Pressure switch
Technical data
Fig. 1 and 2
Type
Operating
range for
LT bulb
[°C]
Max.
bulb
temp.
[°C]
Mechnical
contact
differential
Regulation
range
∆
t
[°C]
RT 270
-30 – 40
65
2
0 – 15
RT 271
20 – 100
200
3
0 – 20
Installation
A set of Pg13.5 cable gland is attached to
the RT in a separate bag. To ensure IP66
(units with automatic reset) or IP54 (units
with external reset) grade of RT enclosure
it is necessary to assemble this gland as
shown in the fig. 3. If this gland is not used
with a cable, a metal blinding should be
also assembled.
Fitting
Locate the LT bulb (1) in the coldest me-
dium and the HT bulb (32) in the warmest
medium.
Setting
The differential required between tem-
peratures is set by rotating the nut (5), at
the same time reading the main scale (9).
Turning the nut (5) is done most easily with
a screwdriver.
Example
It is desired to cool a potato store by
means of ventilation with outside air when
the outdoor temperature is lower than the
indoor temperature.
Connect the fan to the RT 270 thermostat
terminals 1-4. Locate the LT bulb (1) in the
open, screened against the sun rays, and
the HT bulb (32) in the store.
Set the thermostat, for example, for a dif-
ferential of 3 °C. The thermostat will then
start the fan when the outdoor temperature
is 3 °C + 2 °C = 5 °C lower than the cold
store temperature. The 2 °C
is the contact
differential. When the difference between
the outdoor and indoor temperature has
been reduced to 3 °C, the switch changes
over, and the fan is cut out.
Pressostater
Tekniske data
Fig. 1 og 2
Type
LT-føler
enhedens
funktions-
område
[°C]
Max.
føler-
tepe-
ratur
[°C]
Fast
kontakt-
differens
Indstillings-
område
∆
t
[°C]
RT 270
-30 – 40
65
2
0 – 15
RT 271
20 – 100
200
3
0 – 20
Montage
Et sæt Pg13,5 kabelforskruning er vedlagt
produktet i en separat pose. For at sikre
kapslingsgrad IP66 (enheder med automa-
tisk reset) eller IP54 (enheder med ekstern
DANSK
RESET) er det nødvendigt at montere
denne kabelforskruning som vist i fig. 3.
Hvis denne kabelforskruning ikke bruges
sammen med et kabel, bør der monteres
en blindprop (metal skive).
Montering
Anbring LT-føleren (1) i det koldeste
medium og HT-føleren (32) i det varmeste.
Indstilling
Den ønskede temperaturdifferens
indstilles ved at dreje skiven (5) under
samtidig aflæsning af hovedskalaen (9).
Skiven (5) drejes lettest med en
skruetrækker.
Eksempe
Et lagerrum, f.eks. indeholdende kartofler,
ønskes afkølet ved ventilering med udeluft,
når udetemperaturen er lavere end
indetemperaturen.
Tilslut ventilatoren til RT 270 termostatens
klemmer 1-4. Anbring LT-føleren (1) i det fri
skærmet mod solstråler, og HT-føleren (32)
i lagerrummet.
Indstil termostaten på f.eks. 3 °C differens.
Termostaten vil derpå starte ventilatoren
når udetemperaturen er 3 °C + 2 °C = 5 °C
lavere end temperaturen i lagerrummet.
De 2 °C er kontaktdifferensen. Når forskellen
mellem ude og indetemperaturen er
formindsket til 3 °C sker kontaktskifte og
ventilatoren kobles ud.