RECIPROCATING COMPRESSORS
IP rating: 54 (with cable gland)
9
Voltage application range
ELECTRICAL CONNECTIONS AND WIRING
Electrical connections
Motor voltage code
Nominal voltage
Voltage application range
1
208-230 V / 1 / 60 Hz
187 – 253 V
3
200-230 V / 3 / 60 Hz
180 – 253 V
4
400 V / 3 / 50 Hz
460 V / 3 / 60 Hz
360 – 440 V (50 Hz)
414 – 506 V (60Hz)
5
230 V / 1 / 50 Hz
207 – 253 V
6
230 V / 3 / 50 Hz
207 – 253 V
7
500 V / 3 / 50 Hz
575 V / 3 / 60 Hz
450 – 550 V (50 Hz)
517 – 632 V (60 Hz)
9
380 V / 3 / 60 Hz
342 – 418 V
Models:
NTZ048 - NTZ068 - NTZ096 -
NTZ108 - NTZ136
Models:
NTZ215 - NTZ271
Three phase electrical
characteristics
Compressor
model
Winding
resistance
(between phases
+/- 7% at 25°C)
Ohm
LRA
(Locked Rotor
Amp)
A
MCC
(Maximum Conti-
nuous Current)
A
RLA
(Rated Load
Amps.)
A
NTZ048-4
11.55
16
4.8
3.4
NTZ068-4
7.11
25
8.4
6.0
NTZ096-4
5.03
32
10.1
7.2
NTZ108-4
4.00
45
12.1
8.6
NTZ136-4
3.80
51
14.3
10.2
NTZ215-4
2.23
74
22.3
15.9
NTZ271-4
1.61
96
27.0
19.3
Spade connectors
1/4” AMP-AWE
Earth M4-12
Knock-out
Ø 21 mm
Ø 21 mm
Screw
10-32 UNF x 9,5
Earth M4-12
Knock-out
Ø 29 mm
Ø 29 mm
IP rating: 55 (with cable gland)
Summary of Contents for Maneurop NTZ048