itself is not a ”unit” in the scope this directive. 

 •  It is recommended to install the unit on rubber 

grommets or vibration dampers (not supplied).

  •  It is possible to stack units on top of each other.

Unit

Maximum 

stacking

Housing 1 

(Code no. 114X31-- or 114X41--)

3

Housing 2 

(Code no. 114X32-- or 114X42--)

2

Housing 3 

(Code no. 114X33-- or 114X43--)

2

Housing 4

(Code no. 114X34-- or 114X44--)

2

  •  When stacking, the topmost unit must be secu-

red to the wall, as shown in picture 2.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as pos-

sible to avoid oil contamination from ambient 
moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  Braze with great care using state-of-the-art 

technique and vent piping with nitrogen gas 
flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 
remove the internal valve.

  •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 
insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.

  •  Do not use dye for leak detection.
 •  Perform a leak detection test on the complete 

system.

  •  The maximum test pressure is 31*

)

 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

*

)

 25 bar for OP-.......AJ.... & OP-.......FH.... models

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the sys-

tem.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

7 – Electrical connections

  •  Switch off and isolate the main power supply.
 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  Ensure that the power supply corresponds to 

the unit characteristics and that the power sup-
ply is stable (nominal voltage ±10% and nomi-
nal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing. 

  •  Make the power supply according to local stan-

dards and legal requirements.

 •  The unit is equipped with an electronic control-

ler. Refer to Manual RS8GDxxx for details.

 •  

P02 version models (OP-xxxxxxxxxP02E) are 
equipped with Electronic circuit board (Module 
B Plus). Refer to section " Module B Plus User 
Guide " of this manual.

 •  The unit is equipped with a main switch with 

overload protection. The overload protection is 
factory preset but it is recommended to check 
the value before taking the unit in operation. 
The value for the overload protection can be 
found in the wiring diagram in the front door of 
the unit.

 •  The unit is equipped with high and low pres-

sure switches, which directly cut the power 
supply to the compressor in case of activation. 
Parameters for high and low pressure cut outs 
are preset in the controller, adapted to the com-
pressor installed in the unit.

 •  

P05 models are also equipped with phase 
sequence relay to protect the unit against 
phase loss/sequence/ asymmetry and under-/
over-voltage.

For units with a 3-phase scroll compressor (OP-
MPXMxxxxxxxxE), correct phase sequence for 
compressor rotation direction shall be observed.
 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 
orders of line phases L1, L2 and L3.

  •  Connect line phases L1, L2 and L3 to main swit-

ch terminals T1, T2 and T3 respectively.

8 – Safety

Fusible Plug is not installed in unit, it is replaced 
with adapter blanking plug. 
Unit has liquid receiver with an Adapter Plug with 
3/8” NPT connection. installer/end user can select 
various options as mentioned in EN378-2 : 2016 
Article § 6.2.2.3
  •  The unit/installation into which the condensing 

unit is mounted/integrated, must be in accor-
dance with the PED.

  •  Beware of extremely hot and cold components.
 •  Beware of moving components. Power supply 

should be disconnected while servicing.

9 – Filling the system

 •  

Never start the compressor under vacuum. 
Keep the compressor switched off.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 
charging of the system to 4 – 5 bar for R404A/ 
R448A/R449A/R407A/R407F/R452A and ap-
prox. 2 bar for R134a and R513A.

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 
condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

10 – Setting the electronic controller

 •  The unit is equipped with an electronic control-

ler which is factory programmed with parame-
ters for use with the actual unit. Refer to Manual 
RS8GDxxx for details.

 •  

By default, the electronic controller display 
shows the temperature value for the suction 
pressure in °C. To show the temperature value for 
the condensing pressure, push the lower button 
(picture 3).

The electronic controller is factory preset for R404A 
or R449A or R452A or R134a depending on the mo-
del of compressor mounted and application (Refer 
Annexx in Optyma Controller installation manual). 
If another refrigerant is used, the refrigerant setting 
must be changed. Parameter r12 must be set to 0 
before (software main switch= off).
 •  Push the upper button for a couple of seconds. 

The column with parameter codes appears.

 •  Push the upper or lower button to find parame-

ter code o30.

 •  Push the middle button until the value for this 

parameter is shown.

  •  Push the upper or lower button to select the new 

value: 2 = R22, 3 = R134a, 36 = R513A, 17 = R507, 
19 = R404A, 20 = R407C , 21 = R407A, 37 = R407F, 
40 = R448A, 41 = R449A, 42 = R452A.

 •  Push the middle button to confirm the selected 

value.

 

For P02 version models (OP-xxxxxxxxxP02E), 

if o30 value is 19= R404A or 40=R448A or 
41=R449A in controller, 

 •  Push the upper or lower button to find parame-

ter code r84. 

 •  Push the middle button until the value for this 

parameter is shown as 125

 •  Push the upper button to select the new value: 

130.

 

Change controller parameter o37 to 1 in 

case of SPPR retrofit. In case you add the SPPR 
(Supply monitoring relay) option to protect 
the compressor please change the setting O37 
from 0 to 1

11 – Verification before commissioning

 Use safety devices such as safety pressure swit-

ch and mechanical relief valve in compliance with 
both generally and locally applicable regulations 
and safety standards. Ensure that they are opera-
tional and properly set. 

 Check that the settings of high-pressure swit-

Summary of Contents for Optyma Plus

Page 1: ...h p 56 E Greek p 62 Norsk Norwegian p 68 B lgarski Bulgarian p 74 Rom n Romanian p 80 e tina Czech p 86 Polski Polish p 92 Russian p 98 GA Drawings GA tegninger GA Zeichnungen Sch mas GA Diagramas GA...

Page 2: ...4X41 250 550 456 456 Housing 2 Code n 114X32 or 114X42 250 650 530 530 Housing 3 Code n 114X33 or 114X43 250 760 581 581 Housing 4 Code n 114X34 or 114X44 250 900 700 700 Picture 1 Minimum mounting di...

Page 3: ...switches Replaceable filter drier Electronic controller Main circuit breaker Main switch with overload protection Fan and compressor capacitors Compressor contactor Supply monitoring relay Robust wea...

Page 4: ...are also equipped with phase sequence relay to protect the unit against phase loss sequence asymmetry and under over voltage For units with a 3 phase scroll compressor OP MPXMxxxxxxxxE correct phase s...

Page 5: ...nspections 14 Emergency running without controller In case of controller failure the condensing unit can still be operated when the controller standard wiring picture 4 is modified into a temporary wi...

Page 6: ...testing and test methods part 2 Condensing units 17 Warranty Always transmit the model number and serial number with any claim filed regarding this pro duct The product warranty may be void in followi...

Page 7: ...interface Module B Plus powers on power LED 1 will be solid red all the time When the Module is powered off power LED 1 will be off If Module B Plus powers on and has no error status LED 2 will be so...

Page 8: ...k Tryk p den nederste knap for at skifte til tempe raturv rdien for kondenseringstrykket Billede 3 Elektronisk regulatordisplay W Q R X Z Y Q Luft ind R Luft ud Enhed W mm X mm Y mm Z mm Hus 1 Kodenr...

Page 9: ...ter Elektronisk regulator Hovedafbryder hovedafbryder med overbe lastningssikring Ventilator og kompressorkondensatorer Kompressorkontaktor Forsyningsoverv gningsrel Robust vejrbestandigt hus V skeind...

Page 10: ...mpres sorens omdrejningsretning p aggregater med en 3 faset scroll kompressor OP MPXMxxxxxxxxE Find faser kkef lgen ved hj lp af en fasem ler for at etablere faser kkef lgen for fase L1 L2 og L3 Tilsl...

Page 11: ...og t thed kontrolleres Not r b de k lemiddeltypen og fyldningen foruden driftsbetingelserne Dette anvendes som referencepunkt ved fremtidige eftersyn 14 N ddrift uden regulator Kondenseringsaggregatet...

Page 12: ...g v skek lere til pro cesk ling Kondenseringsaggregatm linger er udf rt i henhold til standarden EN 13771 2 2017 Kom pressorer og kondenserende enheder til k ling Ydeevnepr vning og pr vningsmetoder D...

Page 13: ...r slukket vil LED 1 v re slukket Hvis Modul B Plus t nder og ikke har nogen fejl vil LED 2 v re konstant gr n Se billede 6 vedr rende placering af LED 1 og LED 2 p Modul B Plus Hvis Modul B Plus t nde...

Page 14: ...017 OP MPYM008 009 012 014 OP MPHM007 010 012 015 018 H1 OP LPQM026 048 068 074 OP MPBM018 024 026 034 OP MPXM034 046 057 OP MPGM033 34 OP MPHM026 034 OP LPHM026 H2 Instructions 104 AN18658643414604 0...

Page 15: ...on are in mm Dansk Legend A 12 hul til montering B Skueglas C Regulatordisplay D Luft ind E Luft ud F Suger r G V sker r H Typeskilt Elektriske ledninger Bem rk Alle m l angives i mm Deutsch Legende A...

Page 16: ...ning voor de bevestiging B Kijkglas C Regelaar display D Luchtinlaat E Luchtuitlaat F Zuigpoort G Vloeistofpoort H Typeplaatje Elektrische kabels Opmerking alle afmetingen zijn in mm Suomi Legenda A 1...

Page 17: ...dge Switch auto reset PSL R1 Ambient Temperature sensor T4 R2 Discharge Temperature Sensor T2 R3 Suction Temperature Sensor T3 R8 Discharge Temperature Sensor T1 Insulation P00 Models OP LPQM017 026 0...

Page 18: ...s 7 Fl ssigkeits Kugelabsperrventil 8 Saugseitiges Kugelabsperrventil B1 Druckmessaufnehmer Hochdruck P1 B2 Druckmessaufnehmer Niederdruck P2 B3 Hochdruck Patronendruckschalter automa tisches Zur ckse...

Page 19: ...presostat automatick reset PSL R1 Sn ma teploty okol T4 R2 Sn ma v tla n teploty T2 R3 Sn ma sac teploty T3 R8 Sn ma v tla n teploty T1 Izolace Polski Legenda 1 Spr arka 2 Elektryczny zaw r rozpr ny 3...

Page 20: ...Code G OP LPQM048 068 WD 1 Instructions 110 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02...

Page 21: ...Code G OP LPQM026 074 OP MPGM033 OP LPHM018 OP MPBM018 024 026 034 WD 2 Instructions 118U3276G AN18658643414604 001701 111 Danfoss Climate Solutions 2022 02...

Page 22: ...Code G OP MPXM068 080 Instructions 112 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 WD 3...

Page 23: ...Code E OP MPBM026 034 Instructions 118U3276G AN18658643414604 001701 113 Danfoss Climate Solutions 2022 02 WD 4...

Page 24: ...Code E OP LPQM048 068 074 OP MPXM034 046 057 Instructions 114 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 WD 5...

Page 25: ...Code E OP LPOM067 084 098 Instructions 118U3276G AN18658643414604 001701 115 Danfoss Climate Solutions 2022 02 WD 6...

Page 26: ...Instructions 116 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code E OP LPOM120 168 WD 7...

Page 27: ...Code G OP LPQM017 OP MPYM008 009 012 014 Instructions 118U3276G AN18658643414604 001701 117 Danfoss Climate Solutions 2022 02 WD 8...

Page 28: ...Instructions 118 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code G OP MPXM034 046 057 WD 9...

Page 29: ...Instructions 118U3276G AN18658643414604 001701 119 Danfoss Climate Solutions 2022 02 Code E OP LPQM215 271 OP MPXM125 162 WD 10...

Page 30: ...Instructions 120 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code E OP LPQM096 136 OP MPXM068 080 108 WD 11...

Page 31: ...Instructions 118U3276G AN18658643414604 001701 121 Danfoss Climate Solutions 2022 02 Code E P05 OP MPXM034 046 057 WD 12...

Page 32: ...Instructions 122 AN18658643414604 001701 118U3276G Danfoss Climate Solutions 2022 02 Code E P05 OP MPXM068 080 108 WD 13...

Page 33: ...Instructions 118U3276G AN18658643414604 001701 123 Danfoss Climate Solutions 2022 02 Code E P05 OP MPXM125 162 WD 14...

Page 34: ...ar g B4 Pressostato bassa pressione OFF 0 3bar g ON 0 5bar g C1 Condensatore di avviamento compressore C2 Condensatore di marcia compressore C3 Condensatore di marcia ventola 1 C4 Condensatore di marc...

Page 35: ...otorbeveiliging K1 Schakelaar K2 Startrelais M1 Compressor M2 Ventilatormotor 1 M3 Ventilatormotor 2 M4 Elektronisch expansieventiel Q1 Hoofdschakelaar R1 Sensor omgevingstemperatuur R2 R8 Voeler pers...

Page 36: ...e a motorului K1 Contactor K2 Releu de pornire M1 Compresor M2 Motor ventilator 1 M3 Motor ventilator 2 M4 Valv electronic de expansiune Q1 Comutator principal R1 Senzor temp ambiant R2 R8 Senzor temp...

Reviews: