Instructions
28 | AN405821998738en-000102 - 118A5495A
© Danfoss | Climate Solutions | 2023.02 | LCA012A024
Code
No.
Data display contents
Data
display
range
Min. unit
Remarks
<Error counter information>
C80
Counter/current cut (CM1)
0~255
1
C84
Counter/compressor 1 start error
0~255
1
C86
Counter/inverter 1 step-out error
0~255
1
C95
Auto feed display 1
Feeds and displays C26, C28, C27.
C96
Data reset
<Others>
C97
Program/sub version
000~991
C98
Program/POL version
0.00~9.99
0.01
C99
Auto feed display 2
Alarm code display
• If following controls take place during operation, data corresponding to each control is displayed on 7-segment display
Code
No.
Data display contents
Data
display
range
Min. unit
Remarks
<User setting>
Setting of contents of functions described on
catalogue
P02
Gas cooler fan snow control
→
(15-8)
0: (Default)
0, 1
0: External snow fan control invalid (Default)
1 or more: External snow fan control valid
P03
Gas cooler fan snow control ON time setting
→
(15-8)
30: (Default)
10, 30~, 60
0 [sec]
30
Changes 10, 30, 60, 90 … 600.
P04
Demand rate change value
(1st stage at multistage setting)
80:
(Normally)
0, 40, 60, 80
P05
External output (CNZ1) function assignment
2: (Default)
0 – 20
1
P06
External output (CNZ2) function assignment
4: (Default)
0 - 20
1
P07
External input (CNS2) function assignment
1: (Default)
0 – 20
1: Demand input
2: Quiet mode input
3: (Spare)
4: Compulsory oil return control input
5: Gas cooler fan snow control input
9: Multistage demand input
P08
External input (CNS3) function assignment
4: (Default)
0 - 20
1
P09
External input (CNG1) function assignment
5: (Default)
0 - 20
1
P10
External input (CNG2) function assignment
9: (Default)
0 - 20
1
P11
Quiet mode setting
0: (Default)
0 - 9
1
P14
Multistage demand rate change value (2nd stage)
60:
(Normally)
0, 40, 60, 80
P15
Multistage demand rate change value (3rd stage)
40:
(Normally)
0, 40, 60, 80
P17
Operation permission/prohibition by external input
0: (Default)
0, 1
P19
Compressor oil check operation
Compressor speed
90: (Default)
30 - 100
P20
Error inspection reset
0,1
-
0
0: Invalid
Increases or decreases default value.
Special to performance measurement mode.
<Service personal setting>
Genaral setting adjusted by service personal at site
P58
Oil return time change value
5: (Default)
5 – 10
1 min.
P60
Oil return frequency change value
70: (Default)
40 – 104
(rps)
1
P61
EEVSC target superheat degree change value
20: (Default)
1 – 40 (0.5 –
20 deg)
1
P62
EEV-LB target discharge pipe temp. change
0: (Default)
-20 – 20 deg
1
Table 2: 7 segment software input