Operation data check sheet
(1) Condensing unit
Check the data of each code in the 7-segment display of the control PCB (PWB1).
7-segment have six digits, the three digits on the left shows code and the three digits on the right shows the data of the code.
Each code value increases by 1 for each press of SW7 of control PCB (PWB1) and by 10 for each press of SW8.
*1
Check the data in either below case 1 or 2
1. When the compressor is stopped and there is no pressure difference between medium pressure and low pressure
2. Compressor is runnning
*2
Check the data during compressor runnning
Code
Display
Unit
Criteria
data display by time
( : )
( : )
( : )
( : )
( : )
C00
Compressor operation frequency
rps
40~104
C02
Outdoor air temp.
°C
-20~50
C03
Gas cooler inlet temp.
°C
≤135
C04
Gas cooler outlet temp.
°C
≤60
C08
Discharge pipe temp.
°C
≤135
C10
Under-dome temp.
°C
≤85
C12
Power transistor temp.
°C
≤90
C15
Liquid feed pipe temp.
°C
-
C18
Current
A
≤19
C20
Medium pressure receiver inlet expansion valve
Pulse
180~400
C21
Liquid bypass electronic expansion valve
Pulse
10~470
C23
Subcool coil expansion valve
Pulse
60~470
C24
Fan 1 actual speed
rpm
0~1000
C25
Fan 2 actual speed
rpm
0~1000
C26
PSH high pressure sensor
Bar
65~140
C27
PSL low pressure sensor
Bar
6~46
C28
PSM medium pressure sensor
Bar
14~79
C29
Inverter current 1
A
≤23
C31
Pressure switch
left end
1
C32
Oil level switch
left end
1
*1
C46
Medium Pressure satuation temp
°C
-
C50
Suction superheat degree
deg
≥
5
C51
Subcool coil superheat degree
deg
≥
10
*2
C52
Under-dome superheat degree 1
deg
≥
10
Subcool Calculated By C46-C15
deg
≥
1
↑
↑
0
1
0
0