20
AB243586442172en-001401
Electrical data, connections and wiring
Motor protection
Compressor models SH090-105-120-140-161-184
have been provided with an internal overload
motor protection to prevent against excessive
current and temperature caused by overloading,
low refrigerant flow or phase loss. The cutout
current is the MCC value listed in section “Three
phase electrical characteristics”.
The protector is located in the star point of the
motor and, should it be activated, will cut out all
three phases. It will be reset automatically.
While not compulsory, an additional external
overload is still advisable for either alarm or
manual reset.
Then it must be set below MCC value (at max
operating current:
• when the motor temperature is too high, then
the internal protector will trip
• when the current is too high the external
overload protection will trip before the internal
protection therefore offering possibility of
manual reset.
Compressor models SH180-240-295-380-485 are
delivered with a pre installed motor protection
module inside the terminal box. This device
provides for efficient and reliable protection
against overheating and overloading as well as
phase loss/reversal.
The motor protector comprises a control module
and PTC sensors embedded in the motor
winding. The close contact between thermistors
and windings ensures a very low level of thermal
inertia.
The motor temperature is being constantly
measured by a PTC thermistor loop connected
on S1-S2. If any thermistor exceeds its response
temperature, its resistance increases above the
trip level (4,500 Ω) and the output relay then
trips – i.e. contacts M1-M2 are open. After cooling
to below the response temperature (resistance
< 2,750 Ω), a 5-minute time delay is activated.
After this delay has elapsed, the relay is once
again pulled in – i.e. contacts M1-M2 are closed.
The time delay may be cancelled by means
of resetting the mains (L-N -disconnect) for
approximately 5 sec.
A red/green twin LED is visible on the module.
A solid green LED denotes a fault free condition.
A blinking red LED indicates an identifiable fault
condition:
PTC overheat
Delay timer active (after PTC over temp.)
Use a phase meter to establish the phase
orders and connect line phases L1, L2 and L3
to terminals T1, T2 and T3, respectively. The
compressor will only operate properly in a single
direction, and the motor is wound so that if the
connections are correct, the rotation will also be
correct.
Phase sequence and reverse
rotation protection
Compressor model
Overheating
protection
Over current
protection
Locked rotor
protection
Phase reversal protection
SH 090 - 105 - 120 - 140- 161
- 184
Internal motor protection
Internal reverse vent
SH 180
Electronic module located in terminal box
Internal reverse vent
SH240 - 295 - 380-485
Electronic module located in terminal box
Appr. 1 second
40ms
40ms
460ms
460ms
Appr. 1 second
920ms
80ms
Application Guidelines
Summary of Contents for SH485