background image

REP24 CO1

GB

Installation Instructions 
User Instructions 

Electronic Proportional Heat / Cool Thermostat

Summary of Contents for REP24 CO1

Page 1: ...REP24 CO1 GB Installation Instructions User Instructions Electronic Proportional Heat Cool Thermostat ...

Page 2: ...2 Index INDEX Installation Instructions 3 6 User Instructions 8 GB ...

Page 3: ... Installation Instructions Specification GB Thermostat features Temperature Range 10 30 C Thermostat Heat Standby Cool Selector Yes Power Supply 24 Vac 15 50 60Hz Fan Output 3 1 A 10 230Vac Type 1B Control Method P I 2k Proportional Band Dimensions mm 110 wide x 90 high x 40 high Design Standard EN60730 2 9 Rated Impulse Voltage 2 5Kv Ball Hardness Test 75 C Control Pollution Situation Degree 2 Te...

Page 4: ...iring Product overview This thermostat is designed for fan coil and chilled beam applications alongside proportional valves and actuator systems where a 0 10v proportional control output is required The thermostat also has a single speed fan output The operational mode of the fan auto or continuous is selected at time of installation via DIL switches accessible on the rear of the unit When the uni...

Page 5: ...Electronics Common In Heating 24 Vac N Cool Heat Cooling 0 10V outputs or 0V 24V A B Installation Instructions GB Commissioning Prior to re fitting the thermostat to the wallplate the DIL switches on the rear of the unit must be set to the desired setting ...

Page 6: ...ture is 0 2 C or more above below depending on heat cool mode setpoint When temperature reaches setpoint the fan will switch off Switch 2 MOT Motorised valve actuator selection WAX Wax valve actuator selection Mounting thermostat to the wallplate To mount the thermostat to the wallplate align the tabs on the top of the thermostat with the apertures in the wallplate and hinge the thermostat down pr...

Page 7: ...nge turn the setting dial to 3 and remove knob Position the locking springs on the rear of the dial to the desired position and re mount the knob ensuring that number 3 on the dial aligns with the reference mark on the case Installation Instructions GB ...

Page 8: ...n becomes active at 8 C If the temperature in the room drops below 8 C then the output will activate When frost protection is activated the right LED will turn orange Standby Mode In cooling mode the standard frost protection is not available instead there is standby mode When the dial is turned past 10 C the unit enters standby mode and cooling will be inactive until the dial is turned up past 10...

Page 9: ...n when thermostat is powered and fan is in continuous mode LED lit orange when fan is running in auto mode LED off when setpoint reached LED red when heating LED green when cooling LED orange when frost protection activated Temperature setting dial Frost protection mode ...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...12 Part No 25285v01 07 08 www danfoss com BusinessAreas Heating 2004 108 EC 2006 95 EC ...