background image

Instructions

© Danfoss | DCS (CC) | 2018.02  | 3

FRCC.PI.020.A2.02

 •  The compressor ambient temperature may not 

exceed 55°C during off-cycle.

 •  Mount the compressor on a horizontal flat sur-

face with less than 3° slope.

 •  Verify that the power supply corresponds to the com-

pressor motor characteristics (see nameplate).

 •  When installing PSH, use equipment specifi-

cally reserved for HFC refrigerants which was 
never used for CFC or HCFC refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.
 •  The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

4 – Assembly

 •  In parallel assemblies of PSH the compressor 

requires a rigid mounting on the rails. Use the  
pre-mounted rigid spacers.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the compressor to the system as soon 

as possible to avoid oil contamination from 
ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 
remove the internal valve.

 •  The liquid injection valve must be fed by liquid, 

picked-up on the liquid line of the system, 
downstream the filter drier. 

 •  Protect the compressor and the liquid injection 

valve against heat while brazing the liquid line. 

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.
 •  Pressurize the system on HP side first and then 

on LP side. Never let the pressure on LP side ex-
ceed the pressure on HP side with more than 5 
bar. Such pressure difference could cause internal 
compressor damage.

 •  Do not use dye for leak detection.
 •  Perform a leak detection test on the complete 

system.

 •  The test pressure must not exceed : 

Models

LP side HP side

PSH 019.023.026.030.034.039

33.3bar 48.7bar

 
 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the sys-

tem.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

7 – Electrical connections

 
 

•  Switch off and isolate the main power supply. 
 •  All electrical components must be selected as per 

local standards and compressor requirements.

 •  The Danfoss scroll compressor only works cor-

rectly in one rotation direction. Line phases L1, 
L2, L3 must absolutely be connected to com-
pressor terminals T1, T2, T3 to avoid reverse ro-
tation.

 •  Use ø 4.8 mm (3/16”) screws and ¼” ring termi-

nals for the power connection. Fasten with 3 
Nm torque.

 •  The compressor must be connected to earth 

with the 5 mm earth terminal screw.

 •  

Connect the discharge temperature sensor 
cable plug to OCS.

 •  Connect the OCS to power supply and earth

 To avoid personal injury, with 230V OCS, do 

not forget to connect the earth, and to check for 
earth continuity.

 PSH019-023-026-030-034-039’s OCS inte-

grated phase protection/DGT protection func-
tion. Never disconnect the pre-installed wire 
between terminal pins and OCS. And make sure 
the OCS relay output is connected to system 
control safety chain.

8 – Filling the system

 •  Keep the compressor switched off.
 •  

Fill the refrigerant in liquid phase into the 
condenser or liquid receiver. The charge must 
be as close as possible to the nominal system 
charge to avoid low pressure operation and ex-
cessive superheat. Never let the pressure on LP 
side exceed the pressure on HP side with more 
than 5 bar. Such pressure difference could cause 
internal compressor damage.

 •  Keep the refrigerant charge below the indi-

cated charge limits if possible. Above this limit; 
protect the compressor against liquid flood-
back with a pump-down cycle or suction line 
accumulator.

 •  Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant 

charge limit (kg)

PSH019

5.9

PSH023.026.030.034.039

7.9

 

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 
with both generally and locally applicable regu-
lations and safety standards. Ensure that they 
are operational and properly set. 

 Check that the settings of high-pressure swit-

ches and relief valves don’t exceed the maximum 
service pressure of any system component.

 •  

A low-pressure switch is recommended to 
avoid vacuum operation. Minimum setting for 
PSH: 1.6 bar (absolute).

 •  Verify that all electrical connections are proper-

ly fastened and in compliance with local regu-
lations.

 •  Ensure that the liquid injection valve (LIV) coil 

is correctly positioned on the LIV body: one of 
the lock pins on the coil must fit into one of the 
dents on the valve body.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-
up and start-up after prolonged shutdown for 
belt type crankcase heaters (6 hours for surface 
sump heaters).

10 – Start-up

 •  Never start the compressor when no refrige-

rant is charged.

 •  All service valves must be in the open position.
 •  Balance the HP/LP pressure.
 •  Energize the compressor. It must start promp-

tly. If the compressor does not start, check wi-
ring conformity and voltage on terminals.

 •  If the internal overload protector trips out, it 

must cool down to 60°C to reset. Depending 
on ambient temperature, this may take up to 
several hours.

11 – Check with running compressor

 •  Check current draw and voltage.
 •  Check suction superheat to reduce risk of slug-

ging.

 •  Observe the oil level in the sight glass for about 

60 minutes to ensure proper oil return to the 
compressor.

 •   Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 
measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 
far as possible from the compressor. The com-
pressor must be operating during this process.

 •  Do not overcharge the system.
 •  Never release refrigerant to atmosphere.
 •  Before leaving the installation site, carry out 

a general installation inspection regarding 
cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

12 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent inju-
ry.Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.

To prevent system related compressor problems, 
following periodic maintenance is recommended:

Summary of Contents for PSH019

Page 1: ...p 8 Fran ais French p 11 Espa ol Spanish p 14 Italiano Italian p 17 Svenska Swedish p 20 Nederlands Dutch p 23 Irish Gaelic Irish p 26 Latvie u Latvian p 29 Eesti keel Estonian p 32 Elinika Greek p 3...

Page 2: ...must be handled with caution in the vertical position maximum offset from the vertical 15 Danfoss PSH019 023 026 030 034 039 compressors are protected against overheating and overloa ding by an inter...

Page 3: ...put is connected to system control safety chain 8 Filling the system Keep the compressor switched off Fill the refrigerant in liquid phase into the condenser or liquid receiver The charge must be as c...

Page 4: ...turned unsealed Rust water or leak detection dye inside the compressor Use of a refrigerant or lubricant not approved by Danfoss Any deviation from recommended instructions pertaining to installation...

Page 5: ...KS KS J1 J3 PT1000 OCS J5 J2 KS HP TH 180 s 85 52 019 A T1 T2 M T3 KA KA A1 A2 A3 LPS Forklaring Sikringer F1 Kompressorkontaktor KM Styrerel KA Sikkerhedsl serel KS Valgfri kort genstart timer 3 min...

Page 6: ...af anl gget Kompressoren skal v re slukket Fyld k lemiddel i v skefase i kondensatoren eller receiveren Fyldningen skal ligge s t t p den nominelle fyldning i anl gget som muligt for at undg lavtryksd...

Page 7: ...uktgarantien kan bortfalde i f lgende tilf l de Manglende typeskilt Udvendige ndringer i s rdeleshed boring svejsning delagte f dder og st dm rker Kompressoren har v ret bnet eller er returne ret uden...

Page 8: ...Verdichtersch tz KM Steuerrelais KA Sicherheits Sperrrelais KS Optionaler Kurzzyklus Timer 3 min 180 s Hochdrucksicherheitsschalter HP Trennschalter mit Sicherung Q1 Verdichtermotor M Druckgasthermos...

Page 9: ...n mit einem Drehmo ment von 3 Nm fest Der Verdichter muss mit einer 5 mm Erdungs schraube an den Erdleiter angeschlossen wer den Schlie en Sie den Kabelstecker des Verdich tungsendtemperaturf hlers an...

Page 10: ...ie sicher dass keine Lecks in der Anla ge vorhanden sind berpr fen Sie die Stromaufnahme des Kom pressors Vergewissern Sie sich anhand der Wartungs unterlagen dass die Anlage entsprechend den bisherig...

Page 11: ...gende Fusibles F1 Contacteur du compresseur KM Relais de contr le KA Relais de verrouillage de s curit KS Minuterie de cycle court en option 3 min 180 s Pressostat de s curit haute pression HP Sectio...

Page 12: ...terre et de v rifier la continuit la terre PSH019 023 026 030 034 039 Protection de phase int gr e OCS fonction de protection DGT Ne jamais d brancher le c ble pr install entre les broches de connexio...

Page 13: ...ve au produit signa lez toujours le num ro de mod le et le num ro de s rie La garantie du produit peut tre nulle dans les cas suivants Absence de plaque signal tique Modifications externes en particul...

Page 14: ...A1 A2 A3 LPS Leyenda Fusibles F1 Contactor del compresor KM Rel de control KA Rel de bloqueo de seguridad KS Temporizador de ciclo corto opcional 3 min 180 s Interruptor de seguridad de alta presi n H...

Page 15: ...a conexi n Funci n de protecci n integrada de fases del OCS y protecci n DGT para los modelos PSH019 023 026 030 034 y 039 No desconecte nunca el cable preinstalado entre las clavijas del terminal y e...

Page 16: ...s ambientales Comprobar que todas las conexiones el ctricas se encuentren correctamente fijadas Mantener limpio el compresor y comprobar la ausencia de xido y herrumbre en la carcasa del compresor los...

Page 17: ...F1 Contattore compressore KM Rel di controllo KA Rel blocco di sicurezza KS Timer opzionale ciclo breve 3 min 180 sec Pressostato di sicurezza alta pressione HP Sezionatore con fusibile Q1 Motore comp...

Page 18: ...rra PSH019 023 026 030 034 039 Protezione di fase integrata OCS funzione di protezione DGT Non scollegare in alcun caso il cavo preinstallato tra i morsetti e l OCS Assicurarsi che l uscita del rel de...

Page 19: ...ia no adeguatamente allacciati Mantenere il compressore pulito e verificare l assenza di ruggine e ossidazione sull invo lucro i tubi e i collegamenti elettrici del com pressore 13 Garanti Comunicare...

Page 20: ...iktighet och i uppr tt position maximal offset fr n uppr tt position 15 Kompressorerna i produktserien Danfoss PSH 019 023 026 030 034 039 r skyddade mot verhettning och verbelastning genom ett inbygg...

Page 21: ...Anslut hetgastemperaturgivarens kabelkon takt till OCS Anslut OCS till str mtillf rseln och jorden F r att undvika personskador n r 230 V OCS anv nds f r du inte gl mma att ansluta jorden och kontrol...

Page 22: ...systemet fungerar p ett s tt som r konsekvent med observationer fr n tidigare underh llsarbete och nuvarande milj f rh l landen Kontrollera att alla elektriska anslutningar sitter ordentligt H ll komp...

Page 23: ...9 A T1 T2 M T3 KA KA A1 A2 A3 LPS Legende Zekeringen F1 Compressorschakelaar KM Stuurrelais KA Veiligheidsrelais KS Optionele korte cyclustimer 3 min 180 s Veiligheidsschakelaar voor hoge druk HP Cont...

Page 24: ...stroomverbin ding Haal aan met een koppel van 3 Nm De compressor moet worden geaard door mid del van de 5mm aardschroef Sluit de kabelplug van de afvoertempera tuursensor aan op de OCS Sluit de OCS aa...

Page 25: ...en en correct zijn ingesteld Het systeem controleren op lekken Het stroomverbruik van de compressor contro leren Controleren of het systeem werkt op een manier die vergelijkbaar is met vorige onde rho...

Page 26: ...3 LPS Eochair Eolais Aidhn n F1 Comhbhr iteoir teagmh la KM Athsheachadadh rialaithe KA Riala glasta amach s bh ilteachta KS Uainead ir roghnach timthriall gairid 3 n m 180 s Lasc s bh ilteachta ardbr...

Page 27: ...nta a sheachaint OVS 230V n d an dearmad ar an talmh a cheangal n seice il as lean nachas talmhaithe Feidhm chosanta phas chomhth ite OCS feidhm chosanta DGT de chuid PSH019 023 026 030 034 039 N d sc...

Page 28: ...ha comhthimpeallacha Seice il go bhfuil gach ceangal leictreach feis tithe mar is ceart Coinnigh an comhbhr iteoir glan agus b ag cinn ti nach bhfuil meirg n ocsa di ar shliog n an comhbhr iteora fead...

Page 29: ...A3 LPS Apz m jumi Dro in t ji F1 Kompresora kontaktors KM Vad bas relejs KA Dro bas sl d a r jais relejs KS Papildu s cikla taimeris 3 min 180 s Augsta spiediena dro bas sl dzis HP Atvienots dro in t...

Page 30: ...ti izveidojiet sazem jumu jo sist ma OCS darbojas ar 230 V spriegumu un p rbaudiet vai tas ir izdar ts pareizi PSH019 023 026 030 034 039 OCS inte gr ta f zu aizsardz bas DGT aizsardz bas funk cija Ne...

Page 31: ...jumi jo proj m ir pien c gi nostiprin ti Nodro iniet lai kompresors b tu t rs un p r baudiet vai uz t korpusa caurul m vai elek triskajiem savienojumiem nav r sas un ok sid an s paz mju 13 Garantija N...

Page 32: ...KS KS J1 J3 PT1000 OCS J5 J2 KS HP TH 180 s 85 52 019 A T1 T2 M T3 KA KA A1 A2 A3 LPS Legend Kaitsmed F1 Kompressori kontaktor KM Juhtrelee KA Turvaluku v ljundrelee KS Valikuline l hikese ts kli tai...

Page 33: ...CS i vahele eelpaigaldatud juhet Ja veenduge et OCS i releev ljund oleks hen datud juhtimiss steemi ohutusahelaga 8 S steemi t itmine Hoidke kompressorit v ljal litatud re iimis Lisage jahutusaine ved...

Page 34: ...garantii ei pruugi j rgmistel tingimustel kehtida Andmesilt puudub V lised muudatused eriti puurimis keevita mis l hkumis ja m lkimisj ljed Kompressor on avatud v i tagastati katkise pit seriga Kompr...

Page 35: ...030 034 039 OCS L1 L3 L2 Q1 CONTROL CIRCUIT F1 F1 KM KA KA KS KS J1 J3 PT1000 OCS J5 J2 KS HP TH 180 s 85 52 019 A T1 T2 M T3 KA KA A1 A2 A3 LPS F1 KM KA KS 3 180 s HP Q1 M DGT LPS CC OCS 1 2 3 E F C...

Page 36: ...HP 5 bar LP HP PSH 019 023 026 030 034 039 33 3 bar 48 7 bar 6 LP HP 500 m Hg 0 67 mbar 7 Danfoss L1 L2 L3 T1 T2 T3 4 8 mm 3 16 3 Nm 5 mm OCS OCS OCS 230V OCS PSH019 023 026 030 034 039 DGT OCS OCS 8...

Page 37: ...Danfoss DCS CC 2018 02 37 FRCC PI 020 A2 27 60 1 5 mm 12 100 C 13 Danfoss 14 Danfoss...

Page 38: ...A A1 A2 A3 LPS Legenda Poistky F1 St ka kompresora KM Sp nacie rel KA Bezpe nostn blokovacie rel KS Volite n asova kr tkych cyklov 3 min 180 s Vysokotlakov bezpe nostn presostat HP Odp jacia poistka Q...

Page 39: ...syst mu 8 Plnenie syst mu Pri plnen mus by kompresor vypnut Chladivo v kvapalnej f zi pl te do kondenz to ra alebo do zbera e chladiva Mno stvo mus by o najbli ie k nomin lnej n plni syst mu aby sa p...

Page 40: ...jte typ model a v rob n slo Z ruka produktu m e by neplatn v nasle dovn ch pr padoch Ch baj ci t tok Boli uroben zmeny vonkaj ka najm v tanie zv ranie zlomen nohy alebo s vidie zn mky n razov Kompreso...

Page 41: ...Varovalke F1 Kontaktor kompresorja KM Nadzorni rele KA Rele varnostnega zaklepa KS Opcijski asomer kratkega cikla 3 min 180 s Visokotla no varnostno stikalo HP Izklopno stikalo z varovalko Q1 Motor k...

Page 42: ...Polnjenje sistema Kompresor naj bo izklopljen Vlijte hladilno sredstvo v teko i obliki v konden zator ali posodo za teko ino Koli ina polnjenja mora biti im bli je nominalni koli ini sistema da se iz...

Page 43: ...sko tevilko Jamstvo je lahko ni no v teh primerih Manjka napisna plo ica Spremembe zunanjosti zlasti vrtanje varjenje polomljene no ice in znaki udarcev Vrnjen kompresor je odprt ali pa nima oznake ki...

Page 44: ...78 0 3 0 7 bar 15 Danfoss PSH019 023 026 030 034 039 OCS L1 L3 L2 Q1 CONTROL CIRCUIT F1 F1 KM KA KA KS KS J1 J3 PT1000 OCS J5 J2 KS HP TH 180 s 85 52 019 A T1 T2 M T3 KA KA A1 A2 A3 LPS F1 KM KA KS 3...

Page 45: ...026 030 034 039 33 3bar 48 7bar 6 500 m Hg 0 67 mbar 7 Danfoss Line phases L1 L2 L3 T1 T2 T3 4 8 mm 3 16 3Nm 5 mm OCS OCS 230V OCS PSH019 023 026 030 034 039 s OCS DGT OCS OCS 8 5 bar Kg PSH019 5 9 P...

Page 46: ...26 030 034 039 OCS L1 L3 L2 Q1 CONTROL CIRCUIT F1 F1 KM KA KA KS KS J1 J3 PT1000 OCS J5 J2 KS HP TH 180 s 85 52 019 A T1 T2 M T3 KA KA A1 A2 A3 LPS F1 KM KA KS 3 min 180 s HP Q1 M DGT LPS CC OCS 1 2 3...

Page 47: ...3 4 PSH 5 5 PSH 019 023 026 030 034 039 33 3 bar 48 7 bar 6 500 m Hg 0 67 mbar 7 Danfoss L1 L2 L3 T1 T2 T3 4 8 mm 3 16 3 Nm 5 OCS OCS OCS 230 V OCS DGT PSH019 023 026 030 034 039 OCS OCS 8 5 kg PSH01...

Page 48: ...48 Danfoss DCS CC 2018 02 FRCC PI 020 A2 44 60 1 5 12 100 C 13 Danfoss 14 Danfoss...

Page 49: ...T1000 OCS J5 J2 KS HP TH 180 s 85 52 019 A T1 T2 M T3 KA KA A1 A2 A3 LPS Legend Siguran e F1 Contactor compresor KM Releu de comand KA Releu de blocare de siguran KS Cronometru op ional cu ciclu scurt...

Page 50: ...ol al sistemului 8 Umplerea sistemului P stra i compresorul oprit Turna i agent frigorific n faz lichid n conden sator sau recipientul pentru lichid nc rcarea trebuie s fie c t mai aproape posibil de...

Page 51: ...i ntotdeauna num rul modelului i num rul de serie mpreun cu orice reclama ie legat de acest produs Garan ia produsului poate fi nul n urm toarele situa ii Absen a pl cu ei de caracteristici Modific r...

Page 52: ...1 T2 M T3 KA KA A1 A2 A3 LPS Jelmagyar zat Olvad biztos t k F1 Kompresszor m gneskapcsol KM Vez rl rel KA Biztons gi kiz r rel KS K l n rendelhet r vid ciklus id z t 3 min 180 s Biztons gi t lnyom s k...

Page 53: ...039 integr lt OCS f zisv delme DGT v delmi funkci ja Soha ne k sse ki az el re telep tett vezet ket a csat lakoz rintkez k s az OCS k z l Tov bb biz tos tsa hogy az OCS rel kimenet kapcsol djon a ren...

Page 54: ...kre vonatkoz garancia megsz nik az al bbi esetekben Az adatlap hi nyzik K ls m dos t sok k l n sen f r s hegesz t s let rt l b s t d si nyomok A kompresszort felnyitott k vagy nem lez rt llapotban k l...

Page 55: ...ki KM Przeka nik sterowania KA Przeka nik blokady bezpiecze stwa KS Opcjonalny regulator czasowy kr tkich cykli 3 min 180 s Wy cznik bezpiecze stwa wysokiego ci nienia HP Od cznik z bezpiecznikami Q1...

Page 56: ...peratury t oczenia do uk adu sterowania OCS Pod czy uk ad sterowania OCS do zasilania i uziemienia W celu zabezpieczenia przed obra eniami w przypadku pod czenia uk adu sterowania OCS do napi cia zasi...

Page 57: ...spr arki Upewni si czy uk ad pracuje w spos b sp jny z poprzednimi zapisami dotycz cymi konserwacji i warunkami otoczenia Sprawdzi czy wszystkie po czenia elektry czne s w dalszym ci gu odpowiednio p...

Page 58: ...its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All trademarks in this...

Reviews: