background image

Installation guide

Thermostat

 

RT 101, RT 102

017

R9

31

8

017

R9

31

8

© Danfoss | DCS (jmn) | 2015.11

IC.PI.P10.R1.53 | 520B4023 | 1

RT 101

Danfos

s

17-5027.10

Fig. 2

Fig. 3

RT 101 – RT 102

Fig. 1

Fig. 4

ENGLISH

Thermostats Types RT 101, RT 102
Fig. 1 and 2

 

Max. ambient temperature: 70 °C 
Max. temperature of sensor : 300 °C

 

INSTALLATION
A set of Pg13.5 cable gland is attached to 
the RT in a separate bag. To ensure IP66 
(units with automatic reset) or IP54 (units 
with external reset) grade of RT enclosure 
it is necessary to assemble this gland as 
shown in the fig. 3. If this gland is not used 
with a cable, a metal blinding should be 
also assembled.

SETTING 
Fig. 4

A. Range setting
B. Differential obtained
C. Differential setting

 

The thermostat should be set according to 
the function - make or break - to take place 
on a drop in temperature (range setting).
Setting is done by rotating the knob (5), at 
the same time reading the main scale (9).
The differential is set by rotating the 

differential adjusting nut (19) to the value 
indicated by the nomogram in Fig. 4. The 
maximum operating temperature is thus 
the sum of the temperature setting and 
the differential.

Example
It is desired to control the temperature of 
an oil-fired central heating boiler by the 
use of an RT 101

Maximum temperature: 76 °C

  

Minimum temperature: 70 °C 
Differential: 76 °C - 70 °C = 6 °C

1.  Connect the oil burner to terminals 2-1 
  of the thermostat
2.  Set the thermostate for 70 °C by rotating 
  the knob (5)
3.  Set the differential adjusting nut (19) 
  between figures 3 and 4, as indicated by 
  the nomogram in fig. 4.

DANSK

Termostater Type RT 101, RT 102
Fig. 1 og 2 

Omgivelses temperatur: 70 °C 
Max. følertemperatur: 300 °C

INSTALLATION
Et sæt Pg13,5 kabelforskruning er vedlagt
produktet i en separat pose. For at sikre
kapslingsgrad IP66 (enheder med automa-
tisk reset) eller IP54 (enheder med ekstern
DANSK RESET) er det nødvendigt at mon-
tere denne kabelforskruning som vist i fig. 3. 
Hvis denne kabelforskruning ikke bruges
sammen med et kabel, bør der monteres
en blindprop (metal skive).

INDSTILLING 
Fig. 4

A. Områdeindstilling
B. Opnået differens
C. Differensindstilling

 

Termostaten indstilles efter den funktion 
- slutte eller bryde - som skal ske ved 
faldende temperatur (områdeindstilling). 
Selve indstillingen udføres med 
håndknappen (5) under samtidig aflæsning 
af hovedskalaen (9).
Differensen indstilles med differensrullen 
(19) efter nomogrammet i figur 4. Højeste 
funktionstemperatur er således lig sum-
men af indstillingstemperatur og differens.

Eksempel
Temperaturen i en oliefyret centralvarme-