Instructions
118A5495A - AN405821998738en-000102 | 27
© Danfoss | Climate Solutions | 2023.02 | LCA012A024
Code
No.
Data display contents
Data
display
range
Min. unit
Remarks
C36
Relay output
0, 1
(0: Open
1: Short)
100's place: Crankcase heater 1
10's place: Spare
1's place: Spare
C37
Relay output
0, 1
(0: Open
1: Short)
100's place: Cooling fan
10's place: Ventilation fan
1's place: Spare
C38
Relay output
0, 1
(0: Open
1: Short)
100's place: SVHG1
10's place: Spare
1's place: SV-INJ1
C39
Relay output
0, 1
(0: Open
1: Short)
100's place: Spare
10's place: Spare
1's place: SV-OIL1-2
C40
Relay output/external output
0, 1
(0: Open
1: Short)
100's place: Spare
10's place: Spare
1's place: External output (CNZ1)
C41
External output
0, 1
(0: Open
1: Short)
100's place: External output (CNZ2)
10's place: Operation output (CNH)
1's place: Error output (CNY)
(*1) 7 segment display of C24, C25 indicates 10 min
-1
/count.
(*2) When the pulse input is set, 0 and 1 are switched if it changes Open
→
Short.
(*3) 0: OLS OFF (No oil), 1: OLS ON (With oil)
<Unit information>
C44
Compressor total operation time (CM1)
0~655
(*1)
1(100h)
C46
Medium pressure saturation temp.
-50~30
0.1°C
In the unit of 1°C in the range beyond display (-10°C
or under)
C47
Suction pressure saturation temp.
-50~30
0.1°C
In the unit of 1°C in the range beyond display (-10°C
or under)
C48
Subcooling coil temp. sensor 1 saturation pressure
0~8.5
0.1 bar
C49
Suction superheat degree 1
0~50
0.1deg
C51
Subcooling coil superheat degree
0~50
0.1deg
C52
Under-dome superheat degree 1
0~50
0.1deg
C54
Compressor total operation time after previous
maintenance (CM1)
0~655
(*1)
1(100h)
C61
Demand rate display
0~100
1%
(*1) 7 segment display of C44, C54 indicates 100 h/count.
<Control status>
C66
Control status
0~127
1
Digital
→
Analog display
C67
Protective control status
0~127
1
Digital
→
Analog display
C68
Cause of compressor stop
0~127
1
C73
Cause of compressor error detection 1
0~127
1
Displays No. of error detection, which occurred
most frequently, out of error detections occurred
after turning power on and starting operation.
This is retained in EEPROM memory till the cause of
compressor stop by first error occurs after turning
power on.
C74
Cause of compressor error detection 2
0~127
1
Displays No. of error detection, which occurred at
second place frequently, out of error detections
occurred after turning power on and starting
operation.
This is retained in EEPROM memory till the cause of
compressor stop by first error occurs after turning
power on.
C75
Cause of compressor error detection 3
0~127
1
Displays No. of error detection, which occurred
at third place frequently, out of error detections
occurred after turning power on and starting
operation.
This is retained in EEPROM memory till the cause of
compressor stop by first error occurs after turning
power on.