background image

© Danfoss | DCS (vt) | 2021.03

BC372016561395en-000101 | 10

ADAP-KOOL

®

Summary of Contents for PAGM

Page 1: ...User Guide Gas detecting sensor Type PAGM for CO2 and Halocarbon www danfoss com...

Page 2: ...xhaust and zero air filter assembly 3 2 1 Gas Sample Probe 3 2 2 Purge Zero Air Carbon Filter Assembly 3 2 3 Battery 4 3 Front Panel Display Controls 4 4 General operation 5 4 1 Normal operation 5 4 2...

Page 3: ...tions For details on appropriate use refer to the general description application and operation discussions in this manual Before risking equipment damage or personal injury contact the manufacturer i...

Page 4: ...Before the unit can be used please connect the battery pack the unit is designed for a 16 V DC input Set battery voltage output to 16 V refer to the battery manufacturer s instruction sheet for detail...

Page 5: ...ng functions MEASURE indicates that the monitor is actively measuring the refrigerant gas level at the sample point To reset the peak value to zero press the ENTER button PURGE is displayed when the m...

Page 6: ...ng the SILENCE button while a fault condition still exists causes the internal audible alarm to turn OFF for a period of time as set by the SILENCE The front panel FAULT light will continue to flash O...

Page 7: ...act service department for further instructions 0800 Sample Flow Fault Check for a restriction in the gas sample inlet or exhaust Check the external Coalescing Inline Filter and or internal Hydrophobi...

Page 8: ...ied out at least once every 6 months but is dependent on the environment and usage If used in harsh environment where a large amount of dust and moisture particles are present in atmospheres the maint...

Page 9: ...ient CO2 level typically 390 ppm Example unit exposed to 5000 ppm should read 4610 ppm 5 which is from 4380 4840 ppm PAGM IR for halogen gas Set up the unit to measure R134A gas Using a regulator infl...

Page 10: ...Danfoss DCS vt 2021 03 BC372016561395en 000101 10 ADAP KOOL...

Reviews: