FRCC.PC.017.A1.02

16

A

PPLICATION

 

GUIDELINES

S

YSTEM

 

DESIGN

 

RECOMMENDATIONS

Essential piping design 
considerations

Proper piping practices should be employed to 
ensure adequate oil return, even under minimum 
load conditions with special consideration given 
to the size and slope of the tubing coming from 
the evaporator. Tubing returns from the evapora-
tor should be designed so as not to trap oil and to 
prevent oil and refrigerant migration back to the 
compressor during off -cycles.

If the evaporator lies above the compressor, the 
suction line must have a loop at the evaporator 
outlet to prevent refrigerant from draining into 
the compressor during off -cycles.

If the evaporator were situated below the com-
pressor, the suction riser must be trapped so as 
to prevent liquid refrigerant from collecting at the 
thermal bulb location (see fi g. 1).

When the condenser is mounted at a higher po-
sition than the compressor, a suitably sized «U»-
shaped trap close to the compressor is necessary 
to prevent oil leaving the compressor from drain-

ing back to the discharge side of the compressor 
during off  cycle. The upper loop also helps avoid 
condensed liquid refrigerant from draining back 
to the compressor when stopped (see fi g. 2). The 
maximum elevation diff erence between the in-
door and outdoor section cannot exceed 8 m. 
System manufacturers should specify precau-
tions for any applications that exceed these limits 
to ensure compressor reliability.

Piping should be designed with adequate three-
dimensional fl exibility. It should not be in contact 
with the surrounding structure, unless a proper 
tubing mount has been installed. This protection 
proves necessary to avoid excess vibration, which 
can ultimately result in connection or tube failure 
due to fatigue or wear from abrasion. Aside from 
tubing and connection damage, excess vibration 
may be transmitted to the surrounding structure 
and generate an unacceptable noise level within 
that  structure  as  well  (for  more  information  on 
noise and vibration, see the section on: "Sound 
and vibration management"). 

General

Successful application of scroll compressors is 
dependent on careful selection of the compres-
sor for the application. If the compressor is not 

correct for the system, it will operate beyond the 
limits given in this manual. Poor performance, re-
duced reliability, or both may result.

0.5 % slope,
4 m/s or more

0.5 % slope,
4 m/s or more

U-trap

U-trap, as short as possible

U-trap, as short as possible

max. 4 m

fig.1

max. 4 m

8 to 12 m/s

To condenser

Evaporator

Condenser

HP

U-trap

3D flexibility

Upper loop

LP

fig. 2

Summary of Contents for Performer HHP015T4LP6

Page 1: ...Performer Heat Pump scroll compressors 50 Hz R407C Selection application guidelines MAKING MODERN LIVING POSSIBLE...

Page 2: ......

Page 3: ......

Page 4: ...mum Continuous Current 10 Max Oper A Maximum Operating Amp 10 Winding resistance 10 Electrical connections 10 Nominal capacitor value 11 Internal motor protection 11 Phase sequence and reverse rotatio...

Page 5: ...ystem 20 Compressor sound radiation 20 Mechanical vibrations 20 Gas pulsation 20 INSTALLATION 21 System cleanliness 21 Compressor handling and storage 21 Compressor mounting 21 Compressor holding char...

Page 6: ...he motor stator is rigidly attached to the shell The rotor is shrink t onto the eccentric shaft The shaft is supported by two bearings one in the crankcase and the second below the motor SCROLL COMPRE...

Page 7: ...illustrat ed below The centre of the orbiting scroll traces a circular path around the centre of the xed scroll This movement creates compression pockets be tween the two scroll elements Low pressure...

Page 8: ...lication H high temperature Family HP heat pump R407C PVE Nominal capacity Model variation T motor design Motor voltage code 4 380 400V 3 50 Hz 5 220 240V 1 50 Hz Motor protection L internal motor pro...

Page 9: ...10 1 7 9 270 1 7 10 900 1 7 12 690 1 7 50 3 180 1 7 3 680 1 7 4 340 1 8 5 180 1 9 6 180 1 9 7 340 2 0 8 670 2 1 10 160 2 2 11 830 2 2 60 4 660 2 3 5 300 2 4 6 110 2 4 7 070 2 5 8 200 2 6 9 480 2 7 10...

Page 10: ...t spade terminals P terminal box type 1 7 41 41 29 5 5 16 18 UNC self tapping Recommended torque for mounting bolts 11 Nm 1 Nm 11 238 8 4 x 19 0 20 0 95 25 128 5 111 3 69 4 71 4 34 31 45 14 109 7 95 2...

Page 11: ...5 5 16 18 UNC self tapping Recommended torque for mounting bolts 11 Nm 1 Nm 11 Ring connect screw terminals C terminal box type C T S T R T 239 190 25 190 75 95 25 133 6 121 78 5 80 5 182 54 184 54 S...

Page 12: ...belled T1 T2 and T3 For single phase applications the terminals are labelled C common S start and R run Prior to energizing verify that leads and terminal connectors are in proper working condition Wa...

Page 13: ...Amp Winding resistance Winding resistance is the resistance between indicated terminal pins at 25 C resistance value 7 Winding resistance is generally low and it requires adapted tools for precise mea...

Page 14: ...he average for all phases Phase sequence and reverse rotation protection Voltage imbalance Internal motor protection The Performer Heat Pump scroll compressors are equipped with an internal line break...

Page 15: ...e directive 73 23 EC 93 68 EC Internal free volume CE 0062 or CE 0038 European Directive All models UL Underwriters Laboratories All models Other approvals certi cates CB certi cate available upon req...

Page 16: ...ant provides the best possible result in terms of reliability and compres sor lifetime The PVE lubricant is compatible with R22 which makes the Performer Heat Pump scroll compres sors a very versatile...

Page 17: ...ermostat Continuous opera tions beyond the compressor s operating range will cause serious damage to the compressor A DGT accessory is available from Danfoss refer to section Spare parts and accessori...

Page 18: ...in duce such a problem The minimum low pressure safety switch loss of charge safety switch setting is given in the above table For systems without pump down the LP safety switch must either be a manu...

Page 19: ...to the compressor when stopped see g 2 The maximum elevation di erence between the in door and outdoor section cannot exceed 8 m System manufacturers should specify precau tions for any applications...

Page 20: ...nditions As such reversible cycle applications require spe ci c precautions for ensuring a long compressor life and satisfactory operating characteristics Regardless of the refrigerant charge in the s...

Page 21: ...device OUTDOOR COIL Expansion device SYSTEM CHARGE TEST REQUIRED ACCEPTABLE SUMP SUPERHEAT TEMPERATURE ACCUMULATOR REQUIRED SYSTEM CHARGE TEST REQUIRED ACCEPTABLE SUMP SUPERHEAT TEMPERATURE ACCUMULAT...

Page 22: ...quipped with an internal pressure relief valve for protec tion against blocked condenser and fan failure conditions High pressure ratio Danfoss recommends the use of a thermostatic expansion valve for...

Page 23: ...jacket Sound power dBA With jacket Sound power dBA Without jacket Sound power dBA With jacket HHP015 70 62 70 62 HHP019 70 62 70 62 HHP021 71 63 71 63 HHP026 71 63 71 63 HHP030 72 64 72 64 HHP038 72 6...

Page 24: ...ndensablesubstancesand system contaminants such as metal shavings sol der and ux have a negative impact on compres sor service life Many of these contaminants are small enough to pass through a mesh s...

Page 25: ...use substantial damage to the internal parts of the system and compressor The PVE oil used in Performer Heat Pump scroll compressors is highly hygroscopic and will rap idly absorb moisture from the ai...

Page 26: ...Danfoss DCL solid core lter driers containing activated alumina are recommended The drier is to be oversized rather than under sized When se lecting a drier always take into account its capac ity wat...

Page 27: ...l together on one pallet They can be ordered in quantities of full pallets only multiples of 12 Each industrial pack pallet contains following accessories 4 grommets per compressor 4 sleeves per compr...

Page 28: ...45 suction Multipack 10 120Z0365 Rotolock adaptor 1 1 2 HHP all discharge Multipack 10 Type Code n Description Application Packaging Pack size 40 F 8173231 Run capacitor F HHP015 Multipack 10 60 F 120...

Page 29: ...VE 0 95 liter can HHP015 to 045 Multipack 1 Type Code No Description Application Packaging Pack Size 120Z5005 Mounting kit for 1 scroll compressor including 4 grommets 4 sleeves 4 bolts 4 washers All...

Page 30: ......

Page 31: ......

Page 32: ...We are o ering a single source for one of the widest ranges of innovative refrigeration and air conditioning components and systems in the world And we back technical solutions with business solution...

Reviews: