background image

Instructions

118A2221A - AN363632996019en-ZA0101 | 3

© Danfoss | DCS (CC) | 2020.12

secured to the wall, as shown in picture 2.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as 

possible to avoid oil contamination from 
ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  Braze with great care using state-of-the-art 

technique and vent piping with nitrogen gas 
flow.

 •  

Connect the required safety and control 
devices. When the schrader port is used for this, 
remove the internal valve.

  •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 
insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.

  •  Do not use dye for leak detection.
 •  Perform a leak detection test on the complete 

system.

  •  The maximum test pressure is 31 bar.
 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the 

system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

7 – Electrical connections

  •  Switch off and isolate the main power supply.
 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 

• 

 

Refer to wiring diagram for electrical 
connections details.

 •  

Ensure that the power supply corresponds 
to the unit characteristics and that the power 
supply is stable (nominal voltage ±10% and 
nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing. 

 •  

Make the power supply according to local 
standards and legal requirements.

 • 

 

The unit is equipped with an electronic 
controller. Refer to Manual 118U3808 for details.

 •  The unit is equipped with a main switch with 

overload protection. The overload protection is 
factory preset but it is recommended to check 
the value before taking the unit in operation. 
The value for the overload protection can be 
found in the wiring diagram in the front door of 
the unit.

 •  

The unit is equipped with high and low 
pressure switches, which directly cut the power 
supply to the compressor in case of activation. 
Parameters for high and low pressure cut outs 
are preset in the controller, adapted to the 
compressor installed in the unit.

 •  

P05 models are also equipped with phase 
sequence relay to protect the unit against 
phase loss/sequence/ asymmetry and under-/
over-voltage.

For units with a 3-phase scroll compressor (OP-
MPXMxxxxxxxxE), correct phase sequence for 
compressor rotation direction shall be observed.
 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 
orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main 

switch terminals T1, T2 and T3 respectively.

8 – Safety

Fusible Plug is not installed in unit, it is replaced 
with adapter blanking plug. 
Unit has liquid receiver with an Adapter Plug with 
3/8” NPT connection. installer/end user can select 
various options as mentioned in EN378-2 : 2016 
Article § 6.2.2.3
 •  Optyma Plus fitted with atmospheric pressure 

relief valve. Don’t connect any tube at end of the 
pressure relief valve.

 •  Once the pressure relief valve opens, don’t use 

dry air or oxygen to evacuate the refrigerants.

 •  Optyma Plus (P06 version only) factory fitted 

with pressure relief valve at 33 bar setting.

 

• 

 

Once pressure relief valve opens, Danfoss 
recommended to replace new pressure relief 
valve.

  •  The unit/installation into which the condensing 

unit is mounted/integrated, must be in 
accordance with the PED.

  •  Beware of extremely hot and cold components.
 •  Beware of moving components. Power supply 

should be disconnected while servicing.

9 – Filling the system

 •  

Never start the compressor under vacuum. 
Keep the compressor switched off.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 
charging of the system to 4 – 5 bar for R404A/ 
R448A/R449A/R407A/R407F/R452A and 
approx. 2 bar for R134a and R513A.

 •  

The remaining charge is done until the 
installation has reached a level of stable 
nominal condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

10 – Setting the electronic controller

  •  The unit is equipped with an electronic controller 

which is factory programmed with parameters 
for use with the actual unit. Refer to Manual 
118U3808 for details.

 •  

By default, the electronic controller display 
shows the temperature value for the suction 
pressure in °C. To show the temperature value for 
the condensing pressure, push the lower button 
(picture 3).

The electronic controller is factory preset for R404A 
or R449A or R452A or R134a depending on the 
model of compressor mounted and application 
(Refer Annexx in Optyma Controller installation 
manual). If another refrigerant is used, the 
refrigerant setting must be changed. Parameter 
r12 must be set to 0 before (software main switch= 
off).
 •  Push the upper button for a couple of seconds. 

The column with parameter codes appears.

  •  Push the upper or lower button to find parameter 

code o30.

 •  Push the middle button until the value for this 

parameter is shown.

  •  Push the upper or lower button to select the new 

value: 2 = R22, 3 = R134a, 36 = R513A, 17 = R507, 
19 = R404A, 20 = R407C , 21 = R407A, 37 = R407F, 
40 = R448A, 41 = R449A, 42 = R452A.

 •  Push the middle button to confirm the selected 

value.

 •  Push the upper or lower button to find parame-

ter code r84. 

 •  Push the middle button until the value for this 

parameter is shown as 125

 •  Push the upper button to select the new value: 

130.

11 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 
with both generally and locally applicable 
regulations and safety standards. Ensure that 
they are operational and properly set. 

 Check that the settings of high-pressure 

switches and relief valves don’t exceed the 
maximum service pressure of any system 
component.
 •  Verify that all electrical  connections inside the 

condensing unit are properly fastened as they 
could have worked loose during transportation.

 •  When a crankcase heater is required, the unit 

Summary of Contents for OPTYMA Plus OP-LPQM

Page 1: ...W Q R X Z Y Q Air in R Air out Unit W mm X mm Y mm Z mm Housing 4 Code n 114X34 or 114X44 250 900 700 700 Picture 1 Minimum mounting distances The condensing unit must only be used for its designed pu...

Page 2: ...Handle the unit with care The packaging allows for the use of a forklift or pallet jack Use appropriate and safe lifting equipment Store and transport the unit in an upright position Store the unit be...

Page 3: ...e Plug is not installed in unit it is replaced with adapter blanking plug Unit has liquid receiver with an Adapter Plug with 3 8 NPT connection installer end user can select various options as mention...

Page 4: ...thermostat DI1 and put them together with an insulated 250 Vac 10mm terminal bridge Remove wire 25 room thermostat DI1 and wire 11 compressor supply and put them together with an insulated 250VAC 10mm...

Page 5: ...l modifications in particular drilling welding broken feet and shock marks Compressor opened or returned unsealed Rust water or leak detection dye inside the compressor Use of a refrigerant or lubrica...

Page 6: ...ish Legend A 12 Hole for Mounting B Sight Glass C Controller Display D Air in E Air out F Suction Port G Liquid Port H Nameplate Electrical Cables Note all dimension are in mm H4 Instructions 6 AN3636...

Page 7: ...B3 High Pressure cartridge Switch auto reset PSH B4 Low Pressure cartridge Switch auto reset PSL D1 Pressure relief valve PRV R1 Ambient Temperature sensor T4 R2 Discharge Temperature Sensor T2 R3 Su...

Page 8: ...sor R4 R5 Auxiliary Temp Sensor optional R6 Crankcase Heater R7 NTC Resistor S1 Room Thermostat optional S2 Door Limit Switch X1 Terminal Supply Supply Fan Fan Alarm Alarm Comp Compressor CCH Crankcas...

Reviews: