006 NTZ271 120F0007 Compressor model Code no Motor voltage code 1 3 4 5 6 7 9 Nominal voltage 208 230 1 60 200 230 3 60 460 3 60 400 3 50 230 1 50 230 3 50 575 3 60 500 3 50 380 3 60 NTZ048 120F0008 NTZ068 120F0009 NTZ096 120F0010 NTZ108 120F...

Page 5: ...886 1 19 4 3 9 62 NTZ271 271 47 3 57 0 6955 1 24 8058 1 21 4 3 9 64 SPECIFICATIONS Technical specifications and nominal ratings Maneurop NTZ compressors comply with the following approvals and cer tificates Operating envelope R404A R507A Operating conditions R404A Evap temp 35 C Cond temp 40 C RGT 20 C SC 0K Approvals and certificates CE European Directive All models UL Underwriters Laboratories Mode...

Page 6: ...alisation 3 8 Schrader 1 4 35 37 118 68 Suction 147 Discharge 142 39 123 159 Threaded oil sight glass 141 263 17 17 ø 224 HM8 40 23 15 Silent block 6 1 cylinder OUTLINE DRAWINGS Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction Discharge Suction Discharge NTZ048 NTZ068 1 1 4 1 5 8 1 2 V09 V06 ...

Page 7: ... 145 125 188 171 8 38 82 74 68 265 Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 HM8 40 23 15 Silent block 7 OUTLINE DRAWINGS 2 cylinders Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction Discharge Suction Discharge NTZ096 NTZ108 1 3 4 1 1 4 7 8 3 4 V07 V04 NTZ136 1 3 4 1 1 4 1 1 8 3 4 V02 V04 ...

Page 8: ...r 1 4 Mounting hole for PTC crankcase heater Suction rotolock 1 3 4 Discharge rotolock 1 1 4 Oil equalisation 3 8 VE version only Rotolock connections size Pipe sizing Rotolock valve Suction Discharge Suction Discharge Suction Discharge NTZ215 NTZ271 1 3 4 1 1 4 1 1 8 3 4 V02 V04 30 19 HM12 50 H M12 50 Silent block 8 OUTLINE DRAWINGS ...

Page 9: ... 632 V 60 Hz 9 380 V 3 60 Hz 342 418 V Models NTZ048 NTZ068 NTZ096 NTZ108 NTZ136 Models NTZ215 NTZ271 Three phase electrical characteristics Compressor model Winding resistance between phases 7 at 25 C Ohm LRA Locked Rotor Amp A MCC Maximum Conti nuous Current A RLA Rated Load Amps A NTZ048 4 11 55 16 4 8 3 4 NTZ068 4 7 11 25 8 4 6 0 NTZ096 4 5 03 32 10 1 7 2 NTZ108 4 4 00 45 12 1 8 6 NTZ136 4 3 8...

Page 10: ...otected by a temperature current sensing bimetallic protector which senses the main and start win ding current as well as motor winding temperature If the motor were to be overloaded and the protector trips it might take up to several hours to reset and restart the compressor The standard CSR wiring system pro vides additional motor torque at start up by the use of a start capacitor in combination...

Page 11: ... HCFC Hydrochlorofluorcarbon with chlorine component ODP Ozone Depletion Potential base R11 ODP 1 Temperature glide difference between saturated vapor temperature and saturated liquid temperature at constant pressure Montreal protocol In such installation the factory charged polyolester POE lubricant must be replaced by mineral oil The use of hydrocarbons is not autho rised in NTZ compressors Only a...

Page 12: ...g trapped in the system and ensuring a constant oil return to the compressor As long as the amount of oil circulating through the system is small it will contribute to good system operation and improved heat transfer efficiency Lubricant getting trapped in the evaporator or suction lines will affect system performance and will ultima tely lead to compressor lubrication failures Where a poor oil retur...

Page 13: ... specific systems may differ from these average sizes The suction line must always be insu lated to limit suction gas superheat Oil charge and oil separator Filter driers For new installations with NTZ com pressors Danfoss recommends using the Danfoss DML 100 molecular sieve solid core filter drier Molecular sieve filter driers with loose beads from third party suppliers shall be avoided For servicing...

Page 14: ...ed off by the low pressure protection Depending on how the low pressure switch and delay timer are set short cycling can occur To avoid these problems several solu tions are possible based on reducing condenser capacity Liquid flooding of condensors note this solution requires extra refri gerant charge A non return valve in the discharge line is required and special care should be taken when designi...

Page 15: ...ip at not more than 140 of the RLA value A circuit breaker shall be selected to trip at not more than 125 of the RLA value Further requirements for the external protector are Over current protection the protec tor must trip within 2 minutes at 110 of the Maximum Continuous Current MCC The MCC value is listed in the table on page 9 and stamped as A max on the compressor nameplate Locked rotor prote...

Page 16: ...uring operation During system standstill and after pressure equalisation refrigerant will condensate in the coldest part of the system which may be the compressor when it is placed in a cold environ ment Ultimately the full system refri gerant charge can condensate in the compressor crankcase A large amount will dissolve in the compressor oil un til the oil is completely saturated with During norm...

Page 17: ...st be positio ned on the compressor shell as close as possible to the oil sump to ensure good heat transfer to the oil The be low illustrated mounting positions are recommended Belt crankcase heaters are not self re gulating Control must be applied to energise the belt heater once the com pressor has been stopped and then to de energise it while the compressor is running The belt heater must be en...

Page 18: ...losed in a sound proo fing material lined compartment Sound transmitted by mounting feet pipework and refrigerant should be treated the same way as vibration see next section Vibration The mounting grommets delivered with the compressor should always be used They will largely attenuate the compressor vibration transmit ted to the base frame These rubber grommets have been selected and calculated in...

Page 19: ...vacuum pumps etc dedicated for R404A and R507A Compressor handling mounting and connection Maneurop NTZ compressors must be handledwithcareandallhandlingpro cedures must be performed smoothly and gently Each NTZ has been fitted with one lift ring which shall always be used to lift the compressor Once the compressor is installed the lift ring shall never be used to lift the complete installation Alw...

Page 20: ...mpressor via the schrader valve to prevent air and moisture ingress Purging must start when the plugs are removed and pro ceeded during the brazing process When rotolock valves are used on the compressor they shall be closed im mediately after mounting thus kee ping the compressor isolated from atmosphere or from a not yet dehy drated system Note when the compressor is built into a pack or rack co...

Page 21: ...7 mbar A two sta ge vacuum pump shall be used with a capacity appropriate for the system volume It is recommended to use connection lines with a large diame ter and to connect these lines to the service valves and not to the schrader connection so as to avoid excessive pressure losses 3 Once the vacuum level of 500 mi crons has been reached the system must be isolated from the vacuum pump Wait 30 ...

Page 22: ... is recommended to keep the suction gas superheat at a lower value to increase the compres sor performance and service life On the other hand note that extremely low superheat values can increase the risk of unwanted liquid floodback to is a near azeotropic mixture and must be charged in the liquid phase R507A is an azeotropic mixture and can be charged either in liquid or gas phase Warning When a ...

Page 23: ......

Page 24: ... Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Maneurop Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ww...

Reviews: